background image

 

 

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

 

PAK200608_01F   Jan 2021                     ©2019 ELMDENE INTERNATIONAL LTD  

 

I

NSTALLATION 

 

 

 

This  unit  is  only  suitable  for  installation  as  permanently  connected  equipment.  The  PSU  is  NOT  SUITABLE  for 
external installation.  
 
This unit must be fed from a mains power source having a separate (approved) disconnect device and fitted with a 
fuse  or  other  over-current  protection  device  rated  at  5  A  maximum.  Ensure that  the  disconnect  device  used  has 
appropriate earth fault protection to the applicable standard. 

 

Where the PSU is used to provide power to a fire alarm circuit, the mains isolation and disconnect device should be 

provided solely for this purpose and be suitably marked “FIRE ALARM –

 

DO NOT TURN OFF”. All cabling should meet 

national and local fire system installation regulations, e.g. FP200 type cable for high integrity installations. 

 

Where  the  PSU  is  used  for  other  applications,  it  should  be  installed  according  to  all  relevant  safety  regulations 
applicable to that application. 

 

Where the GEN PSU Fault and EPS Fault outputs are used, they should only be connected to circuits having voltages 
less than 60V dc. 
 

Cable Sizing 

1)

 

Mains input cable must be to the applicable standard with a 5A or greater current capacity, i.e. 0.75mm

2

 

nominal conductor area, having a minimum operating voltage of 300/500V ac. 

2)

 

The low voltage output cable must be sized to carry the rated load current to the devices connected to the 
PSU. 

3)

 

All cabling should be securely fastened in position. 

 
Mounting the Module

  

4)

 

Fix  the  module  into  the  chosen  enclosure  using  3  x  fixing  points  as  per  Fig  1  (all  fixings  must  be  used). 
Ensure sufficient space for heat dissipation and adequate ventilation to avoid overheating of the unit or 
associated batteries. 

 
Figure 1 

 Fixing Points 

 
 
 
 
 
 
 
 

 
 

C

OMMISSIONING

 

 

 

Mains Power Up 

1)

 

With no external connections made to the PSU, connect the mains input wires to the terminal block, 

ensuring that the mains isolator (disconnect device) is open

. Fasten wiring in place with cable tie to 

saddle. 

Note: Equipment must be earthed.

 

2)

 

Apply mains input. Confirm that all LED indicators flash on briefly proving integrity of indicating circuits. 
Ensure that the green Mains LED then stays illuminated and that the yellow Fault LED flashes after 
approximately 3s (indicating a disconnected battery). 

3)

 

Disconnect the mains power. 

 

Load Output and Remote Signalling 

4)

 

Connect the EPS and GEN PSU Fault outputs to the appropriate inputs of control equipment if remote fault 
monitoring is required. 

5)

 

Connect the load (output) wiring as shown in Figure 2.  

Module Dimensions 

150 x 207 x 52 (mm) 

75mm 

12mm 

128mm 

98mm 

Summary of Contents for STX2402-MOD

Page 1: ...mature battery failure when operating from standby for extended periods Two sets of volt free solid state relay fault output signal i loss of mains and ii battery fault charger fault and loss of outpu...

Page 2: ...2 5A 2 0A 2 5A 1 8A Battery Capacity eg PowerSonic model Yuasa model Interlogix model 2 x 2 1Ah 12V PS12021 NP2 1 12 2 x 7Ah 12V PS12070 NP7 12 2 x 17 18Ah 12V PS12170 NP17 12 BS131N Battery Charging...

Page 3: ...S Fault GEN Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains C...

Page 4: ...ctive Battery charging normally but 90 of full charge None 2 PULSES ON No Battery Battery disconnected Battery fuse blown Battery heavily discharged Check battery connections Check battery fuse Check...

Page 5: ...d with a 5A or greater current capacity i e 0 75mm2 nominal conductor area having a minimum operating voltage of 300 500V ac 2 The low voltage output cable must be sized to carry the rated load curren...

Page 6: ...and Negative terminals of the batteries to the PCB terminals Batt and Batt using the cables provided See Figure 2 and 3 13 Connect the battery temperature sensor two white wires to the PCB terminals T...

Page 7: ...a battery fault or a GEN PSU fault the corresponding Fault signal contacts will open If the output of the PSU fails the cause of the failure should be investigated e g short circuit load connection o...

Page 8: ...oduct any batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries safely for o...

Reviews: