4
Technical Support: +44(0)23 9269 6638 (option 3)
PAK200583_02C Jan 2021 ©2019 ELMDENE INTERNATIONAL LTD
Fault Diagnostic table
–
Internal - Engineer
Orange LED
Diagnostic
Green LED
Mains
Condition
Possible Cause
Action
O
FF
O
N
Normal
operation
Mains present
Battery fully charged
None
O
FF
Standby
Operation
Mains Lost. No faults present
Battery driving load
Investigate loss of mains
F
LASH
C
ONTINUOUS
O
N
or O
FF
No output
Output fuse blown
Output overload
Output short circuit
Check and replace output
fuse
Disconnect output load and
test load
1
P
ULSE
O
N
Battery
Charging
No faults active
Battery charging normally but
< 90% of full charge
None
2
P
ULSES
O
N
No Battery
Battery disconnected
Battery fuse blown
Battery heavily discharged
Check battery connections
Check battery fuse
Check battery condition
Replace battery if aged
O
FF
Low Battery
Volts
Standby Mode
Battery almost discharged
Restore mains
3
P
ULSES
O
N
or O
FF
Battery Fault
High impedance in battery
connection
Battery internal fault
Check battery connections
for corrosion. Replace
battery if aged
4
P
ULSES
O
N
or O
FF
Charger Fault
Internal failure of battery charger
Return to manufacturer
5
P
ULSES
O
N
or O
FF
Battery
Temperature
Probe Fault
Battery temperature monitor
disconnected or damaged
PSU running in Safe Mode
Check temperature sensor
connections and condition
of sensor.
Replace if suspect
I
NSTALLATION
This Power Supply Unit (PSU) is only suitable for installation as permanently connected equipment (Power Supply
Equipment / PSE). The PSE is NOT SUITABLE for external installation. This product is designed for the use in
automatic fire detection and fire alarm systems. If the PSE is used as a power supply for Control and Indicating
Equipment (CIE), the PSE shall be installed no further than 10cm from the CIE, and close coupled by conduit.
This unit must be fed from a mains power source having a separate (approved) disconnect device and fitted with a
fuse or other over-current protection device rated at 5 A maximum. Ensure that the disconnect device used has
appropriate earth fault protection to the applicable standard.
Where the PSE is used to provide power to a fire alarm circuit, the mains isolation and disconnect device should be
provided solely for this purpose and be suit
ably marked “FIRE ALARM –
DO NOT TURN OFF”. All cabling should meet
national and local fire system installation regulations, e.g. FP200 type cable for high integrity installations.
Where the PSE is used for other applications, it should be installed according to all relevant safety regulations
applicable to that application.
Where the GEN PSU Fault and EPS Fault outputs are used, they should only be connected to circuits having voltages
less than 60 Vdc.
Cable Sizing
1)
Mains input cable must be to the applicable standard with a 5 A or greater current capacity, i.e. 0.75 mm
2
nominal conductor area, having a minimum operating voltage of 300/500V ac.
2)
The low voltage output cable must be sized to carry the rated load current to the devices connected to the
PSE.
3)
Mains input and low voltage output cables should be routed to use different entry / exit holes in the case.
Bushes should be used to protect cable sheaths from chafing. Ensure that these bushes are correctly sized
(i.e. close fitting with respect to cable sizing). Note that the bushes should meet a minimum flammability
specification of UL94 HB.
4)
All cabling should be securely fastened in position using a cable tie through the saddles provided.