PAK200583_02C Jan 2021                        ©2019 ELMDENE INTERNATIONAL LTD  

Fault Diagnostic table 

 Internal - Engineer 

Orange LED 

Diagnostic 

Green LED 

Mains 

Condition 

Possible Cause 

Action 

O

FF

 

O

N

 

Normal 

operation 

Mains present 
Battery fully charged 

None 

O

FF

 

Standby 

Operation 

Mains Lost. No faults present 
Battery driving load 

Investigate loss of mains 

F

LASH 

C

ONTINUOUS

 

O

N

 or O

FF

 

No output 

Output fuse blown 
Output overload 
Output short circuit 

Check and replace output 
fuse 
Disconnect output load and 
test load 

1

 

P

ULSE

 

O

N

 

Battery 

Charging 

No faults active 
Battery charging normally but  
< 90% of full charge 

None 

2

 

P

ULSES

 

O

N

 

No Battery 

Battery disconnected 
Battery fuse blown 
Battery heavily discharged 

Check battery connections 
Check battery fuse 
Check battery condition 
Replace battery if aged 

O

FF

 

Low Battery 

Volts 

Standby Mode 
Battery almost discharged 

Restore mains 

3

 

P

ULSES

 

O

N

 or O

FF

 

Battery Fault 

High impedance in battery 
connection 
Battery internal fault 

Check battery connections 
for corrosion. Replace 
battery if aged 

4

 

P

ULSES

 

O

N

 or O

FF

 

Charger Fault 

Internal failure of battery charger 

Return to manufacturer 

5

 

P

ULSES

 

O

N

 or O

FF

 

Battery 

Temperature 

Probe Fault 

Battery temperature monitor 
disconnected or damaged 
PSU running in Safe Mode  

Check temperature sensor 
connections and condition 
of sensor. 
Replace if suspect 

 

I

NSTALLATION 

 

 

 

This Power Supply Unit (PSU) is only suitable for installation as permanently connected equipment (Power Supply 
Equipment / PSE). The PSE is NOT SUITABLE for external installation. This product is designed for the use in 
automatic fire detection and fire alarm systems. If the PSE is used as a power supply for Control and Indicating 
Equipment (CIE), the PSE shall be installed no further than 10cm from the CIE, and close coupled by conduit. 

 

This unit must be fed from a mains power source having a separate (approved) disconnect device and fitted with a 
fuse or other over-current protection device rated at 5 A maximum. Ensure that the disconnect device used has 
appropriate earth fault protection to the applicable standard. 

 

Where the PSE is used to provide power to a fire alarm circuit, the mains isolation and disconnect device should be 
provided solely for this purpose and be suit

ably marked “FIRE ALARM –

 

DO NOT TURN OFF”. All cabling should meet 

national and local fire system installation regulations, e.g. FP200 type cable for high integrity installations. 

 

Where the PSE is used for other applications, it should be installed according to all relevant safety regulations 
applicable to that application. 

 

Where the GEN PSU Fault and EPS Fault outputs are used, they should only be connected to circuits having voltages 
less than 60 Vdc. 
 

Cable Sizing

 

1)

 

Mains input cable must be to the applicable standard with a 5 A or greater current capacity, i.e. 0.75 mm

2

 

nominal conductor area, having a minimum operating voltage of 300/500V ac. 

2)

 

The low voltage output cable must be sized to carry the rated load current to the devices connected to the 
PSE. 

3)

 

Mains input and low voltage output cables should be routed to use different entry / exit holes in the case. 
Bushes should be used to protect cable sheaths from chafing. Ensure that these bushes are correctly sized 
(i.e. close fitting with respect to cable sizing). Note that the bushes should meet a minimum flammability 
specification of UL94 HB. 

4)

 

All cabling should be securely fastened in position using a cable tie through the saddles provided. 

Summary of Contents for STX2401-C

Page 1: ...elay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an optional plug in serial interface that can provide diagnostic and fault reporting...

Page 2: ...ttery Capacity e g PowerSonic model Yuasa model 2 x 1 2 Ah 12 V PS12021 NP1 2 12 2 x 7 Ah 12 V PS12070 NP7 12 Battery Charging Constant current bulk charging to 80 capacity within 24 hours Float charg...

Page 3: ...ault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN Fa...

Page 4: ...systems If the PSE is used as a power supply for Control and Indicating Equipment CIE the PSE shall be installed no further than 10cm from the CIE and close coupled by conduit This unit must be fed f...

Page 5: ...wall fixings are appropriate to support this weight 7 The product should be mounted no further than 10 cm from the control and indicating equipment close coupled by conduit if it is being used to pow...

Page 6: ...ault LED flashes after approximately 3 s indicating a disconnected battery 3 Disconnect the mains power Load Output and Remote Signalling 4 Connect the EPS and PSU Fault outputs to the appropriate inp...

Page 7: ...ull alarm condition Note ensure batteries have sufficient charge to support the system under full load Final 18 Reconnect the mains Verify that the green Mains LED illuminates and the yellow Fault LED...

Page 8: ...of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries saf...

Reviews: