Technical Support: 023 9269 6638 

                        

PAK200838_03A  Feb 2019                           ©2019 ELMDENE INTERNATIONAL LTD 

  

 
Table 2: Summary of symptoms and possible faults 

 

Symptom 

Fault 

Action 

Sounder cannot be silenced 

BL+ holdoff input is not > 7V 

Verify that the control panel is biasing BL+ to 
>7V in standby mode. 

Holdoff supply (ALIM) is disconnected 
or very low 

Check integrity of holdoff (ALIM) supply 

Sounder stops after 5s 

Incorrect timer link setting 

Set correct timer jumper links. 

Tamper condition indicated 
at control panel or cannot 
SET control panel 
(due to sounder tamper) 

Tamper outputs (AP) not connected 
correctly to panel. 

Refer to connection diagram Figure 2 

Tamper switch not closed 

Check cover 

No response to BL+ input 

Battery not connected 

Check battery connections to terminal block 

Battery faulty or voltage low 

Replace battery 

Battery charger faulty 

Return unit to manufacturer 

Audible alarm stops before 
timeout. 

Battery level very low 

Recharge battery 

 

 

D

ISPOSAL OF 

P

RODUCT AT 

E

ND OF 

L

IFE

 

 

 

This product falls within the scope of EU Directives 2012/19/EU Waste Electrical and Electronic Equipment 
(WEEE)  and  2013/56/EU  (Battery).  At  the  end  of  life,  the  product  must  be  separated  from  the  domestic 
waste stream and disposed via an appropriate approved WEEE disposal route in accordance with all national 
and local regulations. 
Before disposal of the product, the battery must be removed, and disposed of separately via an appropriate 
approved battery disposal route in accordance with all national and local regulations. Package used batteries 
safely for onward transport to your supplier, collection point or disposal facility. 

 

Caution:  Risk of fire or explosion 

if exposed battery wires are allowed to touch. 

 

See  Specification  for  battery  type  information.  The  battery  is  marked  with  the  crossed  out  wheelie  bin 
symbol, which may include lettering to indicate cadmium (Cd), lead (Pb), or mercury (Hg).  

 

The packaging supplied with this product may be recycled. 

  Please dispose of the packaging appropriately.

 

 

For more information see: 

www.recyclethis.info

 

 

 
 
 
 
 

 

F

AULT 

F

INDING

 

 

Summary of Contents for SI500

Page 1: ...ics module Compliant with NF EN50131 4 2009 RTC50131 4 2011 Note For security reasons the tamper output of the siren is triggered when the siren detects Removal of ALIM charging supply Removal 0V supp...

Page 2: ...Hold off charging supply will cause the sounder to self activate but a tamper signal is not generated A tamper signal is only generated in the event that the cover is unscrewed removed FUNCTIONAL INFO...

Page 3: ...battery lead after ALIM supply is applied HP Speaker connections ALIM Permanent positive hold off supply ALIM Permanent negative hold off supply AP Tamper output return connections to control panel Se...

Page 4: ...itable mounting position for the SI500 sounder 2 Drill holes as required for fixing the backplate to the wall and for cable entry to the rear of the unit 3 Route cable from control panel through cable...

Page 5: ...tenance visit 1 Correct operation of sounder from control panel signal 2 Correct operation of cover and rear tampers 3 Remove the ALIM supply from the control panel and check that the internal battery...

Page 6: ...low Recharge battery DISPOSAL OF PRODUCT AT END OF LIFE This product falls within the scope of EU Directives 2012 19 EU Waste Electrical and Electronic Equipment WEEE and 2013 56 EU Battery At the end...

Page 7: ...ominally Battery Deep DIscharge Protection 9 5V nominal resulting in de activation of sounder Battery autonomy duration 36h Tamper detection Cover switch Tamper Output Max 2A 30Vdc rated Sound Trigger...