Technical Support Line +44 (0)23 9269 6638 (Option 3) POE-ULTRAPOD™ PAK200903_02B Nov 2017 © 2017 Elmdene International Ltd
Power Up
1)
Attach correctly rated load cable to load equipment and fasten using cable ties – Note polarity
2)
Attach suitable Ethernet cable from PoE++ source to
POE IN
RJ45 connector (100m max from PSE)
3)
Attach suitable Ethernet cable between IP device and
DATA
RJ45 connector (if required)
4)
Loop battery cable through supplied ferrite (1 turn) and attach to
BATT
terminal block, fasten with
cable ties
NOTE:
ensure correct polarity of battery connections:
+
use
Red
lead,
-
use
Black
lead
Fig. 2 Position of ferrite
5)
Connect charged 12V battery 17Ah (max) to the other end of battery cable.
6)
Observe Green LED is ON when PoE is present
7)
Observe Load equipment indicates power is present
8)
Remove
POE IN
cable and observe load equipment continues to indicate power is present
9)
Reconnect PoE INPUT cable
Signalling
1)
Connect fault outputs to appropriate input of Control and Indicating Equipment (CIE) if required
2)
Close cover and secure using fastening key provided
O
PERATING
I
NSTRUCTIONS
In the event of loss of PoE++ to the POE-ULTRAPOD™, the PoE Fault signal contact will open and the
Green LED will turn off, the POE-ULTRAPOD™ will continue to deliver up to 13.8V 3A of power to the
load for up to 4 hours (dependant on charge state or capacity of 17Ah battery).
If the output of the POE-ULTRAPOD™ fails, the cause of the failure should be investigated e.g. short
circuit load, connection of a deeply discharged battery. The fault should be rectified before restoring
power to the POE-ULTRAPOD™. If any of the fuses require replacing, ensure the correct fuse rating and
type is used.
Battery charging will only start after a compliant PoE power source is connected to POE-ULTRAPOD™, it
will NOT start up on battery. Ensure only 12V battery is fitted to the system.
M
AINTENANCE
This unit is intended for use by Service Personnel only. There are NO USER SERVICEABLE parts inside.
There is no regular maintenance required of the POE-ULTRAPOD™ other than periodic testing, and
replacement of the standby battery.
Reference should be made to the battery manufacturer's documentation to determine
typical/expected battery life with a view to periodic replacement of the battery.