2
Technical Support: +44(0)23 9269 6638 (option 3)
PAK200546_03A Mar 2020 ©2020 ELMDENE INTERNATIONAL LTD
S
PECIFICATION
Mains Input
Rated Voltage / (Operational Voltage)
100-240Vac / (90 – 265Vac)
Frequency
50/60Hz
Input current
GEN3-08
&
GEN3-18 < 1.0A
at full load
Fuse
T2A 20mm HRC
Output
GEN3-08-y
GEN3-18-y
Voltage at full load
Mains power
Battery standby
13.2 –14.2Vdc (13.8Vdc nominal)
9.8 – 13.0Vdc
Ripple
<400mV pk – pk max @ Rated Voltage
Fuse:
Load
Battery
F1.0A
F1.0A
F1.6A
F1.6A
Continuous Output Current
*
Mains
Battery for 12 hours
30 hours
60 hours
1.0 A
0.60A with 8Ah Battery
0.26A with 8Ah Battery
0.13A with 8Ah Battery
1.5A
1.5A with 18Ah Battery
0.6A with 18Ah Battery
0.3A with 18Ah Battery
*See below for quiescent current of PSU under battery when calculating total system standby current resources.
Mechanical
Product Reference
GEN3-08-A
GEN3-08-B
GEN3-18-B
GEN3-08-C
GEN3-18-C
Enclosure Dimensions
w x h x d (mm)
230 x 200 x 80
355 x 330 x 80
330x 275 x 80
Weight (kg)
excluding battery
2.0
4.0
3.3
Material
1.2mm steel white powder coated
Environmental
Temperature
-10 to +40°C (operating) 75% RH non-condensing
-20 to +80°C (storage)
Installation environment:
Intended for internal / indoor installation only.
Standby Battery Management
Warning: risk of explosion if incorrect battery type fitted
Maximum Battery Size
GEN3-08: 8 Ah 12V Valve Regulated Lead Acid
(Not supplied with unit)
GEN3-18: 18Ah 12V Valve Regulated Lead Acid
Intelligent Battery Recharge Time:
< 24 hours to 80% - If a heavily discharged battery, having a
terminal voltage > 9.0V, is connected the PSU will attempt to
charge it. If battery fails to accept charge in 24 hours it will fail
the active load test.
Minimum energy level:
(EN50131-6_2017 §6.0 ref. y’) Percentage of SD (battery) rated
capacity available to support the load = 100% (8Ah or 18Ah)
Testing:
Battery not Present: <9.0V battery voltage
Low battery voltage: <11.6V (no mains present)
Active load test at full rated output current
Protection:
Reverse battery connection protection
Overvoltage protection - Trips at 125% of rated O/P voltage
Deep discharge protection - Battery disconnect at 10.5V battery
terminal voltage
Quiescent Current:
64mA when running on battery - less than 1mA after deep
discharge protection.
Battery Cold Start (BCS)
Momentarily link BCS pins together to connect battery to load if
PSU commissioned without any mains