G2401N
G2402N
G2403N G2405N
Standby Battery
11)
Attach supplied battery cables to terminal block and batteries.
NOTE:
ensure correct polarity of battery connections:
Red
lead to
+ve
of
battery
1
,
Black
lead to
-ve
of
battery 2
. Connect
-ve
of
battery 1
to
+ve
of
battery 2
using short link lead
12)
Position batteries to avoid lid fixing screw.
13)
Apply mains power. Check Green Mains LED is ON.
14)
Check there is no fault indication on Yellow Fault LED.
15)
Disconnect mains power. Check that the batteries continue to supply voltage and current to the
load. Check Green Mains LED is OFF.
NOTE
: Batteries must have sufficient charge to supply the load
16)
Reconnect mains power. Check Green Mains LED is ON.
17)
Remove Load fuse and check Yellow Fault LED is ON.
18)
Replace Load fuse. Check Yellow Fault LED is OFF.
M
ODEL
S
PECIFICATION
T
ABLE
G2401N
G2402N
G2403N
G2405N
Output Current
1A
2A
3A
5A
Battery Charge Current
0.5A
0.5A
0.5A
0.5A
Mains LED (Green)
√
√
√
√
Fault LED (Yellow)
√
√
√
√
Max Mains Input Current
(at 90Vac)
1.0A
1.3A
1.4A
2.0A
F1 - Mains Input Fuse (20mm HRC)
T2.0A
T2.0A
T3.15A
T3.15A
F2 - Output Fuse (20mm)
F1.0A
F2.0A
F3.15A
F5.0A
F3 - Battery Fuse (20mm)
630mA
630mA
630mA
630mA
O
PERATING
I
NSTRUCTIONS
This unit is intended for use by Service Personnel only - There are NO USER SERVICEABLE parts inside.
The Green Mains LED will be illuminated whilst the mains supply is present. In the event of a fault
condition, the Yellow Fault LED will be illuminated.
10cm all round
.
N
L
E
10cm all round
.
L E N
10cm all round
.
E
N
L