background image

     

 

 

 

 

 

 

 

 

 

2

 

 
Standby Battery 

Battery Type 

2 x 12V Valve Regulated Lead Acid 

Battery Capacity 

See below under enclosure size. 

Battery Charging Fuse protection 

F630mA 20mm glass 

 

Mechanical  

Model 

Enclosure 

Dimensions  

w x h x d [external] (mm) 

Max Battery 

Capacity 

Weight (kg) 

[excluding battery]

 

G240xN-C

 

330 x 275 x 80

 

2 x NP7 (7Ah)

 

G2401N

 

3.16 

G2402N 

3.22 

G2403N, G2405N

 

3.30 

G240xN-R

 

390 x 410 x 80

 

2 x NP17 (17Ah)

 

G2401N

 

6.03 

G2402N

 

6.09 

G2403N, G2405N

 

6.17 

G240xN-H

 

400 x 420 x 140

 

2 x NP17 (17Ah)

 

G2401N

 

8.39 

G2402N

 

8.45 

G2403N, G2405N

 

8.53 

 

Environmental  

Temperature  

-10 to +40°C (operating) 75% RH non-condensing  

 

-20 to +80°C (storage) 

 

C

ONNECTIONS

 

 

 

O/P +, - 

Connection to equipment to be powered (Observe polarity) 

 

BATT +, - 

Connection to standby battery. Use cables provided (Observe polarity) 

 

I

NSTALLATION 

I

NSTRUCTIONS

 

 

 

This  unit  is  only  suitable  for  installation  as  permanently  connected  equipment.    This  PSU  is

 

NOT 

SUITABLE 

for external installation. This unit must be fed from a mains power source having a separate 

(approved) disconnect device and fitted with a fuse or other over-current protection device rated at 3A 
maximum.  Ensure  that  the  disconnect  device  used  has  appropriate  earth  fault  protection  to  the 
applicable  standard.

 

EQUIPMENT  MUST  BE  EARTHED

.  Before  installation,  ensure  that  external 

disconnect  device  is

  OFF

.

 

The  PSU  should  be  installed  according  to  all  relevant  safety  regulations 

applicable to the application.  
 

Mounting 

1)

 

Mount securely in correct orientation allowing minimum clearance – see diagram. 

2)

 

Route mains and low voltage output cables via different knockouts and/or cable entry holes. 

3)

 

Use bushes and cable glands rated to UL94 HB minimum.

 

 

 
Mains Power Up 

4)

 

Attach correctly rated mains cable (minimum 0.5mm

2

 [3A], 300/500Vac).Fasten with cable ties. 

5)

 

Apply mains power. Check for 27.6Vdc on load outputs. Check Green Mains LED is ON. 

6)

 

Disconnect mains power.

 

 

 
Load Output

 

7)

 

Attach correctly rated load cable and fasten using cable ties. Note polarity. 

8)

 

Apply mains power. Check Green Mains LED is ON.  

9)

 

Verify load is operating correctly. 

10)

 

Disconnect mains power. 

www.acornfiresecurity.com

www.acornfiresecurity.com