4
Technical Support Line +44 (0)2392 696638 G240xBM-x-y PAK200536_01G May 2016 Elmdene International Ltd ©
M
AINTENANCE
There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby
batteries.
Reference should be made to the battery manufacturer’s documentation to determine typical/expected
battery life with a view to periodic replacement of the battery.
If the output of the PSU fails the cause of the failure should be investigated e.g. short circuit load. The fault should be
rectified before restoring power to the PSU. The fuses may need to be replaced. Ensure the correct fuse rating and
type is used.
L
OCAL
I
NDICATORS
M
AINS
LED
(
GREEN
)
F
AULT
LED
(
YELLOW
)
C
HARGE
LED
(
ORANGE
)
S
TATUS
ON
OFF
OFF
NORMAL - battery fully charged
ON
OFF
ON
NORMAL - battery charging
ON
1s ON, 1s OFF
ON or OFF
FAULT - see Signalling Outputs
OFF
0.1s ON, 3s OFF
OFF
FAULT - Mains Loss
PSU operating on battery
standby
OFF
OFF
OFF
FAULT - No Output
Mains and Battery loss
C
OMPLIANCE
This power supply unit meets the essential requirements of the following European Directives:
Low Voltage: 2014/35/EU
EMC: 2014/30/EU
WEEE: 2012/19/EU
RoHS2: 2011/65/EU
D
ISPOSAL OF
P
RODUCT AT
E
ND OF
L
IFE
This product falls within the scope of EU Directives 2012/19/EU Waste Electrical and Electronic Equipment (WEEE) and
2013/56/EU (Battery). At the end of life, the product must be separated from the domestic waste stream and disposed
via an appropriate approved WEEE disposal route in accordance with all national and local regulations.
Before disposal of the product, any batteries must be removed, and disposed separately via an appropriate approved
battery disposal route in accordance with all national and local regulations. Package used batteries safely for onward
transport to your supplier, collection point or disposal facility.
Caution: Risk of fire or explosion if bare battery wires are allowed to touch.
See Specification for battery type information. The battery is marked with the crossed out wheelie bin symbol, which
may include lettering to indicate cadmium (Cd), lead (Pb), or mercury (Hg).
For more information see:
www.recyclethis.info
The packaging supplied with this product may be recycled.
Please dispose of packaging accordingly.