Technical Support Line +44 (0)2392 696638 G240xBM-x-y PAK200536_01G May 2016 Elmdene International Ltd ©
Standby Battery
Battery Type
2 x 12V Valve Regulated Lead Acid
Battery Capacity
See below under enclosure size.
Battery Charging Fuse protection
See Model Specification Table
Battery Re-Charge Time
<24hrs (to 80% of 8Ah capacity)
Mechanical
Model
Enclosure
Dimensions
w x h x d [external] (mm)
Max Battery
Capacity
Weight (kg)
[excluding battery]
G240xBM-C
330 x 275 x 80
2 x NP7 (7Ah)
G2401BM
3.16
G2402BM
3.22
G2403BM, G2405BM
3.30
G240xBM-R
390 x 410 x 80
2 x NP17 (17Ah)
G2401BM
6.03
G2402BM
6.09
G2403BM, G2405BM
6.17
G240xBM-H
420 x 420 x 180
2 x NP38 (38Ah)
G2403BM, G2405BM
8.53
Environmental
Temperature
-10 to +40°C (operating) 75% RH non-condensing
-20 to +80°C (storage)
S
IGNALLING
O
UTPUTS
GEN Fault (general)
0.1 A @ 60 VDC N/O volt-free contact.
Open when battery disconnected, output fuse fail, battery fuse fail,
output short circuit or low output voltage.
EPS Fault (mains)
0.1 A @ 60 VDC N/O volt-free contact.
Open when loss of mains for more than 8s.
C
ONNECTIONS
O/P +, -
Connection to equipment to be powered (Observe polarity)
BATT +, -
Connection to standby battery. Use cables provided (Observe polarity)
GEN Fault
Volt-free contacts for general faults
EPS Fault
Volt-free contacts for loss of mains indication
I
NSTALLATION
I
NSTRUCTIONS
This unit is only suitable for installation as permanently connected equipment. This PSU is
NOT SUITABLE
for external
installation. This unit must be fed from a mains power source having a separate (approved) disconnect device and fitted
with a fuse or other over-current protection device rated at 3A maximum. Ensure that the disconnect device used has
appropriate earth fault protection to the applicable standard.
EQUIPMENT MUST BE EARTHED
. Before installation,
ensure that external disconnect device is
OFF
.
The PSU should be installed according to all relevant safety regulations
applicable to the application.
Mounting
1)
Mount securely in correct orientation allowing minimum clearance – see diagram.
2)
Route mains and low voltage output cables via different knockouts and/or cable entry holes.
3)
Use bushes and cable glands rated to UL94 HB minimum.
Mains Power Up
4)
Attach correctly rated mains cable (minimum 0.5mm
2
[3A], 300/500Vac). Fasten with cable ties.
5)
Apply mains power. Check for 27.6Vdc on load outputs. Check Green Mains LED is ON.
6)
Disconnect mains power.