1
Technical Support Line +44 (0)2392 696638 G240xBM-x-y PAK200536_01G May 2016 Elmdene International Ltd ©
27.6V
DC
S
WITCH
M
ODE
P
OWER
S
UPPLIES
W
ITH
R
EMOTE
F
AULT
S
IGNALLING AND
B
ATTERY
M
ONITORING
Models:
G240xBM-y
Where ‘x’ is max load current and ‘y’ is Enclosure type
F
EATURES
High efficiency cost effective power supply ideal for use in Fire, Access Control and General Security applications.
Featuring a regulated 27.6Vdc output supplying continuous full rated current to load plus additional current for
charging 2 x 12V standby batteries. Maximum battery life is assured using deep discharge protection to prevent
premature battery failure when operating in standby mode for extended periods. Two sets of volt-free contacts are
provided to signal (i) loss of mains and (ii) battery and loss of output faults. The universal mains input voltage enables
the power supply to be used across a wide geographical area. The highly efficient switch mode design ensures low
operating costs, generates less heat and with a small physical size increases the room available for additional PCBs or
cables. The modular construction simplifies maintenance.
•
Continuous full rated current to load
•
Reverse battery connection protection
•
Additional current to charge 2 x 12V standby
batteries
•
Modular construction for ease of maintenance and
installation
•
Battery Deep Discharge Protection
•
G2403 & G2405 - Full electronic short circuit and
overload protection on load output (under mains power
only)
•
Universal mains input voltage 90-264Vac
•
G2401 & G2402 - Fuse protection
•
Volt free contact signalling mains failure
•
Mains transient protection circuit
•
Volt free contact signalling output and battery faults
•
Green Mains present LED
•
High efficiency electronics for reduced running costs
and lower operating temperatures
•
Yellow Fault LED
•
Installer safe design with all high voltage electronics
fully shrouded
•
Orange Battery Charging LED (visible on PCB only)
S
PECIFICATION
Input Specification
Voltage (rated) / (operating)
100-240Vac / 90-264Vac (Both at 50 – 60Hz)
Max Current / Input Fuse
See Model Specification Table
Max standby Power
0.8W (No load and no battery connected)
Output Specification
Voltage
27.0 – 28.0Vdc (27.6Vdc nominal) on mains power
21.0 – 24.7Vdc on battery standby
Max load current / load fuse
See Model Specification Table
Ripple
100 mV pk-pk max
Overload
Electronic shutdown until overload or short circuit removed
(under mains power only) (G2403BM & G2405BM)
Fuse Protection (G2401BM & G2402BM)
Elmdene International Ltd
Tel: +44 (0)23 9269 6638
3 Keel Close, Interchange Park,
Fax: +44 (0)23 9266 0483
Portsmouth, Hampshire, PO3 5QD, UK
Web:
www.elmdene.co.uk