Elma RCD Test
side 42
Included in the set
FITESTpro
Twisted test lead with measuring tip
Pouch
User’s Manual
Calibration Certificate
Cardboard shipping case
Optional accessories
P 5050 – adapter for charging accumulators
P 5060 – set of 4 NiMH AAA accumulators
P 2011 – test lead, black, 2 m
P 3011 – test tip, black
P 4011 – crocodile clip, black
Note: optional accessories P 2011 + P 3011, respectively P 2011 + P 4011 can be
connected instead of twisted test lead with measuring tip.
Putting the instrument into operation
Putting the instrument into operation consists of inserting the batteries or accumulators -
the procedure is described in the Chapter 4.1. of this manual.
Measurements
Turning the instrument on and off, standby, auto power off
Hold the
START
key pressed until the device turns on.
The instrument is turned off after two short pressing/releasing the
START
button, while no
voltage can be applied on the test tips.
The instrument enters standby mode (reduced display brightness) after short time of
inactivity (no key pressed, no voltage applied on the test tips).
From standby mode (to full display brightness), the instrument enters after pressing any
button or by applying the voltage on the test tips.
Auto power off occurs when the instrument is idle (no key pressed, no voltage applied on
the test tips) for about a minute.
After turning off the device can be switched on again after about 1s.
Notes and principles applicable to all measurements
•
Select required parameter or function by the
FUNC
,
I
Δ
N
,
TYPE
and
xI
Δ
N
keys. The
START
key starts measurement. All set parameters and functions remain valid until
they are changed.
•
If voltage applied on the test tips is < 190 V (consider also the note in the next
paragraph!) or > 260 V, the relevant information is displayed and the
START
button
does not start measurement: