12
The voltage parameter are at 250C, 24VDC system, and twice in 48VDC system.
NOTE: When Output source priority is Battery and the battery voltage lower than the Low Voltage Disconnect
Voltage(LVD
adjustable), the system will switch utility to supply power for load.
2) Advanced interface for engineers
Operation:
Step1: Press the + button and hold on 5s under the real-time interface.
Step2: Press the button and hold on 5s under the setting parameter interface.
Step3: Press the button to enter the parameter.
Step4: Press the
button to exit the setting interface.
Setting
:
Item
LCD
Instruction
Default
Range
9
BCT
Boost Charging Time
30M
30M/60M/120M/180M
10
BCV
Boost Charging Voltage
AGM
:
28.8 VDC
GEL
:
28.4 VDC
FLD
:
29.2 VDC
USER
:
28.8VDC
VDC
VDC
VDC
VDC
User 25.0
〜
29.6
Step size 0.2
11
BVR
Boost Voltage Reconnect
26.4VDC
User: 25.0
〜
28.0
Step size 0.2
12
FCV
Float Charging Voltage
27.6 VDC
User: 26.0
〜
28.0VDC
Step size 0.2VDC
13
OVR
Over Voltage Reconnect Voltage
30.0 VDC
User: 29.0
〜
31.0VDC
Step size 0.2VDC
14
OVD
Over Voltage Disconnect Voltage
32.0 VDC
User: 31.0
〜
32.2VDC
Step size 0.2VDC
15
AOF
Auxiliary module OFF voltage
Auxiliary module ON voltage
28.0VDC
User: 24.0
〜
29.6VDC
Step size 0.2VDC
16
AON
24.0 VDC
17
DON
22.2 VDC
User: 21.6
〜
24.0VDC
Step size 0.2VDC
18
DOF
Dry connect OFF voltage
Dry
connect ON voltage
24.0 VDC
User: 24.0
〜
26.5VDC
Step size 0.2VDC
19
MCC
Max. charging current
60.0A
15.0
〜
60.0A
20
PSM
Power saving mode
OFF
ON /OFF
21
CFA
Clear fault
OFF
ON /OFF
22
QCL
Clear the accumulated energy
OFF
ON /OFF
23
VER
Software version
U-1.0
—
The voltage parameter are at 250C 24VDC system (twice in 48VDC system ).
For the inverter/charger of different power, the current setting range is not the same, see Technical Parameters
for details.
NOTE
15/16
:
Stop/restore auxiliary module charging voltage
Only when the charging mode is Solar priority or Utility priority will the auxiliary module charging voltage be
effective.
20: Power saving mode
When the switch is on “Saving” side, the inverter will enter into the Saving Mode. It will shut off the output if the loads
value is less the 70W. Then restart and detect the power of the load again after 10s. If the load is more than 70W, the
inverter will turn on the output. Otherwise it will shut off output. It cycles like this. So please don’t use the saving mode
if the load is smaller then 70W.
21: Clear the faults
In occurrence of short circuit or overload caused to AC output, the fault can be cleared out.