1
2
3
4
Immediate Close
DIP Switch
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
20 sec
40 sec
1 min
1 min 20 sec's
1 min 40 sec's
2 min's
2 min's 20 sec
2 min's 40 sec
3 min's
3 min's 20 sec's
3 min's 40 sec's
4 min's
On
On
Off
On
On
On
On
On
4 min's 20 sec's
4 min's 40 sec's
5 min's
On
On
On
On
On
On
On
Table 5 - Delay Timer
Setting a Delay Time before closure on receipt of fire signal
A signal from the fire alarm will immediately activate the FCP - 01 visual and audible warnings
By setting a combination of DIP Switches from the table opposite, a delay time will be entered
to give audio / visual warning before closure of the shutter begins
1
Door
CLOSES
on fire alarm
2
Panel requires a
N.O
Fire alarm signal to activate
Off
On
Off
On
Door
OPENS
on fire Alarm
3
(see note)
Off
On
4
Off
On
Not used
Table 4 - Fire Options
DIP
Aux relay operates for the same time as the alarm signal
Not used
Aux relay latches for 3.5 min's in normal operation
.......(continued)
**Function Only active in fire
**Function only active in
normal operation, DIP 3 = off
(FIRE OPTIONS)
Notes
Delay Time
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Panel requires a
N.C
Fire alarm signal to activate
0
3
4
5
2
1
6
Dial
Position
0
1
2
3
4
5
6
Motor run
Time (Sec's)
Auto Close
Delay Time
(Sec's)
2
8
16
26
35
44
52
10
18
34
46
60
70
90
Setting an Auto Delay Time
By setting the dial in the chosen
position,the FCP-01 will pre load both
the motor run timer and the optimum
auto close delay time (requires
photocell connected and DIP 4 =
ON
,
Table - SETUP)
Important
When using auto-close function, set run
time slightly longer than door travel time
The motor must reach its top limit for the
auto-close to activate