7.0) Commissioning
Connect all required devices e.g motor, key-switch (photocell optional)
If no photocell is used ensure link is fitted between 0v and SIG
If a key swiitch is used ensure link is fitted between COM and STOP
Turn Run Time Dial fully clockwise to give max run time (52 sec's)
Apply Power
Before setting the travel limits, turn the motor current sensing OFF by Moving
DIP SW 5 (Table 1 - SETUP) to ON position
Operate the door and set travel limits at desired positions
Check by running the door to full open position, then full closed position, adjust
if necessary
Move DIP SW 5 (Table 1 - SETUP) back to OFF position
If auto close is required move DIP SW 4 (Table 1 - SETUP) to ON position
Operate door again and check photocell in the closing direction for stop and
retract (options set by DIP2, Table 1 - SETUP)
If no photocell is fitted, remove the link between (0v and SIG) to give Hold-to-run
control (Dead man) in the close direction
Please note: In Hold-to-Run (Dead man) mode there is a slight delay when
operating in the close direction
Fire Signal
Select the fire signal type to be used using DIP SW 2 (Table 4 - FIRE OPTIONS)
and connect a volt free signal to the terminals marked "FIRE"
Set the delay time required using the DIP Switches as in "Table 5 - DELAY
TIMER"
Open the door fully and using a simulated fire signal, activate the panel
The panel with give an audio/visual warning for the delay time set, then begin to
close the door
The door will continue to close run for as long as the simulated signal remains
on