GENERAL DESCRIPTION

 

Based  on  a  microcontroller  and  equipped  with  a  short  circuit  isolator,  the  IO501  is  an  output  module 
(OM) with a dry contact output to be used with Elkron FAP series control panels. The module is directly 
powered  from  the  detection  circuit  and  it  doesn’t  need  an  external  power  supply.  A  jumper  is  used  to 
select  the  normally  open  or  normally  closed  contact  type.    The  module  has  an  input  for  supervise  the 
external  local  power  supply  of  the  handled  device:  a  loss  or  presence  of  the  local  power  supply  is 
signalled  from  the  module  to  the  control  panel.  The  bi-colour  LED  (green-red),  in  operating  mode, 
indicates the module condition while, in service mode, it can be used 

to show the detector’s address by a 

special  function  activated  from  the  control  panel.  Delay  between  output  feedback  and  actual  output 
control (hold-off delay) can be programmed in the control panel. This delay is expressed in seconds and it 
covers a range between 0 and 255 seconds with 1 sec. steps. The default value is 0. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
For further information refer to the 

FAP series Control Panel’s programming manual. 

 

ADDRESSING

 

The address (1-128) is software set and stored in a non-volatile memory.  
The module can be addressed, in manual or automatic mode from the Control Panel. 
For further details see the Control Panel’s programming manual. 

 

TERMINAL BOARDS

 

 

Nr. 

Description 

+IN 

Detection circuit positive input  

-IN 

Detection circuit negative input 

SH 

Detection circuit input shield 

-OUT 

Detection circuit negative output 

+OUT 

Detection circuit positive output 

PC 

NO/NC contact switch  

CC 

Common contact switch 

 

JP1:  Closed: default setting 

Open: Power off module 

 

JP2:   Closedelectrical connection between detection line positive input and detection line positive 

output 
Open
: default setting 

 

JP3:   Position 1-2: contact normally open (NO). 

Default setting 
Position 2-3contact normally closed (NC) 

 

JP4:   Connector for per local 24Vdc supervision. Use the supplied cable. 
 

Red wire: 24Vdc positive input 

 

Black wire: 24Vdc negative input 

 

It’s possible to define in control panel the fault signaling for absence or presence of the local voltage. 

ENGLISH 

Summary of Contents for IO501

Page 1: ...e un range fra 0 255 in step da 1 secondi Il valore di fabbrica del ritardo è pari a 0 Per ulteriori informazioni fare riferimento al manuale programmazione delle centrali ELKRON serie FAP INDIRIZZAMENTO L indirizzo 1 128 è impostato via software e memorizzato su una memoria non volatile Il modulo può essere indirizzato dalla centrale in modalità automatica o manuale Per ulteriori dettagli vedere ...

Page 2: ...astico come da figura utilizzando la vite in dotazione Vista installazione modulo all interno della targa OUT PC CC DC OUT DC IN TM24 1 TB24 1 IO501 JP3 1 2 JP4 NERO ROSSO 24Vcc OUT PC CC C A TMSV 1 IO501 JP3 1 2 B JP1 BC JP2 AB JP4 NERO ROSSO 24Vcc OUT PC CC IN OUT TM220 2 TM224 2 IO501 JP3 1 2 JP103 AB JP4 NERO ROSSO 24Vcc Collegamento alle targhe TBxx TMxxx Note 1 Dimensionare l alimentatore 24...

Page 3: ... IO501 JP3 1 2 JP4 ROSSO NERO 24Vcc 24V LINEOUT LINE IN EOL 24Vcc Collegamento alla sirena HPA700F Nota Nel modulo è contenuto un relè bistabile che se soggetto a forti urti es colpi o cadute il contatto del relè potrebbe cambiare di stato Si consiglia pertanto di controllare la posizione del contatto prima di alimentare tutto il sistema Per ripristinare la posizione originaria del contatto prima ...

Page 4: ...el cavo Si consiglia un conduttore con sezione di 1 5 mm2 Usare un cavo elettrico che non ecceda i seguenti limiti Resistenza massima 100 Ω Capacità massima 2 µF Il collegamento elettrico deve essere effettuato rimuovendo circa 10mm di protezione isolante dal conduttore principale inserendolo nella morsettiera INGRESSO LINEA RIVELAZIONE SCHERMO IN IN SH OUT OUT PC CC USCITA LINEA RIVELAZIONE SH SH...

Page 5: ...veloce indirizzo duplicato Uscita contatto 1A 30Vcc carico resistivo Ingresso supervisione tensione locale Ingresso optoisolato 24Vcc 15 10 Temperatura di funzionamento 10 55 C 2 C 14 131 F Umidità relativa 93 2 non condensante Temperatura di immagazzinamento 30 70 C 22 158 F Classe ambientale Interno Dimensioni 66x46xH17 mm Peso 30g Conforme alle norme EN54 18 2005 AC 2007 EN54 17 2005 AC 2007 Mo...

Page 6: ...t covers a range between 0 and 255 seconds with 1 sec steps The default value is 0 For further information refer to the FAP series Control Panel s programming manual ADDRESSING The address 1 128 is software set and stored in a non volatile memory The module can be addressed in manual or automatic mode from the Control Panel For further details see the Control Panel s programming manual TERMINAL BO...

Page 7: ...ied screw as in figure Module installation view inside the VAD OUT PC CC DC OUT DC IN TM24 1 TB24 1 IO501 JP3 1 2 JP4 BLACK RED 24Vdc OUT PC CC C A TMSV 1 IO501 JP3 1 2 B JP1 BC JP2 AB JP4 BLACK RED 24Vdc OUT PC CC IN OUT TM220 2 TM224 2 IO501 JP3 1 2 JP103 AB JP4 BLACK RED 24Vdc Connection to TBxx TMxxx VAD Note 1 Sizing the 24Vdc power in order to supply the VAD 2 The 24Vdc is used to activate t...

Page 8: ...1 2 JP4 RED BLACK 24Vdc 24V LINEOUT LINE IN EOL 24Vdc Connection to HPA700F siren Note Inside the module is present a latching relay which it is subject to hard shock or impact the contact could change its status It s suggest to check the contact position before supplying the entire system To restore original contact position execute the global reset procedure on the control panel before connect t...

Page 9: ... line A lead section of 1 5 mm2 is advised Don t use cable that exceed these limits Maximum resistance 100 Ω Maximum capacitance 2µF The electrical connection must be performed by removing approximately 10 mm of insulating cover from the main lead and insert it on the terminal block DETECTION CIRCUIT INPUT SHIELD IN IN SH OUT OUT PC CC DETECTION CIRCUIT OUTPUT SH SH Detection circuit connection Th...

Page 10: ...ion green blinking fast duplicate address Output contact 1A 30Vdc resistive load Local voltage supervision input 24Vdc opto isolated input 15 10 Operative temperature 10 55 C 2 C 14 131 F Relative humidity 93 2 non condensing Storage shipping temperature 30 70 C 22 158 F Environmental class Type A Dimensions 66x46xH17 mm Weight 30g In compliance with EN54 18 2005 AC 2007 EN54 17 2005 AC 2007 Modul...

Page 11: ...dos y puede cubrir un rango entre 0 255 en pasos de 1 segundo El valor de fábrica del retraso es 0 Para más información remitirse al manual de programación de las centrales ELKRON serie FAP ASIGNACIÓN DE LA DIRECCIÓN La dirección 1 128 se establece mediante software y se almacena en una memoria no volátil El módulo puede ser dirigido desde la central de modo automático o manual Para más detalles c...

Page 12: ...todo el circuito impreso Fijar el módulo dentro del contenedor plástico como se muestra en la figura utilizando el tornillo que se suministra Vista instalación módulo dentro de la placa OUT PC CC DC OUT DC IN TM24 1 TB24 1 IO501 JP3 1 2 JP4 NERO ROSSO 24Vcc ROJO NEGRO Conexión a las placas TBxx TMxxx Notas 1 Dimensionar el alimentador de 24Vcc para alimentar la placa 2 La tensión de 24Vcc activa l...

Page 13: ...IO501 JP3 1 2 JP4 ROJO NEGRO 24Vcc 24V LINEOUT LINE IN EOL 24Vcc Conexión a la sirena HPA700F Nota El módulo contiene un relé biestable que en caso de fuertes golpes por ej impactos o caídas el contacto del relé podría cambiar de estado Por lo tanto se aconseja controlar la posición del contacto antes de alimentar todo el sistema Para restablecer la posición original del contacto antes de conectar...

Page 14: ... sección de los conductores puede variar según la longitud del cable Se aconseja un conductor con sección de 1 5 mm2 Usar un cable eléctrico que no exceda los siguientes límites Resistencia máxima 100 Ω Capacidad máxima 2 µF Para la conexión eléctrica quitar aproximadamente 10 mm de protección aislante del conductor principal introduciéndolo en la caja de terminales Conexión línea de detección El ...

Page 15: ...t rápido dirección duplicada Salida contacto 1A 30Vcc carga resistiva Entrada supervisión tensión local Entrada optoaislada 24Vcc 15 10 Temperatura de funcionamiento 10 55 C 2 C 14 131 F Humedad relativa 93 2 no condensante Temperatura de almacenamiento 30 70 C 22 158 F Clase ambiental Interno Dimensiones 66x46xH17 mm Peso 30g De conformidad con las normas EN54 18 2005 AC 2007 EN54 17 2005 AC 2007...

Page 16: ...ste equipment by handing it over to a designated collection point for the recycling of waste electrical and electronic equipment The separate collection and recycling of your waste equipment at the time of disposal will help to conserve natural resources and ensure that it is recycled in a manner that protects human health and the environment For more information about where you can drop off your ...

Reviews: