4/8 

 

ADDRESSING

 

The  address  (1-128)  is  software  set  and  stored 
in a non-volatile memory.  
The  FM500  can  be  addressed,  in  manual  or 
automatic mode from the Control Panel. 
For  further  details  see  the  Control  Panel’s 
programming manual. 

CONNECTIONS 

A  shielded  cable  must  be  used

:  connect  the 

shield  of  the cable  (one end  in  a  loop  mode) to 
the ground in the control panel only and connect 
the shield between a device. 
The  section  of  leads  can  vary  according  to  the 
length of the detection line. 
A lead section of 1.5 mm

is advised. 

 

Don’t use cable that exceed these limits: 
  Maximum resistance = 100 

Ω 

  Maximun capacitance = 2 µF 

 

The electrical connection must be performed by 
removing  approximately  10  mm  of  insulating 
cover  from  the  main  lead  and  insert  it  on  the 
terminal block. 

 

 

Fig. 3

 

– Connection diagram 

 

The 

FM500 

is only to be used with ELKRON 

FAP series Control Panels.

 

 
 
 
 
 
 
 

 

TESTING 

(trained personnel)

 

Before testing, notify to competent authority that 
the  system  is  temporarily  out  of  service  due  to 
maintenance operations. 
The manual call point can be tested by pressing 
on  the  operating  face  and  verifying  the  alarm 
condition. 

 

At  the  end  of  testing  operations,  restore  the 
system to normal operation and notify the status 
to the competent Authorities. 
 

TECHNICAL SPECIFICATIONS 

 

Operating voltage 

20 Vdc (-15%, +10%) 
modulated 

Average power 
consumption 
(Normal condition) 

250 

A @ 20Vdc 

Average power 
consumption 
(Alarm condition) 

2 mA @ 20Vdc 

Bi-Colour LED 

Red steady: 
alarm condition 
Red blinking slow (2s): 
alarm condition with SLC 
operating voltage < 17V 
Green blinking slow (2s): 
normal condition 
Green blinking fast: 
duplicate address 

Operating temperature 

-10 

 55°C ± 2°C 

(14 

 131°F) 

Relative humidity 

93 % ± 2%  
non condensing 

Storage/shipping 
temperature 

-30 

 70 °C 

(-22 

 158°F) 

Alarm condition 

Type A 

Enviromentals class 

Inside 

Dimensions 

110x110x42 mm 

Weight 

140 g 

Enclosure material 

ABS V0 

In compliance with   EN54-11: 2001/A1:2005 
                                 EN54-17: 2005/AC:2007 
 
Resettable Manual Call Point  FM500

 

Urmet S.p.A.  1293-CPD-0337

 

DoP n. 1293-CPR-0337 

 

Further information are available to the manufacturer. 

 
 

09 

 

1293 

Summary of Contents for FM500

Page 1: ...sterà verso l interno azionando l interruttore e generando la condizione di allarme Il ripristino dalla condizione di allarme è effettuabile inserendo l apposita chiavetta in dotazione nella feritoia e tirando come mostrato in Fig 1 Per aprire il contenitore utilizzare la chiavetta come illustrato dalla Fig 2 È possibile utilizzare la contro base 80SB7410121 per installazioni con canaline elettric...

Page 2: ... addestrato Prima di iniziare le operazioni di test comunicare all autorità competente che il sistema è temporaneamente fuori servizio a causa della manutenzione in corso Per testare il pulsante azionarlo e verificare la condizione di allarme Al termine delle operazioni di test riportare il sistema nelle normali condizioni operative e comunicare il ripristino alle Autorità competenti CARATTERISTIC...

Page 3: ...resettable Manual Call Point the Alarm condition will be initiated by pressing on the operating face of the Manual Call Point Resetting of the Alarm condition is effected by inserting the supplied key in the slit and pulling as shown in Fig 1 To open the enclosure use the key as shown in Fig 2 The 80SB7410121 counter base can be used for installations with external electrical conduits with a diame...

Page 4: ...hority that the system is temporarily out of service due to maintenance operations The manual call point can be tested by pressing on the operating face and verifying the alarm condition At the end of testing operations restore the system to normal operation and notify the status to the competent Authorities TECHNICAL SPECIFICATIONS Operating voltage 20 Vdc 15 10 modulated Average power consumptio...

Page 5: ... de tipo rearmable realizando una presión sobre la parte central del frontal este se hunde hacia dentro accionando un interruptor La restauración del pulsador se realiza introduciendo la llave incluida en la ranura del frontal y tirando como se muestra en la Fig 1 Para abrir el contenedor utilizar la llave como se muestra en la Fig 2 Puede utilizar la contrabase 80SB7410121 para instalaciones con ...

Page 6: ... de la serie FAP PRUEBA personal autorizado Antes de iniciar la prueba comunicar al responsable de seguridad que el sistema estará temporalmente fuera de servicio a causa del mantenimiento Para probar el pulsador accionarlo y verificar la condición de alarma Al terminar la prueba dejar el sistema en condición normal de funcionamiento y avisar al responsable de seguridad CARACTERÍSTICAS TÉCNICAS Te...

Page 7: ...t or on its packaging indicates that this product must not be disposed of with your other household waste Instead it is your responsibility to dispose of your waste equipment by handing it over to a designated collection point for the recycling of waste electrical and electronic equipment The separate collection and recycling of your waste equipment at the time of disposal will help to conserve na...

Page 8: ...02 334491 Fax 39 02 33449213 www elkron com mail to info elkron it ELKRON è un marchio commerciale di URMET S p A ELKRON is a trademark of URMET S p A ELKRON es una marca registrada de URMET S p A Via Bologna 188 C 10154 Torino TO Italy www urmet com MADE IN ITALY ...

Reviews: