6.1 

DESCRIPTION PLAQUE A BORNES 

 

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

000143

 

 

Fig. 3 - Vue de la plaque à bornes 

 

Borne 

Fonction  

Description 

GND 

Terre de protection 

0V 

Entrée négative alimentation 

0V 

Sortie négative alimentation 

24Vcc 

Entrée positive alimentation 

24Vcc 

Sortie positive alimentation 

 

Libre 

 

Libre 

RS485 +A 

Entrée positive transmission RS485 

RS485 -B 

Entrée négative transmission RS485 

10 

 

Libre 

11 

 

Libre 

12 

RS485 +A 

Sortie positive transmission RS485 

13 

RS485 -B 

Sortie négative transmission RS485 

14 

Contact commun relais 

15 

NA 

Contact normalement ouvert relais 

16 

NC 

Contact normalement fermé relais 

 

6.2 

RACCORDEMENTS 

 

Le raccordement des données entre la centrale et la console FKP500 ne doivent pas dépasser la 
longueur maximum de 1200m. On conseille l

’utilisation d’un câble blindé composé de 2x0.75mm

2x1mm

2

  câbles  respectivement  pour  la  connexion  de  données  et  pour 

l’alimentation.  Serrez  la 

ferrite fournie sur le câble près de la console. 
 
 
 

Summary of Contents for FKP500

Page 1: ...azione Installation Manual Manuel d Installation Manual de Instalación FKP500 Pannello di ripetizione e comando remoto Remote LCD Annunciator Panneau de répétition et commande à distance Panel de repeticion y comando remoto E F EN I 0051 18 ...

Page 2: ...ale contenga riferimenti o informazioni di prodotti hardware o software o servizi non ancora commercializzati Tali riferimenti o informazioni non significano in nessun modo che la società intenda commercializzare tali prodotti o servizi Elkron è un marchio commerciale di URMET S p A Tutti i marchi citati nel documento appartengono ai rispettivi proprietari Tutti i diritti riservati Si autorizza la...

Page 3: ... MARCATURA 5 4 INDICATORI TASTI E RELE 6 4 1 INDICATORI FRONTALI 6 4 2 TASTI 6 4 3 RELÈ 7 5 FUNZIONAMENTO 8 5 1 REGOLAZIONE DEL CONTRASTO DEL DISPLAY 9 6 INSTALLAZIONE 10 6 1 DESCRIZIONE MORSETTIERA 11 6 2 COLLEGAMENTI 11 6 2 1 Collegamento punto punto 12 6 2 1 Collegamento multi punto 13 7 INDIRIZZAMENTO 15 8 CARATTERISTICHE TECNICHE 16 ...

Page 4: ...Consolle FKP500 permette un controllo attivo e costante sullo stato della connessione con la centrale La serie di centrali FAP54 consente di gestire fino a 16 pannelli remoti posti ad una distanza massima di 1200m La connessione fra la centrale ed i pannelli remoti avviene tramite un collegamento RS485 a 2 fili a 9600 Bit s la porta di comunicazione RS485 del pannello è opto isolata e questo perme...

Page 5: ...velazione e segnalazione d incendio per edifici FKP500 Da utilizzarsi con una delle seguenti centrali di rivelazione incendio CDS FAP541 FAP544 FAP548 FAP5416 Elenco delle opzioni con requisiti 7 8 Uscite verso i dispositivi di allarme incendio 7 11 Ritardi delle uscite 7 12 Correlazioni su più di un segnale di allarme 8 3 Segnale di guasto dai punti 9 5 Fuori servizio dei punti indirizzabili 10 C...

Page 6: ...sue batterie 4 2 TASTI Tasto Descrizione Selezione del tipo di evento visualizzato a display Rotazione dei messaggi visualizzati a display Reset Tasto di riavvio della centrale reset globale Soggetto ad abilitazione tramite chiave meccanica Verifica Lampade Tasto per la verifica degli indicatori luminosi e sonori Comporta l accensione degli indicatori per alcuni secondi Tacita Riarma Sirena Tasto ...

Page 7: ...la posizionarla su ON La tastiera è attiva solo dopo aver programmato in centrale la presenza del pannello remoto Quando il pannello è riconosciuto dalla centrale e questa ne controlla la presenza sul display in alto a sinistra compaiono alternativamente i caratteri e Per ulteriori informazioni riferirsi al manuale di programmazione della centrale 4 3 RELÈ Nella Consolle FKP500 è presente un relè ...

Page 8: ... Dove RITARDO ATTIVO indica che sulla centrale è presente un ritardo delle attivazioni GUASTO SIRENA indica che l uscita sirena della centrale è guasta SIRENA ESC TACIT indica che l uscita sirena della centrale è esclusa oppure tacitata COM E sono le indicazioni del comunicatore ai dispositivi di trasmissione allarme tipo E COM J sono le indicazioni del comunicatore ai dispositivi di trasmissione ...

Page 9: ...mazioni 5 1 REGOLAZIONE DEL CONTRASTO DEL DISPLAY E possibile regolare il contrasto del display operando nel seguente modo A pannello alimentato premere contemporaneamente i tasti Verifica Lampade e Successivamente apparirà sul display l indicazione della barra di regolazione del contrasto e la temperatura ambiente Per aumentare il contrasto premere insieme i tasti Verifica Lampade e Per diminuire...

Page 10: ...o presenti 3 fori che consentono il fissaggio a parete il pannello dispone di due ingressi coperti da passacavo per il passaggio dei cavi all interno del contenitore OFF ON Reset Verifica Lampade Riarmo Sirena Tacitazione Sirena Aumento Ritardo Allarme Guasto Escluso Sirena Esclusa Aumento Ritardo OFF ON Reset Verifica Lampade Riarmo Sirena Tacitazione Sirena Aumento Ritardo Allarme Guasto Escluso...

Page 11: ...esso negativo trasmissione RS485 10 Libero 11 Libero 12 RS485 A Uscita positivo trasmissione RS485 13 RS485 B Uscita negativo trasmissione RS485 14 C Contatto comune relè 15 NA Contatto normalmente aperto relè 16 NC Contatto normalmente chiuso relè 6 2 COLLEGAMENTI L estensione massima del collegamento dati fra la centrale e le Consolle FKP500 non deve superare la lunghezza di 1200m Si consiglia l...

Page 12: ...unto punto fra una sola Consolle FKP500 e la centrale eseguire le connessioni come riportato in figura 4 I resistori di fine linea del canale dati RS485 devono essere abilitati sia sulla centrale che sul pannello remoto Fig 4 Collegamento punto punto 24 Vcc ...

Page 13: ...estremi del collegamento dovranno avere abilitate le resistenza di fine linea del canale dati RS485 indipendentemente che siano pannelli remoti o centrale 000201 Alimentazione Alimentazione Bus 485 Bus 485 Lunghezza Max 1200m Pannello remoto Pannello remoto Centrale Fig 5 Collegamento multi punto pannelli remoti all estremità della connessione in questo caso deve essere rimosso il jumper JP2 RA su...

Page 14: ...14 Fig 6 Collegamento multi punto centrale ad una estremità della connessione 24 Vcc ...

Page 15: ...ntono di impostare l indirizzo del pannello Posizionare i ponticelli in base all indirizzo desiderato questa operazione deve essere eseguita con il pannello non alimentato Fig 7 Selezione dell indirizzo tramite i ponticelli 1 5 9 13 17 21 25 29 2 6 10 14 18 22 26 30 3 7 11 15 19 23 27 31 4 8 12 16 20 24 28 32 ...

Page 16: ...anto conferire l apparecchiatura giunta a fine vita agli idonei centri comunali di raccolta differenziata dei rifiuti elettrotecnici ed elettronici In alternativa alla gestione autonoma è possibile consegnare l apparecchiatura che si desidera smaltire al rivenditore al momento dell acquisto di una nuova apparecchiatura di tipo equivalente Presso i rivenditori di prodotti elettronici con superficie...

Page 17: ...N 18 3 MARKING 19 4 INDICATORS KEYS AND RELAYS 20 4 1 FRONT INDICATORS 20 4 2 KEYS 20 4 3 RELAYS 21 5 OPERATION 22 5 1 ADJUSTING THE DISPLAY CONTRAST 23 6 INSTALLATION 24 6 1 TERMINAL BOARD DESCRIPTION 25 6 2 CONNECTIONS 25 6 2 1 Point to Point Connection 26 6 2 2 Multi point connection 27 7 ADDRESSING 29 8 TECHNICAL SPECIFICATION 30 ...

Page 18: ...t control over the status of the connection to control panel The series of control panels FAP54 allows to manage up to 16 remote panels placed at a maximum distance of 1200m The connection between control panel and remote panels is through a 2 wires 9600bps RS485 connection the RS485 communication port of the panel is optically isolated so the panel can be used with power supplies other than provi...

Page 19: ...ion and fire alarm control panel FKP500 To be used in conjunction with one of the following fire detection control panels CDS FAP541 FAP544 FAP548 FAP5416 Option with requirement list 7 8 Output to fire alarm device 7 11 Delay to outputs 7 12 Co incidence detection 8 3 Fault signals from points 9 5 Disablement of addressable points 10 Test condition 18 0051 ...

Page 20: ...ed by the mains When blinking the control panel is powered only by its batteries 4 2 KEYS Keys Description Selection of the event type shown on the display Rotation of messages shown on the display Reset Control panel reset key general reset Enabled via a mechanical key Lamps Test Key to test the lit and acoustic indicators It activates the indicators for some seconds Silence Ream Siren Key for si...

Page 21: ...ON The keypad is only active after programming the presence of remote panel at control panel When the panel is acknowledged by control panel and control panel checks for the panel to be present on the top of the display at the left characters and appear in turn For further information refer to control panel programming manual 4 3 RELAYS FKP500 Consolle has a relay which is directly driven by the c...

Page 22: ...lay of the activation SIREN FAULT indicates that the siren output of the control panel is in fault condition SIREN EXCL SILEN means that the siren output of the control panel is excluded or silenced COM E these are the indications of the type E alarm transmission routing equipment COM J these are the indications of the type J fault transmission routing equipment o TX becomes TXA F indicates that a...

Page 23: ...ll be shown on remote panel display 5 1 ADJUSTING THE DISPLAY CONTRAST The display contrast can be adjusted as follows With the panel turned on press the Lamps Test and keys at the same time The contrast adjustment bar and ambient temperature will appear on the display To increase the contrast press the Lamps Test and keys at the same time To decrease the contrast press the Lamps Test and keys at ...

Page 24: ... enabling wall fixing the panel has available two entries covered by cable tray for laying cables through the interior of the container OFF ON Reset Verifica Lampade Riarmo Sirena Tacitazione Sirena Aumento Ritardo Allarme Guasto Escluso Sirena Esclusa Aumento Ritardo OFF ON Reset Verifica Lampade Riarmo Sirena Tacitazione Sirena Aumento Ritardo Allarme Guasto Escluso Sirena Esclusa Aumento Ritard...

Page 25: ...ive input 9 RS485 B BUS RS485 negative input 10 Free 11 Free 12 RS485 A BUS RS485 positive output 13 RS485 B BUS RS485 negative output 14 C Form C Relay common contact 15 NA Form C Relay normally Open contact 16 NC Form C Relay normally Closed contact 6 2 CONNECTIONS The maximum cable length between the control panel and FKP500 Consolle must not exceed 1200m It is suggested a shielded cable compos...

Page 26: ...one FKP500 Consolle only and control panel execute connections as shown in figure 4 End of line resistors of data channel RS485 must be enabled both on control panel and remote panel Fig 4 Point to point connection Control Panel Remote Panel Power supply REMOTE PANEL 24 Vdc ...

Page 27: ...e ends of the connection shall have enabled the end of line resistors of data channel RS485 whether panels are remote or control panels 000201 Power supply Power supply Bus 485 Bus 485 Max Length 1200m Remote panel Remote panel Control panel Fig 5 Multi point connection remote panels are at the end of the connection in this case there must be removed jumper JP2 RA on interface board RS232 485 moun...

Page 28: ...200 Max Length 1200m Power supply Power supply Bus 485 Bus 485 Remote panel Remote panel Control panel Fig 6 Multi point connection control panel at one end of the connection Remote Panel Remote Panel 24 Vdc ...

Page 29: ...esent 5 jumpers allowing to set panel address Place the jumpers based on desired address this operation must be performed with panel powered off Fig 7 Selection of the address via the jumpers 1 5 9 13 17 21 25 29 2 6 10 14 18 22 26 30 3 7 11 15 19 23 27 31 4 8 12 16 20 24 28 32 ...

Page 30: ... bin on the product or on its packaging indicates that this product must not be disposed of with your other household waste Instead it is your responsibility to dispose of your waste equipment by handing it over to a designated collection point for the recycling of waste electrical and electronic equipment The separate collection and recycling of your waste equipment at the time of disposal will h...

Page 31: ...AGE 33 4 INDICATEURS TOUCHES ET RELAIS 34 4 1 INDICATEURS SUR FACADE 34 4 2 TOUCHES 34 4 3 RELAIS 35 5 FONCTIONNEMENT 36 5 1 RÉGLAGE DU CONTRASTE DU DISPLAY 37 6 INSTALLATION 38 6 1 DESCRIPTION PLAQUE A BORNES 39 6 2 RACCORDEMENTS 39 6 2 1 Raccordement point point 40 6 2 2 Raccordement multipoint 41 7 ADRESSAGE 43 8 CARACTERISTIQUES TECHNIQUES 44 ...

Page 32: ... les centrales de détection incendie de la série Elkron FAP54 Le panneau est logé dans un boîtier pour être utilisé soit sur table soit sur mur La Console FKP500 permet un contrôle actif et constant sur l état de la connexion avec la centrale La série de centrales FAP54 permet de gérer jusqu à 16 panneaux à distance placés à une distance maximum de 1200m La connexion entre la centrale et les panne...

Page 33: ...ection et de signalisation d incendie pour édifices FKP500 À utiliser avec l un des systèmes de détection d incendie suivants CDS FAP541 FAP544 FAP548 FAP5416 Listes des options avec prérequis 7 8 Sorties vers les dispositifs d alarme incendie 7 11 Retards des sorties 7 12 Corrélations sur plusieurs signaux d alarme 8 3 Signal de panne à partir des points 9 5 Hors service des points adressables 10...

Page 34: ...re clignotante il indique que la centrale est alimentée par batterie 4 2 TOUCHES Touche Description Sélection du type d événement visualisé sur l écran Rotation des messages visualisés sur l écran Réinitialisation Touche de redémarrage de la centrale reset global Sujet à habitation par clé mécanique Vérification Lampes Touche pour la vérification des indicateurs lumineux et acoustique Cela provoqu...

Page 35: ...ettre sur ON Le clavier est actif seulement après avoir programmé en centrale la présence du panneau à distance Quand le panneau est reconnu par la centrale et celle ci contrôle sa présence sur l écran en haut à gauche apparaissent alternativement les caractères et Pour plus de détails consulter le manuel de programmation de la centrale 4 3 RELAIS Dans la Console FKP500 est présent un relais qui e...

Page 36: ...ndiquent Où ACTION RETARDEE indique que sur la centrale il y a un retard d activation de les sorties d alarme SIRENE PANNE indique que la sortie sirènes est in panne SIRENE EXC SIL indique que la sortie sirènes exclu ou silencieuse COM E sont les indications du communicateur aux dispositifs du transmission d alarme de type E COM J sont les indications du communicateur aux dispositifs du transmissi...

Page 37: ...isées les informations suivantes 5 1 RÉGLAGE DU CONTRASTE DU DISPLAY Il est possible de régler le contraste de l écran en procédant comme suit Le panneau alimenté appuyer simultanément les touches Vérification Lampes et Successivement apparaîtra sur l écran l indication de la barre de réglage du contraste et la température ambiante Pour augmenter le contraste appuyer ensemble les touches Vérificat...

Page 38: ...sents 3 trous qui permettent la fixation murale le panneau dispose de deux entrées couvertes par passe câble pour le passage des câbles à l intérieur du boîtier OFF ON Reset Verifica Lampade Riarmo Sirena Tacitazione Sirena Aumento Ritardo Allarme Guasto Escluso Sirena Esclusa Aumento Ritardo OFF ON Reset Verifica Lampade Riarmo Sirena Tacitazione Sirena Aumento Ritardo Allarme Guasto Escluso Sire...

Page 39: ... négative transmission RS485 10 Libre 11 Libre 12 RS485 A Sortie positive transmission RS485 13 RS485 B Sortie négative transmission RS485 14 C Contact commun relais 15 NA Contact normalement ouvert relais 16 NC Contact normalement fermé relais 6 2 RACCORDEMENTS Le raccordement des données entre la centrale et la console FKP500 ne doivent pas dépasser la longueur maximum de 1200m On conseille l ut...

Page 40: ...et la centrale exécuter les connexions comme reporté dans figure 4 Les résisteurs de fin de ligne du canal de données RS485 doivent être habilités à la fois sur la centrale et sur le panneau à distance Fig 4 Raccordement point point Panneau à distance Centrale Alimentation PANNEAU A DISTANCE 24 Vcc ...

Page 41: ...voir habilitées les résistances de fin de ligne du canal de données RS485 indépendamment qu il s agisse de panneaux à distance ou centrale 000201 Alimentazione Alimentazione Bus 485 Bus 485 Lunghezza Max 1200m Pannello remoto Pannello remoto Centrale Fig 5 Raccordement multipoint panneaux à distance à l extrémité de la connexion dans ce cas le cavalier JP2 RA doit être enlevé sur la carte interfac...

Page 42: ...42 Fig 6 Raccordement multipoint centrale à une extrémité de la connexion Panneau à distance Panneau à distance Alimentation Alimentation Longueur max 1200m PANNEAU A DISTANCE PANNEAU A DISTANCE 24 Vcc ...

Page 43: ...ts qui permettent d imposer l adresse du panneau Placer les ponts en fonction de l adresse désirée cette opération doit être exécutée le panneau non alimenté Fig 7 Sélection de l adresse par les ponts 1 5 9 13 17 21 25 29 2 6 10 14 18 22 26 30 3 7 11 15 19 23 27 31 4 8 12 16 20 24 28 32 ...

Page 44: ...lage indique que ce produit ne doit pas être éliminé avec vos autres déchets ménagers Au lieu de cela il est de votre responsabilité de vous débarrasser de vos équipements usagés en les remettant à un point de collecte spécialisé pour le recyclage des déchets des équipements électriques et électroniques DEEE La collecte et le recyclage séparés de vos équipements usagés au moment de leur mise au re...

Page 45: ...ODUCTO 46 3 MARCADO 47 4 LEDS TECLAS Y RELÉ 48 4 1 LEDS FRONTAL 48 4 2 TECLAS 48 4 3 RELÉ 49 5 FUNCIONAMIENTO 50 5 1 REGULAZION DEL CONTRASTE DEL DISPLAY 51 6 INSTALACIÓN 52 6 1 DESCRIPCIÓN BORNES 53 6 2 CONEXIONADO 53 6 2 1 Conexión punto punto 54 6 2 2 Conexión multi punto 55 7 DIRECCIONAMIENTO 57 8 CARÁCTERISTICAS TÉCNICAS 58 ...

Page 46: ...sobre el estado de la conexión con la central La serie de centrales FAP54 permite gestionar hasta 16 paneles remotos instalados a una distancia máxima de 1200m La conexión entre la central y los paneles remotos se realiza mediante una conexión RS485 de 2 hilos a 9600 Bit s el puerto de comunicación RS485 del panel es auto aislado y esto permite la utilización de los paneles con alimentaciones dife...

Page 47: ...eccion de incendio en edificios FKP500 Para ser utilizado con uno de los siguientes sistemas de detección de incendios CDS FAP541 FAP544 FAP548 FAP5416 Lista de opciones con requisitos 7 8 Salida al dispositivo de alarme incendio 7 11 Retardo de la salida 7 12 Corrlacion en mas de una senal de alarma 8 3 Senal de fallo para los puntos 9 5 Fuera de servicio de los puntos direccionables 10 Condicion...

Page 48: ... TECLAS Tecla Descripción Selección del tipo de evento visualizado en el display Rotación del mensaje visualizado en el display Reset Tecla de rearme de la central reinicio general Sujeto a previa habilitación mediante llave mecánica Verificación Indicadores Tecla para la verificación de los indicadores luminosos y sonoro Se activan los indicadores durante algunos segundos Silenciar Re armar Siren...

Page 49: ...r posicionarla en la posición ON El teclado solo estará activo si previamente se habilitado en la central el panel remoto Cuando el panel es reconocido por la central y a la vez controlada por la misma sobre el display en su parte alta a la izquierda se visualizan alternadamente los caracteres e Para más información referirse al manual de programación de la central 4 3 RELÉ En la Consola FKP500 ha...

Page 50: ...RDO ACTIVO indica que en la central hay presente un retardo de activaciones FALLO SIRENA indica que la salida sirena de la central está averiada SIRENA ESC SILEN indica que la salida sirena de la central está excluida o silenciada COM E es la indicación del comunicador para dispositivos de transmisión de alarma tipo E COM J es la indicación del comunicador para dispositivos de transmisión de fallo...

Page 51: ...ZION DEL CONTRASTE DEL DISPLAY Es posible regular el contraste del display operando del siguiente modo Con el panel alimentado pulsar simultáneamente las teclas Verificación Indicadores y Seguidamente aparecerá en el display la barra de regulación del contraste y la temperatura ambiente Para aumentar el contraste pulsar consecutivamente las teclas Verificación Indicadores y Para disminuir el contr...

Page 52: ...ue permite su fijación a la pared el panel dispone de dos entradas cubiertas por unos pasa cables que facilitan la entrada de cables al interior del contenedor OFF ON Reset Verifica Lampade Riarmo Sirena Tacitazione Sirena Aumento Ritardo Allarme Guasto Escluso Sirena Esclusa Aumento Ritardo OFF ON Reset Verifica Lampade Riarmo Sirena Tacitazione Sirena Aumento Ritardo Allarme Guasto Escluso Siren...

Page 53: ...S485 B Entrada negativa trasmisión RS485 10 Libre 11 Libre 12 RS485 A Salida positiva trasmisión RS485 13 RS485 B Salida negativa trasmisión RS485 14 C Contacto común relé 15 NA Contacto normalmente abierto relé 16 NC Contacto normalmente cerrado relé 6 2 CONEXIONADO El conexionado de datos entre la central y la Consola FKP500 no debe superar la longitud máxima de 1200m Recomendamos el uso de un c...

Page 54: ...sola FKP500 y la central seguir el conexionado como se indica en la figura 4 La resistencia de final de línea del canal de datos RS485 debe de ser habilitada tanto en la central como en el panel remoto Fig 4 Conexión punto punto Central Panel remoto Alimentación PANEL REMOTO 24 Vcc ...

Page 55: ...tar las resistencias de fin de línea del canal de datos RS485 independientemente de que se trate de paneles remotos o de una central 000201 Alimentazione Alimentazione Bus 485 Bus 485 Lunghezza Max 1200m Pannello remoto Pannello remoto Centrale Fig 5 Conexionado multi punto panel remoto en la extremidad de la conexión en este caso debe de ser quitado el puente JP2 RA de la tarjeta interface RS232 ...

Page 56: ...56 Fig 6 Conexionado multi punto central en un extremo de la conexión Longitud Máx 1200m Panel remoto Panel remoto Central Alimentación Alimentación Panel remoto Panel remoto 24 Vcc ...

Page 57: ...tes que permiten configurar la dirección del panel Posicionar el puente en base a la dirección deseada esta operación debe ser realizada con el panel no alimentado Fig 7 Selección de la dirección mediante los puentes 1 5 9 13 17 21 25 29 2 6 10 14 18 22 26 30 3 7 11 15 19 23 27 31 4 8 12 16 20 24 28 32 ...

Page 58: ... su embalaje indica que dicho producto no debe desecharse junto con los otros residuos domésticos Por el contrario es responsabilidad del usuario desechar el equipo entregándolo a un punto de recogida designado para el reciclaje de residuos de equipos eléctricos y electrónicos La recogida separada y el reciclaje de estos residuos en el momento de su eliminación ayudarán a conservar los recursos na...

Page 59: ...59 ...

Page 60: ... 3986703 Milano Tel 39 02 334491 Fax 39 02 33449213 www elkron com mail to info elkron it ELKRON è un marchio commerciale di URMET S p A ELKRON is a trademark of URMET S p A Via Bologna 188 C 10154 Torino TO Italy www urmet com MADE IN ITALY ...

Reviews: