background image

3/8 

 

 
 

 

 

GENERAL DESCRIPTION

 

Based on a microcontroller and equipped with a 
short  circuit  isolator,  the  digital  heat  detector 

FDT500

 offers maximum reliability and accuracy 

for temperature sensing. 
The detector is a fixed threshold type, therefore 
an  Alarm  condition  will  be  initiated  when  the 
temperature exceeds the limit of the class A1S. 
The  FDT500  is  able  to  store  automatically,  into 
its  non  volatile  memory,  thirty  measures  before 
and  thirty  measures  after  the  smoke  alarm 
condition. 
These measures can be displayed in graphic or 
in text mode on the Control Panel monitor. 
This  feature  is  very  important  to  understand 
what  has  happened  before  and  after  the  alarm 
condition being detected. 
The  bi-colour  LED  (green-red),  in  operating 
mode,  indicates  the  detector  condition  while,  in 
service  mode,  it  can  be  used  to  show  the 
detector’s  address  by  a  special  function 
activated from Control Panel. 
or  further  information  refer  to  the  manual  FAP 
series Control Panel

’s programming manual. 

 

MAINTENANCE 

(trained personnel)

 

Generally  no  maintenance  is  needed  for  this 
type of detector. 
If  the  environmental  conditions  where  the 
detector  is  installed  are  not  ideal  (presence  of 
high  rate  of  humidity,  dust,  dirt)  to  maintain 
optimal  operation  is  recommended  to  clean  the 
sensing element at least once per year. 
Remove  the  detector  head  from  the  base  and 
carefully  clean  the  sensing  element  with 
pressurised air. 
 

ADDRESSING

 

The  address  (1-128)  is  software  set  and  stored 
in a non-volatile memory.  
The  detector  can  be  addressed,  in  manual  or 
automatic mode from the Control Panel. 
For 

further 

details  see  Control  Panel’s 

programming manual. 

 

MOUNTING

 

Lean  the  detector  head  on  the  base;  while 
pressing,  turn  it  clockwise  until  it  enters  in  the 
seat of the base as illustrated in the figure. 

 

 

 

 

 
 
 
 

ENGLISH 

Summary of Contents for FDT500

Page 1: ... l indirizzo del rivelatore tramite una funzione attivata dalla centrale Per ulteriori informazioni fare riferimento al manuale programmazione delle centrali ELKRON serie FAP54 MANUTENZIONE personale addestrato In generale nessuna manutenzione è richiesta per questo tipo di rivelatore In particolari condizioni ambientali di esercizio alto tasso di umidità polvere sporcizia per mantenere il corrett...

Page 2: ...i test riportare il sistema nelle normali condizioni operative e comunicare il ripristino alle Autorità competenti CARATTERISTICHE TECNICHE Tensione di funzionamento 20 Vcc 15 10 modulata Assorbimento medio Condizioni normali 250 A 20Vcc Assorbimento medio Condizioni di allarme 2 mA 20Vcc Soglia di allarme statico 58 C 5 LED Bicolore Rosso fisso Stato di allarme Rosso lamp lento 2s Stato di allarm...

Page 3: ...e mode it can be used to show the detector s address by a special function activated from Control Panel or further information refer to the manual FAP series Control Panel s programming manual MAINTENANCE trained personnel Generally no maintenance is needed for this type of detector If the environmental conditions where the detector is installed are not ideal presence of high rate of humidity dust...

Page 4: ...fy the status to the competent Authorities TECHNICAL SPECIFICATIONS Operating voltage 20 Vdc 15 10 modulated Average power consumption Normal condition 250 A 20Vdc Average power consumption Alarm condition 2 mA 20Vdc Static Alarm Threshold 58 C 5 Bi colour LED Red steady alarm condition Red blinking slow 2s alarm condition with SLC operating voltage 17V Green blinking slow 2s normal condition Gree...

Page 5: ... mientras en modalidad de servicio puede ser utilizado para visualizar la dirección del sensor mediante una función específica desde la central Para más información ver al manual de programación de la central ELKRON serie FAP MANTENIMIENTO personal autorizado En general no se requiere ningún mantenimiento para este tipo de sensor En condiciones ambientales especiales de funcionamiento alto nivel d...

Page 6: ...dejar el sistema en su condición normal de funcionamiento y avisar a la autoridad competente CARACTERÍSTICAS TÉCNICAS Tensión de funcionamiento 20 Vcc 15 10 modulada Consumo medio Condición normal 250 A 20Vcc Consumo medio Condición de alarma 2 mA 20Vcc Temperatura de alarma estatica 58 C 5 LED bi color Rojo fijo Estado de alarma Rojo inter lento 2s Estado de alarma con SLC tensión operativa 17V V...

Page 7: ...t or on its packaging indicates that this product must not be disposed of with your other household waste Instead it is your responsibility to dispose of your waste equipment by handing it over to a designated collection point for the recycling of waste electrical and electronic equipment The separate collection and recycling of your waste equipment at the time of disposal will help to conserve na...

Page 8: ...02 334491 Fax 39 02 33449213 www elkron com mail to info elkron it ELKRON è un marchio commerciale di URMET S p A ELKRON is a trademark of URMET S p A ELKRON es una marca registrada de URMET S p A Via Bologna 188 C 10154 Torino TO Italy www urmet com MADE IN ITALY ...