7.12  TELEPHONE NUMBER ASSOCIATION MENU / FAILURE

• This procedure is used to associate the telephone numbers to be called in the case of a

technical failure and to establish whether the call is a voice message.

Select the telephone numbers to

be called by pressing 

,  

to select the required number and

C

 to enable or disable it.

On = symbol

*

Off = symbol

-

telephone
number 1

telephone
number 12

to confirm

the selection

VOC FAULT-PH.NR

> - - - -*-*-*- - -  <

In this example, a voice
message will be sent following
technical failures to numbers 5,
7 and 9.

ENGINEER MENU

ASSOC. FAULT-PH.NR

VOC FAULT-PH.NR

> - - - - - - - - - - - -  <

INSTALLER MENU

ASSOC. FAULT-PH.NR

Summary of Contents for CT06

Page 1: ...CT06 LBT80411 Installation manual PSTN telephone communicator DS80CT49 004B ...

Page 2: ...and remote control function 13 5 5 Default settings 15 5 6 Language selection 16 5 7 Viewing system status 16 6 0 User programming 18 6 1 User Programming list 18 7 0 Engineer programming 19 7 1 Engineer programming list 19 7 2 Telephone number programming list 20 7 3 Output switching menu 21 7 4 Answering service menu for remote controls 22 7 5 Engineer code changing menu 22 7 6 Call Test menu 23...

Page 3: ...essages 60 seconds integrated voice synthesis Remote control feedback by voice messages Non volatile memory operation ensured also during a black out Answering service function Remote call barring DTMF control Skip outgoing message on PSTN line PSTN telephone line test System status menu User menu Engineer menu On board alphanumeric keypad with 2 line 16 character LCD 6 system status and warning L...

Page 4: ...low A A A B A WALL FASTENING HOLES B WIRE PASSAGE ARRANGEMENTS box bottom 1 2 3 4 2 0 Installation 2 1 OPENING CLOSING THE BOX B B B B 2 2 REMOVAL MICROSWITCH INSTALLATION CONNECTION 1 1 2 2 8 8 7 7 6 6 3 3 4 4 5 5 1 2 3 Fit the plug in the suitable seat and adjust the screw until it comes out by 10mm Place the microswitch as shown in the figure Use 2 TAMPER plugs as a support to connect the micro...

Page 5: ...elephone numbers and selecting programming parameter values Key for accessing the SYSTEM STATUS MENU in combination with number keys and for deleting telephone numbers 1 7 4 2 8 5 0 3 9 6 C ABC DEF GHI JKL MNO PQRS TUV WXYZ NETWORK BATTERY ON NETWORK OK OFF NO NETWORK BLINKING LOW BATTERY TELEPHONE FAILURES OFF NORMAL SLOW BLINK FAILURE MEMORY FAST BLINK FAILURE PRESENT ALARM MEMORY OFF NORMAL SLO...

Page 6: ...put 4 IN3 TC input 5 GND 6 PWR 12Vdc power input 7 PWR power input 8 BAT battery 9 BAT battery 10 U1 failure electrical output 11 U2 failure electrical output 12 U3 switching electrical output 13 U4 switching electrical output 14 C 15 N C U5 switching relay output 16 N O 17 Vaux 12Vdc spare Imax 150 mA 18 Vaux 0V 19 tamper protection 20 tamper protection 21 headset socket 4 1 DESCRIPTION OF THE BO...

Page 7: ... and 12V TC ON is provided when the TC input is programmed as N O normally closed 4 3 DESCRIPTION OF THE OUTPUTS U1 and U2 FAILURE OUTPUTS These electrical outputs are dedicated to signalling FAILURES They normally output a 12Vdc signal which is down when the output is signalling Two types of failures are controlled namely TECHNICAL FAILURES and TELEPHONE FAILURES Output U1 is dedicated to technic...

Page 8: ...ed as maintained or timed 5 sec 10 sec 30 sec 60 sec 90 sec Associating an output to an input makes the output activate switch and return to de energised condition in different ways according to the type of associated input If the associated input is 24h the output will activated switched to 12V when the associated input status changes from de energised condition Two cases are possible if the asso...

Page 9: ...t cycle outcome NOTE Fault recovery can be brought forward by manually sending a test call provided that the call is successful 4 5 CYCLE HISTORY FAILURE and ANOMALY events are stored in an archive with the total number of cycles to verify the reliability of the communicator in time See Viewing system status for viewing the cycle history 4 6 SAFETY RULES In accordance with EN41003 standards a SELV...

Page 10: ...CT06 Power Supply Output 1 Output 2 Note it is advisable to connect the plug with the electric system ground to ensure better protection against overvoltage caused by weather events Control Panel BURGLARY ALARM OUTPUT PANIC ALARM OUTPUT Connect 24h input in control panel to manage communicator tamper protection The relay must be wired out of the communicator for safety standard requirements diode ...

Page 11: ... can be viewed in the SYSTEM STATUS menu 7 Stored information will be automatically reset at the next transaction of the TC input from ON to OFF i e following a new system activation or manually by means of the SYSTEM STATUS menu 5 2 VOICE CALL CYCLE After an alarm a vocal call is made on each event associated phone number to which basis message with 10 sec duration is sent followed by message ass...

Page 12: ...Example of barring 5 3 STOPPING THE CALL CYCLE The call cycle can be stopped by dialling 12 in DTMF called Barring code on the tel ephone receiving the voice call Voice messages can be barred as shown below The call in progress and the remaining call cycle voice and text messages will be com pleted if the Barring code is entered If the input that caused the alarm is subjected to TC the call cycle ...

Page 13: ...or 0 is used to activate or deactivate the required output The communicator will give priority to an alarm triggered during the remote control procedure No on off commands will be accepted and a WRONG CODE BEEP will be output Hang up Each remotely controllable output can be programmed as maintained or timed Status changes follow the command if the output is maintained The on command 1 will activat...

Page 14: ...IT RECEIVED CODE DIGIT RECEIVED CODE DIGIT RECEIVED CODE DIGIT RECEIVED CODE DIGIT BEEEEP WRONG CODE 1 2 5 RECEIVED 0 5s BEEP Send code 5 3 3 Send code corresponding to output to be switched OR OR repeat procedure from point 2 RECEIVED 0 5s BEEP 4 4 5 OR 0 Send code 1 on or 0 off 5 1 OR 0 5s 3 BEEPS COMMAND DONE ASSOCIATED VOICE MESSAGE More than one output can be switched or the same output more ...

Page 15: ... type association Failure 6th VOICE MESSAGE PSTN parameters Country Italy Dialling method MF PBX derivation off Tone check off Answer check off PSTN line test off Answering service for remote controls Off User code Code 111111 Engineer code Code 000000 enabled RESETTING DEFAULT PARAMETERS To return the communicator to default parameters 1 Disconnect power and battery where present 2 Reconnect powe...

Page 16: ...G LEDS 5 7 VIEWING SYSTEM STATUS The SYSTEM STATUS menu can be accessed in any condition without entering a code Simply press C followed by a number key 1 2 3 5 7 8 9 Either press to quit the menu or wait for the time out one minute IN Not QUITTED IN 1 alarm memory IN 2 CLEAR alarm mem IN BUTTONS TO PRESS LANGUAGE FRENCH GERMAN DISPLAY TRANSMETTEUR RTC COMMUNICATOR PSTN KOMMUNIKATOR PSTN SELECT LA...

Page 17: ...L OUTCOME ASSOCIATED TO PHONE NUMBER NEXTNUMBER PSTN ANOMALY SOFTWARE RELEASE BOARD INDICATION OPERATION CONDITIONS TELEPHONE LINE TONES CALL OUTCOME X Tone control enabled Selection tone absent Call not made or unavailable S Tone control enabled and Free tone absent Only selection made answer control enabled silence after selection O Tone control enabled and or Busy tone Call not made answer cont...

Page 18: ...T Enter the 6 digit user code x x x x x x default 111111 Press to scroll the menu forwards Press to scroll the menu backwards Press to quit the menu 20 21 23 24 page p a g e page page 22 page 22 page Access to the installation menu will be disabled once the user code is entered USER MENU TELEPHONE NR USER MENU SWITCH OUTPUT USER MENU CODE CHANGING USER MENU CALL TEST USER MENU VOCAL MESSAGES USER ...

Page 19: ... made because the system is being supervised at the time 7 1 ENGINEER PROGRAMMING LIST Enter the 6 digit user code x x x x x x default 000000 20 21 22 23 29 30 31 32 page page page page page page page page 22 page 25 page CT11 M only 24 page ENGINEER MENU TELEPHONE NR ENGINEER MENU SWITCH OUTPUT ENGINEER MENU CODE CHANGING ENGINEER MENU CALL TEST ENGINEER MENU ANSWERING PROG ENGINEER MENU VOCAL ME...

Page 20: ...o enter the required telephone number digits Press to include a 2 seconds pause during dialling To edit a telephone number position the cursor on the digit to be changed by pressing and enter the new digits Press C to delete the entire number Press 0 for at least one second to enter the international prefix Press 7 PQRS for at least one second to enter Press 9 WXYZ for at least one second to enter...

Page 21: ...iginal condition to select the outputs to confirm the output to switch to return to the output switching menu to confirm the selection The current output status is displayed Press C to change ENGINEER MENU SWITCH OUTPUT SWITCH OUTPUT OUTPUT NR 3 SWITCH OUTPUT OUTPUT NR 4 SWITCH OUTPUT OUTPUT NR 5 OUTPUT NR 5 DISABLED OUTPUT NR 5 ENABLED SWITCH OUTPUT OUTPUT NR 5 ...

Page 22: ...7 4 ANSWERING PROGRAMMING MENU for remote controls This procedure can be used to activate the answering service function permitting a connection between the caller and the communicator to operate remote controls to confirm The answering service function will be activated also if the skip outgoing message is automatically activated The number of rings on CM10 M are only indicative see paragraph 6 7...

Page 23: ...er Press the communicator will make three calls to the 12th number repeating the basic voice message three times The test call cycle can be barred by dialling 12 in DTMF from the telephone which is receiving the call see paragraph 5 3 The test call will not be made if the 12th telephone number is not programmed ENGINEER MENU CALL TEST CALL TEST SEND ok eXIT COMMUNICATOR T12 PSTN ...

Page 24: ...larm 5 sec Input 2 alarm 5 sec Output U3 on 5 sec Output U3 off 5 sec Output U4 on 5 sec Output U4 off 5 sec Output U5 on 5 sec Output U5 off 5 sec TECHNICAL FAILURE 5 sec Scroll the list and select the message to be recorded or played to confirm the selection Press to start recording The remaining time will decrease on the display EXAMPLE to confirm selection ENGINEER MENU VOCAL MESSAGE VOCAL MES...

Page 25: ...s function is used to adapt the CT06 to the PSTN standards in force in various countries ENGINEER MENU pstn MENU PSTN MENU NETWORK PSTN MENU SELECTION TYPE PSTN MENU INTERNAL PH NR PSTN MENU TONE CONTROL PSTN MENU ANSWER CHECK PSTN MENU PSTN TEST PSTN MENU NETWORK PSTN MENU ITALY PSTN MENU FRANCE PSTN MENU AUSTRIA PSTN MENU GERMANY PSTN MENU SPAIN PSTN MENU PORTUGAL ...

Page 26: ...ON If the telephone line is connected to a switchboard internal line program the function by setting the number to engage the external line Use the scroll arrows to set the number to dial to make an external call e g 0 SELECTION TYPE mf TONE SELECTION TYPE dc TONE pstn MENU SELECTION TYPE INTERNAL PH NR DISABLED pstn MENU INTERNAL PH NR INTERNAL PH NR NUMBER ...

Page 27: ...n the affirmative case The presence of the ring back tone is checked at the end of the call If no tone is received the call will be interrupted and will be repeated later according to the programmed cycles Voice messages are played if the tone is detected and the answer check is disabled Off the voice message is played immediately after dialling without waiting for the called user to answer On the...

Page 28: ...ately 45 minutes with a NEGATIVE outcome no line tone Press the communicator will check for the presence of the telephone line every 15 minutes only when input 3 TC is off Press the communciator will check for the presence of the line every 15 minutes regardless of the status of input 3 TC PSTN TEST DISABLED PSTN TEST enabled 24H PSTN MENU PSTN TEST PSTN TEST enabled AND TC ...

Page 29: ...he status of input 3 AND TC and can be programmed with a delay of 5 sec 15sec etc to confirm selection to confirm selection to confirm selection Select AND TC programming to select the required delay 5s 15s 30s 60s 90s or instan taneous to confirm selection to select the inputs to select the inputs ENGINEER MENU INPUT PROGR INPUT PROGR INPUT NR 1 INPUT PROGR INPUT NR 2 INPUT 1 normALLY CLOSED INPU...

Page 30: ... page 9 Description of outputs to confirm the selection to select the outputs to confirm the selection to confirm the selection ENGINEER MENU OUTPUTS PROG OUTPUTS PROG OUTPUT NR 3 OUTPUTS PROG OUTPUT NR 4 OUTPUTS PROG OUTPUT NR 5 OUTPUTN 3 SWITCHABLE OUTPUT 3 STEADY OUTPUT N 3 NOT USED OUTPUT N 3 LINK INP 1 OUTPUT N 3 LINK INP 2 OUTPUT 3 5 SEC TIMED OUTPUT 3 90 S TIMED ...

Page 31: ...umbers to be called by pressing to select the required number and C to enable or disable it On symbol Off symbol telephone number 1 telephone number 12 to confirm the selection I 2 VOCAL PH NR In this example numbers 5 7 and 9 have been enabled for voice calls on input 2 to select the inputs ENGINEER MENU ASSOC INP PH NR ASSOC INP PH NR INPUT 1 ASSOC INP PH NR INPUT 2 I 2 VOCAL PH NR ENGINEER MENU...

Page 32: ...oice message Select the telephone numbers to be called by pressing to select the required number and C to enable or disable it On symbol Off symbol telephone number 1 telephone number 12 to confirm the selection VOC FAULT PH NR In this example a voice message will be sent following technical failures to numbers 5 7 and 9 ENGINEER MENU ASSOC FAULT PH NR VOC FAULT PH NR INSTALLER MENU ASSOC FAULT PH...

Page 33: ...witching Deployed battery threshold 10 8V Tamperproof Minimum working voltage 12V Max working voltage 14 5V Typical stand by intake 70 mA Maximum uptake 250 mA Current available on auxiliary power output Imax 150mA Allocated accumulator 12V 2 2 Ah Display LCD 2 rows 16 characters Working temperature range from 5 to 40 C Dimensions 245 L x 185 H x 70 P Case protection level IP3X WARNING Lead batter...

Page 34: ......

Page 35: ......

Page 36: ...ELKRON TEL 39 011 3986711 FAX 39 011 3986703 www elkron com e mail info elkron it ELKRON is a trademark of URMET S p A Via Bologna 188 C 10154 Torino TO Italy www urmet com MADE IN ITALY ...

Reviews: