Eliwell IDplus 961 Manual Download Page 26

ID 961

3/4

Tab. 1

Parameter Table

PAR.

diF

HSE
LSE

Ont

OFt

dOn

dOF

dbi

OdO

dty

dit
dCt

dOH

dEt

dPO

LOC

PA1

CA1

ddL

dro

H00 (1)
H42
reL
tAb

UL
dL
Fr

(1) For 230 V

a

models the default value is 1 (NTC input, see the label on the instrument).

* VALUE column: to be filled manually, with customized settings (if different from the default value).
** LEVEL column: indicates the level of visibility of parameters accessible by PASSWORD (see the related paragraph)

DESCRIPTION

COMPRESSOR REGULATOR (folder with “CP” label)

diFferential. Relay compressor tripping differential. The compressor stops on reaching the
Setpoint value (as indicated by the adjustment probe), and restarts at temperature value
equal to the Setpoint plus the value of the differential.
Note: the value 0 cannot be assumed.
Higher SEt. Maximum possible setpoint value.
Lower SEt. Minimum possible setpoint value.

COMPRESSOR PROTECTIVE DEVICE (folder with “CP” label)

On time (compressor). Compressor activation time in the event of faulty probe. If set to
“1” with Oft at “0” the compressor is always on, while at Oft >0 it functions always
in duty cycle mode.
OFF time (compressor). Compressor in disabled state time in the event of a faulty probe.
If set to “1” with Ont at “0” the compressor is always off, while at Ont >0
it functions always in duty cycle mode.
delay (at) On compressor. Delay time in activating the compressor relay after switch-on
of instrument
delay (after power) OFF. Delay after switch off; the indicated time must elapse between
switch-off of the compressor relay and the successive switch-on.
delay between power-on. Delay between switch-ons; the indicated time must elapse
between two successive switch-ons of the compressor.
delay Output (from power) On. Delay time in activating the outputs after switch-on of
the instrument or after a power failure.

DEFROSTING REGULATOR (folder with “dEF” label

Defrost type. 
0 = electric defrost;
1 = reverse cycle defrost (hot gas);
2 = Free defrost (compressor hot).
defrost interval time. Interval between the start of two successive defrosting operations.
defrost Counting type. Selection of count mode for the defrosting interval.
0 = compressor operating hours (DIGIFROST® method);
1 = Real Time – appliance operating time;
2 = compressor stop.
defrost Offset Hour. Start-of-defrosting delay time from start up 
of instrument.
defrost Endurance time. Defrosting time-out; determines duration of
defrosting.
defrost (at) Power On. Determines if at the start-up the instrument must enter defrosting
(if the temperature measured by the evaporator allows this operation).
y = si; n = no.

DISPLAY (folder with “diS” label)

(keyboard) LOCk. Keyboard locking. However, you can enter parameter programming
modify them along with the status of this parameter in order to allow keyboard locking.
y = yes; n = no
PAssword 1. When enabled (value other than 0) it constitutes the access key for
level 1 parameters.
CAlibration 1.Calibration 1. Positive or negative temperature value added to the value
read by probe 1, based on “CA” parameter settings.
defrost display Lock. Viewing mode during defrosting.
0 = shows the temperature read by the thermostat probe;
1 = locks the reading on the temperature value read by thermostat probe when 
defrosting starts, and until the next time the Setpoint value is reached;
2 = displays the label “deF” during defrosting, and until the next time the
Setpoint value is reached.
display read-out. Select °C or °F for displaying  the temperature read by the probe.
0 = °C, 1 = °F.

CONFIGURATION (folder with “CnF” label)

Probe type selection, PTC or NTC. 0 = PTC; 1 = NTC.
evaporator sensor present.
reLease firmware. Device version: read only parameter.
tAble of parameters. Reserved: read only parameter.

COPY CARD (folder with “Fpr”label)

Up load. Programming parameter transfer from instrument to Copy Card.
Down load. Programming parameter transfer from Copy Card to instrument
Format. Erasing all data in the copy card.

NOTA BENE: using “Fr” parameter (copy card formatting) the data within the copy

DEFAULT

2.0

99.0

-50.0

0

1

0

0

0

0

0

6
1

0

30

n

n

0

0

1

0

0
y

/
/

/
/
/

RANGE

0.1...30.0

LSE..302

-55.0...HSE

0...250

0...250

0...250

0...250

0...250

0...250

0/1/2

0...250

0/1/2

0...59

1...250

n/y

n/y

0...250

-12.0...12.0

0/1/2

0/1

0/1
n/y

/
/

/
/
/

VALUE*

LEVEL**

1

1
1

1

1

1

1

1

1

1

1
1

1

1

1

1

1

1

1

1

1
1
1
1

1
1
1

U.M.

°C/°F

°C/°F
°C/°F

min

min

sec

min

min

min

flag

hures

flag

min

min

flag

flag

number

°C/°F

flag

flag

flag
flag

/
/

/
/
/

Summary of Contents for IDplus 961

Page 1: ...Electronic controllers for refrigerating units GB ID PLUS 961 971 974...

Page 2: ......

Page 3: ...OMMANDS EDIT LOCK 7 PROGRAMMING MENU 7 COPY CARD 8 PASSWORD 9 ENABLING DEFROST CYCLE MANUALLY 9 DIAGNOSTICS 9 ALARMS 10 MAX AND MIN TEMPERATURE ALARM 11 MECHANICAL ASSEMBLY 12 ELECTRICAL WIRING 12 CON...

Page 4: ...t they all function correctly To activate the LOC function enter the Basic Commands menu by pressing press the and keys within 2 seconds If the LOC function is active and you try to enter the Paramete...

Page 5: ...menus SET ENTER Press and release Displays alarms if active Opens Basic Commands menu Press for at least 5 secs Opens the Programming menu Confirms commands Reduced Set Economy LED Flashing Reduced se...

Page 6: ...alarms folder only visible if an alarm is active SEt Set point setting folder Pb1 probe 1 folder Pb2 probe 2 folder dit interval between defrosts folder dEt defrost timeout folder dSt defrost end tem...

Page 7: ...d down the key for more than 5 seconds If specified the PA1 access PASSWORD will be requested see PASSWORD paragraph Press the key to modify the values The display will show the first folder in the me...

Page 8: ...loads the programming parameters from the device UPLOAD device Copy Card Format Fr This command is used to format the copy card an operation which is necessary when using the card for the first time I...

Page 9: ...tions are not satisfied the parameter OdO 0 Models ID961 ID971 and ID974 the evaporator probe Pb2 temperature is higher than the defrost end temperature Models ID971 and ID974 the display will flash 3...

Page 10: ...mperature alarm valuereadbyprobe1 HALafter timeof tAO seeMAX MINALARMStable RecordingoflabelAH1infolderAL Noeffectonregulation Waituntiltemperaturevalueread byprobe1returnsbelowHAL AL1 Probe1LOW tempe...

Page 11: ...int HAL AFd Relative Temperature Value to setpoint Att 1 if LAL is negative Set LAL Set if HAL is negative Set HAL Set Absolute Temperature Value Att 0 Temp LAL LAL with sign Temp HAL HAL with sign Te...

Page 12: ...trument In the model ID 974 with Switching power supply only one voltage free relay output is present on all other models on the contrary all relay outputs are voltage free Do not exceed the maximum c...

Page 13: ...pe as a Class A device in relation to the category and structure of the software Unpermitted use Any other use other than that permitted is de facto prohibited It should be noted that the relay contac...

Page 14: ...esin keys Dimensions front 74x32 mm depth 59 mm excluding terminals Mounting panel mounting with 71x29 mm 0 2 0 1 mm drilling template Terminals screw terminal for cable with a diameter of 2 5mm2 Conn...

Page 15: ...ard EN 60730 2 9 Food safety This device complies with standard EN 13485 as follows suitable for storage climate range A measurement class 1 in the range from 35 C to 25 C exclusively using Eliwell NT...

Page 16: ...VICE folder with CP label Ont On time compressor Compressor activation time in the event of faulty probe If Ont 0 the compressor is always off while Ont 0 the compressor is always on dOn delay at On c...

Page 17: ...e start up the instrument must enter defrosting if the temperature measured by the evaporator allows this operation y yes n no FANS REGULATOR folder with FAn label FSt Fan Stop temperature Fan lock te...

Page 18: ...alarm to lock loads n don t lock loads y lock loads DISPLAY folder with diS label LOC LOCk Basic Commands edit lock However you can enter parameter programming modify them along with the status of thi...

Page 19: ...nt reL reLease firmware Device version read only parameter tAb tAble of parameters Reserved read only parameter COPY CARD folder with Fpr label UL Up Load Programming parameter transfer from instrumen...

Page 20: ...c dOF 0 250 0 0 250 0 0 250 0 min dbi 0 250 0 0 250 0 0 250 0 min OdO 0 250 0 0 250 0 0 250 0 min dty 0 1 2 0 0 1 2 0 flag dit 0 250 6 0 250 6 0 250 6 hours dCt 0 1 2 1 0 1 2 1 0 1 2 1 flag dOH 0 59 0...

Page 21: ...50 0 0 250 0 0 250 0 min EAL n y n n y n n y n flag LOC n y n n y n n y n flag PA1 0 250 0 0 250 0 0 250 0 num ndt n y y n y y n y y flag CA1 12 0 12 0 0 0 12 0 12 0 0 0 12 0 12 0 0 0 C F CA2 12 0 12...

Page 22: ...Alimentation A TTL input Ingresso TTL Entrada TTL TTL Eingang Entr e TTL TTL 1 ID961 A thermostat N L TTL PLUS 2 3 6 7 8 9 10 A D I Supply 230Va 3W max Pb1 1 ID971 A 11 evaporator thermostat N L TTL...

Page 23: ...zione 230Va 10 15 50 60 Hz Consumption Consumo 3W max Display range Range di visualizzazione NTC 50 0 C 110 C PTC 55 0 C 140 C on display with 3 digits sign Accuracy Accuratezza Better than 0 5 of ful...

Page 24: ...he access PASSWORD will be requested parameter PA1 and the label of the first folder will follow To scroll through the other folders use the UP and DOWN keys To enter the folder press set The label of...

Page 25: ...ccording to its automatic operating fea tures as a 1 B type operated control type as a Class A device in relation to the cat egory and structure of the software UNPERMITTED USE Any other use other tha...

Page 26: ...type Selection of count mode for the defrosting interval 0 compressor operating hours DIGIFROST method 1 Real Time appliance operating time 2 compressor stop defrost Offset Hour Start of defrosting de...

Page 27: ...ut thermostat A TTL input for Copy Card NOTE Default user settings 1 2 3 6 7 8 9 ID 961 230 V A Wiring diagram Invensys Controls Italy s r l via dell Industria 15 Zona Industriale Paludi 32010 Pieve d...

Reviews: