background image

 
 

  

EN  

 

 

 

 

Panel

 

 

Panel Mount Programmable Controller  

Installation Manual

 

 
 

 

 

 

Summary of Contents for FREE Panel EVP 3300/C

Page 1: ...EN Panel Panel Mount Programmable Controller Installation Manual...

Page 2: ...e 12 4 Technical Data 14 4 1 General Technical Data 14 4 2 I O features 14 4 3 Display 15 4 4 Serials 15 4 5 Transformer 15 4 6 Mechanical dimensions 15 4 7 Permitted use 15 4 8 Improper Use 15 4 9 Di...

Page 3: ...as well as straightforward programming maintenance and servicing The EVP is designed for panel mounting and can also be wall mounted using a special backplate available as an accessory Programming of...

Page 4: ...rable NTC DI 1 remote current voltage configurable FREE Panel EVP 3500 C R is equipped with serial CAN RS485 and ETHERNET 3 inputs 1 on board humidity module 1 on board NTC 1 remote configurable NTC D...

Page 5: ...tion Make sure the area near the cooling slots is ventilated Mounting the FREE Panel EVP Designed for panel mounting Make a 138x68mm hole Remove the front panel figure 1 and make 4 holes in the panel...

Page 6: ...nputs Probes Probes have no connection polarity and can be extended using a normal two core cable note that the extension of the probes influences the electromagnetic compatibility EMC of the instrume...

Page 7: ...increased using appropriate repeater modules NOTE 2 Single terminal strip with 3 conductors use all 3 conductors for the signal and GS for the braid NOTE 3 Attach the 120 Ohm 1 4W resistors between t...

Page 8: ...supply Built in AI4 RH Sensor On board RH sensor EVP3500 C RH RS485 CAN GS 24 Va c 48 Vc RS485 CAN GS H L POWER Ethernet Remote Probes AI2 AI3 G example of Transducer AI3 G 12V External Power Supply A...

Page 9: ...ment and with the display backlighting mainly OFF In these conditions the following calibration values are obtained Compensation_AI1 12 0 C Compensation_AI4 10 5 C If the usage conditions require the...

Page 10: ...us RTU Master mode o EVEs are in Modbus RTU Slave mode 3 4 2 CAN connection example Field 1 FREE Panel EVP Max 12 FREE Evolution EVE expansion modules connected in CAN EVP EVE 1 485 485 GS 485 485 485...

Page 11: ...Max 127 FREE Evolution EVD EVC or FREE Smart or Eliwell and or third party instruments equipped with RS485 serial o EVP is in Modbus RTU Master mode o All devices equipped with RS485 are in Modbus RT...

Page 12: ...idual controllers and download up to 10 remote menus from the respective Evolution controllers In this case the remote menu allows local navigation of the individual Evolution controller PLC The varia...

Page 13: ...ains possible by way of FREE Studio NOTE refer to the section on Parameters ETHERNET PASSIVE PLUG IN folder BRIDGE FREE Studio allows monitoring of FREE Smart tools or third party tools typically Modb...

Page 14: ...on 1 B Pollution class 2 normal Over voltage category II Nominal pulse voltage 2500V Digital outputs refer to the label on the device Fire resistance category D Software class and structure A Type of...

Page 15: ...le in normal conditions The device must be adequately protected from water and dust with regard to the application and must only be accessible using tools with the exception of the front panel The dev...

Page 16: ...in Edit Mode 4 DOWN Scroll down Move to the next page e g 1 10 2 10 Decrease modify a value Go to previous label 5 Exit Exit menu page go back to previous menu Move cursor to left in Edit Mode press...

Page 17: ...te interfaces HMI and to display I O values and clock The DIA menu can be displayed in 5 languages English Italian German Spanish and French To change the default language open BIOS Parameters Display...

Page 18: ...press OK to update the clock Date and time 16 50 56 20 07 11 Update 5 4 Remote interface EVP Language 0 HMI sel Network COM setting HMI Management 5 4 1 Language This section is for setting the langu...

Page 19: ...1 10 EVP 10 10 File HMIREM KBD Id 0 Id 0 Id 0 Com CAN Com CAN Com CAN Addr 125 Addr 000 Addr 000 From these pages it is possible to launch run the corresponding menu if present Move the cursor onto a...

Page 20: ...The resource is read only W The resource is write only RW The resource can be both read and written to Indicates the size of the data in bits When the field indicates 1 the value read by the register...

Page 21: ...AI CALIBRATION Gain_Ntc_AI2 15617 WORD RW Ai2 NTC calibration gain 0 65535 32768 num AI CALIBRATION Gain_5V_AI3 15620 WORD RW Ai3 0 5V calibration gain 0 65535 32768 num AI CALIBRATION Gain_10V_AI3 1...

Page 22: ...0 10V voltage probes value at 0V 10 for 0 5V probes value at 10 corresponding to 0 5V 9999 9999 0 ANALOGUE INPUTS FullScaleMAx_Ai3 15737 WORD 1 RW Analogue input Ai3 full scale value N B Maximum full...

Page 23: ...485 ON BOARD Stopbit_RS485_OB 15777 WORD Y RW On board RS485 stop bit number 1 1 stop bit 2 2 stop bit 1 2 1 num RS485 ON BOARD Parity_RS485_OB 15778 WORD Y RW On board RS485 protocol parity 0 NULL 1...

Page 24: ...TP server generally listens on port 80 using TCP protocol TFTP Trivial File Transfer Protocol Protocol using basic FTP functionalities Typical use transfer of small files between hosts on a network TF...

Page 25: ...FAULT U M ETHERNET ON BOARD Port_TFTP 15772 WORD Y RW TFTP port TFTP communication Port number Default 0 corresponds to port 69 0 65535 0 num ETHERNET ON BOARD Port_HTTP 15796 WORD Y RW HTTP port HTTP...

Page 26: ...m ETHERNET ON BOARD DefGtwy_3_ETH 15804 WORD Y RW Default Gateway part 3 0 255 0 num ETHERNET ON BOARD DefGtwy_4_ETH 15805 WORD Y RW Default Gateway part 4 0 255 1 num ETHERNET ON BOARD NetMsk_1_ETH 1...

Page 27: ...part 3 0 255 2 num ETHERNET ON BOARD PriDNS_4_ETH 15813 WORD Y RW Primary DNS server part 4 0 255 129 num ETHERNET ON BOARD SecDNS_1_ETH 15814 WORD Y RW Secondary DNS server part 1 0 255 194 num ETHER...

Page 28: ...English 2 French 3 German 4 Spanish 0 65535 0 num Display Par_ContrLCD 15723 WORD Y RW LCD Contrast Allows adjustment of the LCD display contrast 0 64 30 Num Display Par_BackLightTime 15724 WORD RW B...

Page 29: ...5 0 num HMI remote 1 HmiList_Addr_3 15847 WORD RW HMI remote 1 navigation resource address for TCP IP part 3 0 255 0 num HMI remote 1 HmiList_Addr_4 15848 WORD RW HMI remote 1 navigation resource addr...

Page 30: ...st_Addr_1 15857 WORD RW HMI remote 4 navigation resource address for CAN RTU and TCP IP part 1 0 255 0 num HMI remote 4 HmiList_Addr_2 15859 WORD RW HMI remote 4 navigation resource address for TCP IP...

Page 31: ...st_Addr_1 15869 WORD RW HMI remote 7 navigation resource address for CAN RTU and TCP IP part 1 0 255 0 num HMI remote 7 HmiList_Addr_2 15870 WORD RW HMI remote 7 navigation resource address for TCP IP...

Page 32: ...address for TCP IP part 4 0 255 0 num HMI remote 9 HmiList_File_9 15957 15 byte RW HMI remote 9 navigation file DOS 8 3 uppercase format string HMI remote 10 HmiList_ID_10 15830 WORD RW HMI remote 10...

Page 33: ......

Page 34: ...doors preventing the opening of holes in walls with recessed wall wiring Make all the necessary connections then insert the EVP terminal without front in the backplate which serves as a panel followi...

Page 35: ...cription Documentation Notes SAR0RA00X701 USB 485 MINI KIT converter USB cable Converters and cables EVA00USCA0000 USB CAN converter Cable Contact Eliwell Sales Department Ethernet cable TF111202 230V...

Page 36: ...tation Notes Pressure transducers 1 Pressure transducer 4 20mA male or female connector Range from 0 5 7bar to 0 50 bar Depending on model Instruction Sheet 9IS64173 EWPA EN IT ES DE FR RU Code Descri...

Page 37: ......

Page 38: ...3 General Technical Data 14 General warnings 6 H Highlighting icons 3 HMI Management 18 19 HMI sel 18 I I O features 14 Improper Use 15 INTRODUCTION 3 K Keys and LEDs 16 L Language 18 M Mechanical dim...

Page 39: ...phone 39 0437 986 111 Facsimile 39 0437 989 066 Sales 39 0437 986 100 Italy 39 0437 986 200 other countries saleseliwell invensys com Technical helpline 39 0437 986 250 E mail eliwell freeway invensys...

Reviews: