C6 Max set point range +85°C. To limit the maximum set point 

C5 Min set point range -50°C  To limit the minimum set point 

A7 Alarm delay range 0-60 minutes. Delay before alarm activates 

C7 Compressor short cycle protection range 0-90 minutes. Stops 
compressor stop starting excessively 

A2 Compressor run time in event of probe failure range 0-60 minutes. 
Compressor will run for this timed period with no input to avoid thawing 
of product 

A3 Compressor stop time in event of probe failure range 0-60 minutes. 
Compressor will cycle off after this period of time with no input to avoid 
freezing product 

D1 Evaporator probe presence 0 = disabled 1 = enabled 

D2 Probe calibration range -10 to 10°C adjustment of probe input reading 
if accuracy is poor due to extended probe or interference 

D7 defrost stop temperature, defrost terminates when this setting is 
reached 

F5 fan stop temperature, fans will not run at or above this setting 

D8 drip time, at end of defrost time is allowed for condensate to drip off 
coil 

D11 defrost mode 0 is electric heater 1 is hot gas  

F1 fan mode  0 fan operates simultaneously with compressor 1 fan 
operates continuously stops during defrost 2 fan operates continuously 
stops during defrost and drip time 3 fan operates continuously stops 
during defrost fan time delay after defrost 4 Controlled by sensor fan stops 
during defrost 

A full list of parameters follows (some are optional and depend on model) 

 

 

 

 

 

 

 