MAINTENANCE

10W Slim Emergency LED Driver

10W Emergency LED Driver

20W Emergency LED Driver

SYSTEM WIRING DIAGRAM 

LED Emergency

Pack

LED Indicator

& Test Switch

Yellow/Black

White

Brown

Yellow

Red
Blue

Constant 

Hot

Neutral

Battery 

Connector

Cap-O

Cap-O

*REFER ANY SERVICING INDICATED BY THESE CHECKS TO 
QUALIFIED PERSONNEL

TCASE TEST POINT LOCATION 

EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE 
SAME BRANCH CIRCUIT TYPICALLY. IT MAY BE USED WITH 
OTHER DRIVERS. CONSULT THE FACTORY FOR OTHER WIRING 
DIAGRAM.

PAGE 3 OF 4

O.R.-Revision C: 2/24/21

323-888-1973

[email protected]

www.iuseelite.com

Although no routine maintenance is required to keep the emergency 
driver functional, it should be checked periodically to ensure that it is 
working. The following schedule is recommended:

1.

2.

Test the emergency operation of the 

xture at 30 day intervals for a

minimum of 30 seconds. The LED load should operate at reduced
illumination.

Visually inspect the charging indicator light monthly. It should be 
illuminated. If the charging indicator is o

. Contact tech support.

3.

Conduct a 90 minute discharge test once a year. The LED load should
operate at reduced illumination for at least 90 minutes.

0-10V

Dimmer

1               10V

Gray

LED Emergency

Pack

AC LED Driver

LED Indicator

& Test Switch

Yellow/Black

White

White

Black

Red

Blue

Brown

Yellow

Red
Blue

Wall

Switch

Constant 

Hot

Neutral

Battery 

Connector

Violet

Cap-O

Overall Wiring Diagram 

Switched Hot

Emergency Only Wiring Diagram 

Reviews: