![Elite EMG-LED-G2-10W Instructions Download Page 3](http://html1.mh-extra.com/html/elite/emg-led-g2-10w/emg-led-g2-10w_instructions_2389566003.webp)
MAINTENANCE
10W Slim Emergency LED Driver
10W Emergency LED Driver
20W Emergency LED Driver
SYSTEM WIRING DIAGRAM
LED Emergency
Pack
LED Indicator
& Test Switch
Yellow/Black
White
Brown
Yellow
Red
Blue
Constant
Hot
Neutral
Battery
Connector
Cap-O
ff
Cap-O
ff
*REFER ANY SERVICING INDICATED BY THESE CHECKS TO
QUALIFIED PERSONNEL
TCASE TEST POINT LOCATION
EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE
SAME BRANCH CIRCUIT TYPICALLY. IT MAY BE USED WITH
OTHER DRIVERS. CONSULT THE FACTORY FOR OTHER WIRING
DIAGRAM.
PAGE 3 OF 4
O.R.-Revision C: 2/24/21
323-888-1973
www.iuseelite.com
Although no routine maintenance is required to keep the emergency
driver functional, it should be checked periodically to ensure that it is
working. The following schedule is recommended:
1.
2.
Test the emergency operation of the
fi
xture at 30 day intervals for a
minimum of 30 seconds. The LED load should operate at reduced
illumination.
Visually inspect the charging indicator light monthly. It should be
illuminated. If the charging indicator is o
ff
. Contact tech support.
3.
Conduct a 90 minute discharge test once a year. The LED load should
operate at reduced illumination for at least 90 minutes.
0-10V
Dimmer
1 10V
Gray
LED Emergency
Pack
AC LED Driver
LED Indicator
& Test Switch
Yellow/Black
White
White
Black
Red
Blue
Brown
Yellow
Red
Blue
Wall
Switch
Constant
Hot
Neutral
Battery
Connector
Violet
Cap-O
ff
Overall Wiring Diagram
Switched Hot
Emergency Only Wiring Diagram