Elite EMG-LED-G2-10W Instructions Download Page 2

1.

2.

Mount the emergency LED driver by the mounting tabs using
appropriate screws (not provided). The luminaire's installation instructions
may provide guidance on the recommended mounting location.

INSTALLING THE EMERGENCY DRIVER 

                    NOTE: 

                    

This product has been designed to reliably interface with a 

                      wide selection of LED loads and is electrically compatible 
                      with every simple LED array that meets criteria 1 and 2 above. 
However compatibility cannot be guaranteed with all current and future 
LED systems . Compatibility testing of the end-use systems is suggested . 
Please contact the factory with any questions

                    NOTE: 

                    

After installation it will be necessary to measure the egress 

                      lighting illumination level to ensure it complies with national 
                      state and local code requirement.

Installation of this emergency LED driver will vary based on 
the luminaire type, however generally follow these steps.

Mounting Height:

 This product meets or exceeds the NFPA minimum light 

requirements with all loads, down to the smallest rated lamp load, at 
heights up to 7.17ft (2.2m). Many factors in

uence emergency illumination 

levels, such as the lamp load selected, luminaire design, and 
environmental factors. Therefore end use veri

cation is necessary. For 

eld installations, when the attached luminaire is mounted at heights 

greater than 7.17ft (2.2m), the level of illumination must be measured in the 
end application to ensure the requirements of NFPA 101 and local codes 
are satis

ed.

Remote Mounting:

 The emergency LED driver may be remote mounted 

from the luminaire. If used in conjunction with an AC driver the allowed 
distance is up to half the distance the AC driver manufacturer recommends 
remote mounting the AC driver from the LED lo ad . If used without an AC
driver, and remote mounting more than 18 feet from the luminaire, please 
consult the factory to determine the necessary wire gauge. 

CAUTION: 

Remote mounting can result in reduced power output.

 

3.

4.

Mount the supplied 4 wire illuminated test switch in a location that is 
visible and accessible by maintenance personnel. The switch mounts 
through a hole which may need to be added to the luminaire or could 
come pre-punched by the luminaire supplier.

Wire the test switch per wiring diagrams provided on this instruction.

5.

If wired correctly, the test switch indicator light should be ON when AC 
power is supplied to the 

xture, and the battery switch is “ON” 

indicating that the emergency battery is charging.

           NOTE: 

           For 10W models, a short term discharge test may be 
           conducted after the emergency driver has been charged for 
           one hour. A 24 hour charging period must be performed 
before conducting a long term discharge test. For 20W models, a 
short term discharge test may be conducted after the emergency 
driver has been charged for one hour. A 48 hour charging period 
must be performed before conducting a long term discharge test. 
Refer to the OPERATION section of specs.

                   CAUTION: 

                   This unit has more than one power connection point. 
                   To reduce the risk of electric shock, disconnect both the 
                   branch circuit breakers or fuses and emergency power 
supplies before servicing.

OPERATION

PAGE 2 OF 4

O.R.-Revision C: 2/24/21

323-888-1973

[email protected]

www.iuseelite.com

Disconnect AC power from the LED luminaire.

6.

Select the appropriate wiring diagram to connect the emergency 
driver to the AC driver and LED load. Make sure all connections are in 
accordance with the National Electrical Code and any local 
regulations. After installation is complete, supply AC power to the 
emergency driver and turn on battery switch/join battery connector. At 
this point, power should be connected to both the AC driver and the 
emergency driver, and the Charging Indicator Light should illuminate 
indicating the battery is charging.

Emergency Part# 

Application 

Notes 

EMG-LED-G2-10W

 

Integrated Moun

ng 

 

EMG-LED-G2-10W-FLEX

 

Remote Mounting 

Remote mount test switch 

EMG-LED-G2-10W-LP

 

Integrated Moun

ng 

 

EMG-LED-G2-10W-FLEX-CP

 

Remote Moun

ng 

Flex for Chicago Plenum 

EMG-LED-G2-10W-INTG-FLEX

 

Remote Moun

ng 

Test Switch is integrated, Power Flex 

EMG-LED-G2-20W-INTG-FLEX

 

Remote Moun

ng 

Test Switch is integrated, Power Flex 

EMG-LED-G2-20W

 

Integrated Mounting 

 

EMG-LED-G2-20W-FLEX

 

Remote Mounting 

 

 

During normal operation AC power is applied, to the driver, and the 
charging indicator light is illuminated, which indicates that the battery 
is being charged. When power fails, the emergency LED driver will
automatically switch to emergency power (internal battery), operating 
the LED load for a minimum of 90 minutes. When AC power is 
restored, the emergency driver returns to the charging mode.

Max

18ft

Contact

Elite

Emergency

Test 

Switch

Fixture