6.5.1 - Slot Adjustments
Analog Input Card Calibration Adjustments
For the calibration of Analog Input cards, firstly, the channel to be calibrated should be
selected from
window. The calibration parameters are explained below. From
a general point of calibration operations, required signals specified below are applied to
the correspoinding channels and
button is pressed. After stable
value was seen, the value is recorded by selecting the same button.
button is
used to cancel active calibration.
Channel
Press to Calibrate
Cancel
The
button allows manual entry of the calibration value via the keyboard.
The
button resets the calibration values to factory settings.
Manual Set
Load Factory Settings
Figure 6.9 Analog Input Card
Calibration Page
6.5.1 - Slot Adjustments
Analog Input Card Calibration Adjustments
50 mV:
TC (SHORT), CJ-NTC (3 k):
20 mA:
10 V:
390 Ohm:
390 Ohm Line:
Set the calibrator as a millivolt source and adjust the calibrator output 50.000 mV.
Apply the calibrator output to the millivolt input of the related channel.
Set the calibrator as a resistance source and adjust the
calibrator output 3000.00 Ohm. Short circuit the TC input terminals of the related
channels. Apply the calibrator output to the input terminals of the related channel.
Set the calibrator as a milliampere source and adjust the calibrator output
20.00 mA. Apply the calibrator output to the milliampere input of the related channel.
Set the calibrator as a voltage source and adjust the calibrator output 10.00 V.
Apply the calibrator output to the volt input of the related channel.
Set the calibrator as a resistance source and adjust the calibrator output
390.00 Ohm. Apply the calibrator output to the RT input of the related channel. 3. RT line
should be short-circuited by the wiring diagram.
Same as 390 Ohm. Just save after making 390 ohm calibration without
changing anything