Installation
- 26 -
8.3.3
Options regarding plugs/wire ends
In case of cable-option plug type “ZP 2.5/1AN/24“ (of Weidmüller company), the connection numbers in the
figures (designated as connector S99) have the functions as documented below.
In case of “open wire ends” follow cable designation (see
10.1) and colours of wires.
Table 1: Pin assignment PIO cable
Pin on S99
Wire colour
on
PIO cable
Signal name
1
white
0 V / GND
2
brown
+ 24 V
3
yellow
CAN-H
4
green
CAN-L
5
-
shield
6
red
+ 12 V Battery
7
blue
0 V Battery
8
black
SQW
9
violet
MAINT
10
gray-pink
UP
11
red-blue
DOWN
12
white-green
SGC-FB
13
brown-green RESET
14
white-yellow
DZ-SUP
15
yellow-brown DZ
Table 2: Pin assignment SCA cable
Pin on S99
Wire colour
on
Signal name
16
white
SGC-IN
17
brown
SGC-OUT
18
green
Reserved. Do
not connect!
19
yellow
Reserved. Do
not connect!
20
gray
DCS-N
21
pink
OC-IN
22
blue
OC-OUT
23
red
DCS-L
24
black
NOC-IN
25
violet
NOC-OUT
More types of plugs may be defined at a later moment. In this case additional information is created due to pin
assignment of the plug.
Plugs used instead of “Weidmüller-plug” must meet the following minimum requirements:
Rated impulse withstand voltage to neighbor clamp: 4 kV
Rated current: 6 A
Storage and operation temperature: −20 °C …+70 °C
Conductor cross section: min. 0.75 mm
2
for SCA cable and min. 0.25 mm
2
for PIO cable