7. Teaching procedure
(only when using an ELGO FMAX absolute linear encoder)
If an ELGO-FMAX encoder is connected, the following steps must be done, to calibrate and
modulate the sensor with Z58:
1. Press for 3 sec., at the same time - in normal operation mode
- Buttons -
►
and
–
▲
The display shows
2. Move the FMAX-sensor app. 2 cm forwards and backwards and press
Button
-
►
then
The display shows
3. Now move the FMAX-sensor to the desired offset and press
Button -
▲
then
The display shows
4. With releasing the
Button -
▲
the system is calibrated and the display shows
8. Information’s about Pulse Scaling Factor
The adjustable range is between 0,0001 and 9,9999 with
mm
-operation as well as
Inch
-operation. With factors bigger than „1“ the resolution decreases.
Calculating the factor:
Demand value (defined value)
Factor =
Displayed value
Example :