english
GAS ALARM
Placing of the sensor for
carbon monoxide (CO) / smoke:
Mount the external sensor as close as possible to the
point of combustion or flue/chimney to be monitored
but some 15-30 cm below the ceiling as the escaping
gas will be heated and will initially rise.
The sensor may not be used in the following positions:
places where the sensor is shielded from escaping gas (e.g. behind curtains or in
•
cupboards)
directly above hearths or points of combustion or over a wash basin or sink
•
next to a door, windows, ventilator, fan, air conditioning unit etc.
•
in areas where dust or dirt can prevent the sensor from working
•
in areas at risk of explosion
•
START-UP
The GAS ALARM GX-C2 is simply plugged into a 230V/50Hz socket. The LED indicator
(Function) will light up
yellow
. The sensor of the monitoring system requires a warm-up time
of 3-5 minutes to become fully operational. The LED indicator (Function) will then light
green
and the GAS ALARM GX-C2 is operational.
NOTE:
various transport conditions (lengthy storage / humidity) can lead to an alarm state
being triggered immediately after the warm-up time (LED flashes
red
). Disconnect the unit
briefly from the supply and start the warm-up process again. You may need to repeat this
procedure up to three times.
It is essential to observe the prescribed sensor mounting height!
INSTALLATION INSTRUCTIONS
The GAS ALARM GX-C2 and the sensor may be installed only in dry, interior rooms and
must be correctly placed according to the type of gas to ensure faultless operation of the
alarm system.