44
X20: Potential-free relay contact
The relay functions are described under menu item "2.7".
Caution - Damage of components!
Maximum current of 1 A at 230 VAC and 0.4 A at 24 VDC
We recommend the use of LED lamps
When using light bulbs, these should have power of maximum 40 W and be
shock-proof
Force monitoring (DES only)
Menu item "3.1":
The force monitoring function can only be used with fully balanced doors and drive units with
DES switches. It should be able to detect when persons are moving with the door.
Warning!
The force monitoring is no substitute for safety measures in providing protection
against the trapping hazard
Function
Force monitoring
"0"
Off
"2" - "10"
2 - low limit value
10 - high limit value
Important!
Force monitoring for doors with spring balance only
Environmental factors such as temperature or wind load can lead to inadvertent
triggering of the force monitoring