9 POSUN KRIVKY
9 AUTO POSUN
10 STREdNI IZOL
11 REG INTERVAL
12 RYCHLOST REA
12
9. SHIFT TO CURVE
1 - 20
=
manual correction according to the coefficient
, we will use it if the
temperature is still not according to your requirements (after 0.5).
When selecting the manual correction, you set the coefficient of the heating curve shift, where at different. At the required temperatu-
res in the reference room, you can regulate the heating water according to current outdoor temperatures (see page 11 for the formula).
(factory setting 5)
Example
describes the choice of equithermal cu-
rve No.13 (pink) and its calculated correction by a
factor of 5 (for the required room temperatures of
24 ° C at 16 ° C). We will achieve optimal settings
system, where the water temperature of the hea-
ting system is regulated according to the current
outdoor temperature.
Displacement calculation according to the formula:
10°C = (24 - 20) * 5/2
-10°C = (16 - 20) * 5/2
Ie. according to the graph, at an outdoor tempera-
ture of -10 ° C the heating water temperature will
be approx. 70 ° C (if required for a room 24 ° C) and
approx. 50 ° C (if required for a room 16 ° C).
During this control, the heating curve is automatically corrected depending on both the outdoor temperature
and the current temperature in the reference room where the thermostat is located. This achieves higher thermal
comfort in the heated space, optimal operation of the heating system and thus higher savings! It must be at the
boiler during this regulation
always connected outdoor sensor
and constant No.9 must be set to „AUTO“!
AUTO
=
automatic correction
, according to the internal temperature measured
in the reference rooms. We can use this option only after the correctly selected equi-
thermal curve!
By turning the button “ “ select the correction and confirm with “ “.
10. BUILDING INSULATION
The rate of change of the room temperature during frequent outdoor temperature fluctuations depends
on construction and insulation of the building. With this constant, the rate of temperature change can be
taken into account according to the type of heated building (only with equithermal control).
wrong
= uninsulated building, reacts quickly to changes in outdoor temperature
medium
= isolated building, responds more slowly to changes in outdoor temperature
correct
= well insulated building, responds most slowly to changes in outdoor temperature
By turning the button “ “ select the correction and confirm with „ “.
(factory set „medium“)
11. REGULATORY INTERVAL EQUITHERMAL REGULATION
It is selected according to the temperature inertia of the object. The optimal setting is usually 10 to 15
minutes.
Selectable range
5 min to 20 mi
n (1 min each).The length of the interval in minutes affects the oscillati-
on of the system. The lower this value, the greater the risk of oscillations.
By turning the button “ “ select the correction and confirm with „ “.
(from production 10 minutes)
12. RESPONSE SPEED
Active only when selecting equithermal control with automatic correction according to the internal
temperature! Determines how fast the desired temperature is reached. Selectable
range 1 to 16
(1
each).At reaction rate 1, the desired temperature is reached slowly, which prevents the possibility
of overshoot, but the desired temperature is reached later. At reaction rate 16, when the desired
temperature changes, it immediately heats up to the desired temperature, but an overshoot occurs.
By turning the button “ “ select the correction and confirm with “ “.
(factory setting 11)