5
ELEKTRA SelfTec 16 heating cables are available
on spools, terminated with a heat shrink cap to
protect the cable against moisture.
After a cable segment has been cut off, the cable
remaining on the spool also needs to be secured
with a heat-shrink cap. The cables need to be
terminated and connected to the power supply
conductor. For this purpose, the EC-PRO and
ECM25-PRO joint sets have to be applied
(installation manuals included in the sets).
Due to their properties, ELEKTRA SelfTec 16 can
touch or cross and they are not prone to local
overheating. A significant advantage is the
possibility to cut the cables into segments of
required length. However, it is recommended not
to exceed the max. permissible heating circuit
length, as shown in Table 1.
®
®
min. switch-on
temperature
max. circuit length [m]
10A
16A
SelfTec 16
®
type C circuit breaker
-20°C
-15°C
0°C
+10°C
+10°C
in water
0°C
in ice
water
Table 1
55
75
60
80
70
90
80
100
55
60
40
55
Summary of Contents for SelfTec 16
Page 2: ......
Page 24: ......
Page 45: ...RU Instrukcja monta u PL Installation manual UK SelfTec 16 ELEKTRA www elektra otoplenie ru...
Page 46: ......
Page 47: ...ELEKTRA SelfTec 16 ELEKTRA SelfTec 16 47 RU...
Page 50: ...50 SelfTec 16 ELEKTRA ELEKTRA SelfTec 16...
Page 52: ...10 1 15 2 52 SelfTec 16 ELEKTRA 5 C 5 C C 1 1 2 1 2 100 125...
Page 53: ...53...
Page 55: ...SelfTec 16 ELEKTRA 30 55...
Page 56: ...56 SelfTec 16 ELEKTRA...
Page 57: ...57 GH 2 30...
Page 58: ...58 SelfTec 16 ELEKTRA GH 2 DSW 2 DSC 2 6 40 6...
Page 59: ...59 1 DSW SB 1 FCS 1 SS 1 2 2...
Page 60: ...ELEKTRA UTR60 PRO 16 1200 60 SelfTec 16 ELEKTRA...
Page 61: ...40 C o 120 C DIN 16 1200 ELEKTRA ETV 1991 61...
Page 62: ...62 SelfTec 16 ELEKTRA ELEKTRA ETR2 DIN 16A 1200...
Page 63: ...19 63 1000 50 M...
Page 64: ...ELEKTRA ELEKTRA SelfTec 3 c 16 1 a b 2 ELEKTRA 3 a b c d e 4 ELEKTRA 62 SelfTec 16 ELEKTRA...
Page 65: ...E mail P o 3...
Page 66: ...M M M C 1000 50 W...