Examples of heating cable fitted on a pipe flange, suspended pipe bearers and ground supports 

installation tape
heating cable

Heating  cables  fitted  on  valves,  flanges  or  supports  cannot  come  into 
contact  with  each  other.    To  prevent  possible  displacement,  the  cable 
should be fitted with extra tape lengths.

NOTE: 

STAGE 3

After the ELEKTRA FreezeTec™ cable is placed on the pipe, it must be fixed 
with self-adhesive aluminium tape along the whole cable length.

www.elektra.eu

Summary of Contents for FreezeTec 12/10

Page 1: ...emperatures The system may be used only when the following conditions are met A Application FreezeTec ELEKTRA external diameter of pipe to be insulated should not exceed DN 50 mm pipe insulation thick...

Page 2: ...arate control system usually used with conventional heating cables The assembly of the system is quick simple and does not need to be controlled Technical specifications thermostat turn on temperature...

Page 3: ...old tail 1 5 m long Table 1 T Types of Cables FreezeTec 12 2 FreezeTec 12 3 FreezeTec 12 5 FreezeTec 12 7 FreezeTec 12 10 FreezeTec 12 15 FreezeTec 12 21 FreezeTec 12 30 FreezeTec 12 42 2 3 5 7 10 15...

Page 4: ...DN mm INCHES INSULATION THICKNESS AMBIENT TEMPERATURE COEFFICIENT 10mm 20mm 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 5 1 8 2 1 1 1 1 1 1 1 1 2 1 3 o 10 C o 15 C o...

Page 5: ...lay the cable along or helically around the pipe depends on the selected length of heating cable Cables are attached by means of a tape Fig 2a Fig 2b Heating cable 300mm Thermostat Installation tape H...

Page 6: ...hat of pipe by 1 m The additional length of 1 m is used for valve heating while the remaining length of cable is laid along the opposite side of pipe The cable may also be wound with small pitch aroun...

Page 7: ...is 2100 cm P L pipe length is 1200 cm R Thus the cable has to be wound around the pipe so that the distance between cable runs is about 11 cm Examples of heating cable fitted along the pipe bend and...

Page 8: ...cables fitted on valves flanges or supports cannot come into contact with each other To prevent possible displacement the cable should be fitted with extra tape lengths NOTE STAGE 3 After the ELEKTRA...