In the a.m. example:
D - outer diameter of pipe is 4.2 cm
d
- dimension of heating cable is 5 x 7 mm
L
- heating cable length is 2100 cm
P
L
- pipe length is 1200 cm
R
Thus, the cable has to be wound around the pipe so that the distance between
cable runs is about 11 cm.
Examples of heating cable fitted along the pipe bend and on the valve.
installation tape
heating cable
The heating cable should surround
the valve from both sides.