6. Calibrate Analog Output and Adjust Displayed Battery Voltage
a. To view the analog output of the battery monitor connect a hand held
current meter's po) lead to TB2-16 and the negative(-) lead to
TB2-17
b. Press and hold the LIMIT button (approx .. 4 sec)=>
LMIT
is now
flashing, short press the LIMIT button until you scroll through to
CAL,
press and hold the LIMIT button=>
/LO
(low current limit) will be
displayed
c. Use the UP/DOWN button to adjust the low current limit, as displayed
on the hand held current meter, to 4.00mA
d. Short-press the LIMIT button=> to go to the next calibration point,
IHI
(high current limit)
e. Use the UP/DOWN button to adjust the high current limit to 20.00mA
f. Next, adjust the battery voltage readout: Connect the voltage input
leads of your handheld digital volt meter to TBl-1 and TBl-2
g. Go to the next calibration point,
VCAL,
short-press the LIMIT button
Use the UP/DOWN button to adjust the voltage readout of the Battery
Monitor to match the handheld digital multimeter
h. To return to monitor mode press and hold the LIMIT button