Electroswitch Arga 25-1000 Quick Start Manual Download Page 4

ELECTROSW/TCH 

6. Calibrate Analog Output and Adjust Displayed Battery Voltage

a. To view the analog output of the battery monitor connect a hand held

current meter's po) lead to TB2-16 and the negative(-) lead to

TB2-17

b. Press and hold the LIMIT button (approx .. 4 sec)=> 

LMIT 

is now

flashing,  short press the LIMIT button until you scroll through to 

CAL,

press and hold the LIMIT button=> 

/LO 

(low current limit) will be

displayed

c. Use the UP/DOWN button to adjust the low current limit, as displayed

on the hand held current meter, to 4.00mA

d. Short-press the LIMIT button=> to go to the next calibration point, 

IHI

(high current limit)

e. Use the UP/DOWN button to adjust the high current limit to 20.00mA

f. Next, adjust the battery voltage readout: Connect the voltage input

leads of your handheld digital volt meter to TBl-1 and TBl-2

g. Go to the next calibration point, 

VCAL, 

short-press the LIMIT button

Use the UP/DOWN button to adjust the voltage readout of the Battery

Monitor to match the handheld digital multimeter

h. To return to monitor mode press and hold the LIMIT button

TEST 

MONITORING EQUIPMENT 

Storage Battery Systems LLC 
N56 W16665 Ridgewood Drive 

Menomonee  Falls, WI 53051 

www.sbsbattery.com 

800-554-2243

[email protected] 

QSABM0818  4 