
38
Installation manual
7.6
Functions for I/O-cards
The electrical schematic can be one of the following:
7.6.1
Central payment (2J)
To start the machine from a central payment system, the payment system must transmit a start pulse 300–3000 ms
(500 ms is recommended) with a minimum pause of 300 ms (500 ms is recommended) between two pulses. The
start pulse can be either 230V or 24V. In order to receive a feedback signal once the machine has started, 230V or
24V must be connected to connection 19. The feedback signal on connection 18 remains active (high) during the en-
tire program.
fig.7440