Before installing the hood

For the most effcient air flow exhaust, use a    

 

straight run or as few elbows as possible.

         Vent unit to outside of building and recirculating.

At least two people are necessary for installation. 

 

The hood is fitted with Screws and Drywall  

 

 

Anchors suitable for most surfaces, consult a    

 

Qualified Installer, check if they perfectly fit with  

 

your cabinet/wall.     

 

 

 

Do not use flex ducting. 

 

 

 

COLD WEATHER installations should have an    

 

additional backdraft damper that is already     

 

installed to minimize backward cold air flow and a 

 

 nonmetallic thermal break to minimize  

 

 

conduction of outside temperatures as part  

 

 

of the  ductwork. The damper should be  

 

 

on the cold air side of the thermal break. 

 

 

The break should be as close as possible  

 

 

to where the ducting enters the heated portion   

 

of the house. 

 

 

 

 

 

Make up air: Local building codes may require the  

 

use of Make-Up Air Systems when using Ducted 

 

Ventilation Systems greater than specified CFM of  

 

air movement. 

 

 

 

 

 

The specified CFM varies from locale to locale.  

 

Consult your HVAC professional for specific    

 

requirements in your area.

1.

2.

3.

4.

5.

6.

Electrical requirements
IMPORTANT

Observe all governing codes and ordinances.

It is the customer’s responsibility:
To contact a quali!ed electrical installer.
To assure that the electrical installation is adequate
and in conformance with National Electrical Code,
ANSI/NFPA 70 — latest edition*, or CSA Standards
C22.1-94, Canadian Electrical Code, Part 1 and
C22.2 No.0-M91 - latest edition** and all local codes
and ordinances.

If codes permit and a separate ground wire is used, it
is recommended that a quali!ed electrician determine
that the ground path is adequate.

Do not ground to a gas pipe.
Check with a quali!ed electrician if you are not sure
range hood is properly grounded.
Do not have a fuse in the neutral or ground circuit.

IMPORTANT

Save Installation Instructions for electrical inspector’s
use.

The range hood must be connected with copper wire
only.

The range hood should be connected directly to the
fused disconnect (Or circuit breaker) box through
metal electrical conduit.

Wire sizes must conform to the requirements of the
National Electrical Code ANSI/NFPA 70 — lat-
est edition*,or CSA Standards C22.1-94, Canadian 
Electrical Code Part 1 and C22.2 No. 0-M91 - latest 
edition**and all local codes and ordinances.

A U.L.- or C.S.A.-listed conduit connector must be
provided at each end of the power supply conduit (at
the range hood and at the junction box).

Copies of the standards listed may be obtained from:

* National Fire Protection Association Batterymarch Park 
Quincy,Massachusetts 02269

** CSA International 8501 East Pleasant Valley Road Cleveland, Ohio 
44131-5575

Important safety Instructions - Electrical & Installation

requirements

READ AND SAVE THESE INSTRUCTIONS

Electrical & Installation requirements

Summary of Contents for ICON RH42PC60GS

Page 1: ...se Care Guide 36 and 42 Island Range Hood Guia de Instalación Uso y Cuidado 36 y 42 Campana extractora Guide d installation utilisation et d entretien 36 et 42 Hotte aspirante RH36PC60GSB RH42PC60GSB 316495104 AUG 12 ...

Page 2: ...u please use this page to record important product information Keep a record for quick reference Purchase date Model number Serial number see picture for location Questions For toll free telephone support in the U S and Canada 1 877 435 3287 For online support and Internet product information visit http www electroluxappliances com Table of contents Features 14 Control buttons 15 Special functions...

Page 3: ...SE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING INSTALLATION MUST COMPLY WITH ALL LOCAL CODES IMPORTANT Save these Instructions for the Local Electrical Inspector s use INSTALLER Please leave these Instructions with this unit for the owner OWNER Please retain these instructions for future reference Safety Warning Turn off power circuit at service panel and lock out panel before wiring this appliance...

Page 4: ... Of Injury Disconnect From Power Supply Before Servicing This unit is equpeed with integral disconnecting switch located inside the blower housing TO REDUCE THE RISK OF A RANGE TOP GREASE FIRE Never leave surface units unattended at high settings Boilovers cause smoking and greasy spillovers that may ignite Heat oils slowly on low or medium settings Always turn hood ON when cooking at high heat or...

Page 5: ... adequate and in conformance with National Electrical Code ANSI NFPA 70 latest edition or CSA Standards C22 1 94 Canadian Electrical Code Part 1 and C22 2 No 0 M91 latest edition and all local codes and ordinances If codes permit and a separate ground wire is used it is recommended that a quali ed electrician determine that the ground path is adequate Do not ground to a gas pipe Check with a quali...

Page 6: ... 2 Horizontal supports Optional accessories Recirculation KIT Tools Materials required Aluminum tape Wire nuts Tape to mount template 8 rounded metal duct length to suit installation Measuring tape Pliers Gloves to protect against sharp edges Knife Safety glasses Electric drill with 5 16 and 3 8 bits Strain relief 1 2 conduit connector Level Phillips Pozidrive 2 screwdriver torx 2 Wire cutter stri...

Page 7: ...rk The damper should be on the cold air side of the thermal break The break should be as close as possible to where the ducting enters the heated portion of the house Make up air Local building codes may require the use of Make Up Air Systems when using Ducted Ventilation Systems greater than specified CFM of air movement The specified CFM varies from locale to locale Consult your HVAC professiona...

Page 8: ...ge or into any enclosed space Keep duct runs as short and straight as possible Duct fittings elbows and transitions reduce air flow eficiency Back to back elbows and S turns give very poor delivery and are not recommended A short straight length of duct at the inlet of the remote blower gives the best delivery Transition to duct from the integral blower or remote duct transition as close to the do...

Page 9: ... x 4 are required to support the weight of the hood Arrange cross framing in the ceiling to suit the existing structure Your ceiling joists will be like one of the following examples NOTE Do not cut the duct opening shown on the template for the recirculating installation IMPOR TANT Framing must be capable of supporting 150lbs Installing the hood 4 12 16 At least 8 Ceiling 24 minimum 9 Ceiling 30 ...

Page 10: ...th 8 assembly screws 2 per corner The upper vertical supports position will determine the hood s total height Refer to the maximum and minimum extensions line drawing to determine which is the most suitable dimension according to your ceiling s height Always take into consideration the minimum installation heights declared in this manual Position the upper vertical supports C at the proper height ...

Page 11: ... as shown in A1 Keep the duct cover in this position To lock the upper duct cover in place slide it upwards making sure that all tabs stay inside the respective slots When sliding the duct cover upwards make sure that the lower part of the duct cover is locked with the metal spring as shown in B A click sound will be heard Note 2 persons are needed for this operation Place lower duct covers using ...

Page 12: ... the closest distance we can have from the cooking surface 35 is the recommended height TO PROTECT YOU AGAINST ELECTRIC SHOCK THE GREEN AND YELLOW WIRE MUST BE CONNECTED TO THE GROUNDING WIRE IN YOUR HOME ELECTRICAL SYSTEM AND IT MUST UNDER NO CIRCUMSTANCES BE CUT OR REMOVED Failure to do so can result in death or electrical shock Remove junction box cover and knockout on the top left side If not ...

Page 13: ...crews provided as shown Use duct tape to seal the deflector and at the exhaust outlet from the hood Connecting the ductwork Install ductwork making connections in the direction of airflow as illustrated Push duct over the exhaust outlet Wrap all duct joints and the flange connections with duct tape for an airtight seal Make the same connection in the wall or ceiling vent exit Air deflect installat...

Page 14: ...14 Features Features Blower and light controls Lamp housings Grease filter Handle Grease filter Canopy Duct covers Bottom Top Louver holes Only for Recirculating version 1 2 3 4 5 6 7 ...

Page 15: ...ght Lamp state previously OFF Press lamp button to turn OFF the light Lamp state previously ON 2 Timer Button The default timer setting is 10 minutes and it can be adjusted between 20 minutes and 1minute After pressing the timer button the control enters to a timer setup mode and user can adjust the timer countdown time with the and buttons within 5 seconds The timer can be initiated immediately p...

Page 16: ... When this icon flashes on display the charcoal filters installed are required to be replaced or reactivated To reset the charcoal filter saturation indication the user must press the button for 5 seconds after this time the icon Charcoal filter is not displayed and the hood has the normal display operation Audible signal activation and deactivation The audible signals can be activated or deactiva...

Page 17: ...s upward through the hood Thus when heat smoke moisture grease and cooking odors are produced they will be carried outside instead of drifting into other rooms Use the low speeds for normal use and the higher speeds for strong odors or fumes Drafts across the range or cooktop will cause the escape of heat smoke moisture grease and cooking odors from the hood Such drafts should be prevented in so f...

Page 18: ...ly Replace Lights Remove the inner lamp lens cover by inserting a slots and gently prying it free NOTE Do not remove the outer trim ring lamp assembly Grasp the bulb and pull it straight out from the lamp socket Follow package directions wear gloves do not touch bulb with your bare fingers Replace inner cover by inserting the three retaining tabs into the three slots and pressing them firmly in pl...

Page 19: ...etal grease filter mounting instructions included with charcoal filters kit NOTE DO NOT rinse or put charcoal filters in an automatic dishwasher NOTE Charcoal filters are not included with the hood They must be ordered from your supplier Order the needed kit specifying your hood model and width size Charcoal filter placement Recirculating accessories Fit the charcoal filter mattress on the upper s...

Page 20: ...ITNESS FOR A PARTICULAR PURPOSE ARE LIMITED TO ONE YEAR OR THE SHORTEST PERIOD ALLOWED BY LAW BUT NOT LESS THAN ONE YEAR ELECTROLUX SHALL NOT BE LIABLE FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES SUCH AS PROPERTY DAMAGE AND INCIDENTAL EXPENSES RESULTING FROM ANY BREACH OF THIS WRITTEN LIMITED WARRANTY OR ANY IMPLIED WARRANTY SOME STATES AND PROVINCES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDEN...

Page 21: ...LI288F ...

Reviews: