background image

13

Fan Motor

Fan Blade

Suction Tube
Connector

Condenser

Compressor

Drier
Filter

PTC-Starter

Run Capacitor

Clip

34

Defrost Drain Pan

Access Cover

C - Electrical Components / Operation

Electrical Grounding

All refrigerators are equipped with a power supply 
cord incorporating a three-prong grounding plug and 
a ground wire which is attached to the refrigerator 
cabinet for protection against shock hazard. Each 
electrical component is either cabinet mounted or 
connected through a ground wire to the cabinet to 
complete the ground. Certain components, such as 
defrost timers, may be double insulated and do not 
require a ground wire.

Ensure the electrical wall receptacle is of the three 
prong type and is properly grounded in accordance 
with the National Electrical Code and/or local codes.

Compressor Electrical 
Components and Circuits

The new series of very high efficiency compressor is 
equipped with all new electrical components  consist-
ing of a solid state PTC relay with a thermally oper-
ated  overload protector, and a run capacitor. See 
Figure C1.

Figure C1

Solid State Relay

The solid state relay has no moving parts. It consists 
of a PTC resistor mounted in a plastic case with 
appropriate terminals. PTC (Positive Temperature 
Coefficient) simply denotes a resistor which increases 
in resistance as its temperature is increased. The self-
heating PTC resistor used in the solid state relay has 
the unique characteristic of changing from low to very 
high resistance very abruptly, thus serving as an on-
off switch. (See Figure C3.)

The solid state relay plugs directly onto the  
compressor start and run terminals. (See Figure 2.) 
Relay terminals 1, 2, and 5 are connected within the 
relay, as are terminals 3 and 6. 

A run capacitor is connected to relay terminals 2 and 
3, so it is connected in parallel with the PTC resistor. 
One side of the 120 VAC power is connected to relay 
terminal 1. The other side of line is connected to the 
overload protector. (See figure C3.)

Figure C2

Figure C3

     

NOTE

There are 2 exploded views (Cabinet and 
System) at the end of this section to assist you in 
troubleshooting.

Summary of Contents for European Wine Tower

Page 1: ...Service Manual European Wine Tower 5995534509 March 2009 ...

Page 2: ...ffthegassupply Turnoffthewatersupply 3 Never interfere with the proper operation of any safety device 4 USE ONLY REPLACEMENT PARTS CATALOGED FOR THIS APPLIANCE SUBSTITUTIONS MAY DEFEAT COMPLIANCE WITH SAFETY STANDARDS SET FOR HOME APPLIANCES 5 GROUNDING The standard color coding for safety ground wires is GREEN or GREEN with YELLOW STRIPES Ground leads are not to be used as current carrying conduc...

Page 3: ...0 Definitions 20 Recovery 20 Recycling 20 Reclaim 20 Safety Warnings 20 Compressor Testing 20 Charging Sealed Systems 20 Soldering 21 Basic Components 21 Refrigerant Cycle 21 Low High Side Leak or Undercharge 21 Testing for Refrigerant Leaks 22 Compressor Replacement 22 To Flush the System 22 To Use Dry Nitrogen to Flush the System 22 To Use Refrigerant to Flush the System 23 Installing a New Comp...

Page 4: ...iance take off the doors and leave shelves in place so that children may not easily climb inside WARNING Never attempt to repair or perform maintenance on the unit until the electricity has been disconnected Altering cutting of power cord removal of power cord removal of power plug or direct wiring can cause serious injury fire and or loss of property and or life and will void the warranty Do not ...

Page 5: ...s be increased by at least inch over the dimensions given for your unit Width Height Depth 23 1 2 inches 75 76 inches 24 7 8 inch Unit Dimensions Side View 29 875 75 88 cm 27 50 69 85 cm 24 875 63 18 cm 75 76 191 193 cm Front View 23 50 59 69 cm 3 25 2 75 Top View 49 124 46 cm 23 50 59 69 cm 3 00 7 62 cm 6 98 cm 8 25 cm NOTE All units require zero clearance when installed flush with a cabinet or w...

Page 6: ...d regulations WARNING The Anti Tip Kit must be installed on this unit before it is used All screws supplied with the Anti Tip Kit are for mounting the bracket directly to wall studs These screws will not work if used with sheetrock dry wall or anything other than wall studs Installation clearances Allow the following clearances for ease of installation proper air circulation and plumbing and elect...

Page 7: ... not touching the floor 3 Turn the front leveling legs clockwise to raise and counterclockwise to lower 3 Ensure the door does not bind and the seal touches the cabinet on all four sides 4 Replace the toe grille by aligning hooks with opening in front panel and snapping it into place A Installation NOTE The front rollers should only be used to help maneuver the wine keeper into it s final location...

Page 8: ...of the end cap of handle end cap The end caps should be drawn tight against the door with no gaps 1 Remove handle from carton and any other protective packaging 2 Position handle end caps over upper and lower pre installed shoulder bolts A that are fastened into door ensuring the holes for the set screws are facing towards the outside edge of the door 3 While holding handle firmly against door fas...

Page 9: ...heck the temperature of the water Press the or indicator to adjust the temperature to the desired setting The temperature display will begin to blink with the first touch Adjust the temperature by touching the key After three 3 seconds of inactivity the display will beep to accept the new temperature The internal temperature can be controlled between 45 F to 65 F 7 C to 18 C A Installation Factors...

Page 10: ...ivates the lights regardless of whether the door is closed Each succes sive keypress will advance the interior lights from Off to Low Intensity to Maximum Intensity then to Off again Interior lighting is automatically disabled after 120 minutes at which point the lights may be manually activated again if desired on off Pressing and holding for three 3 seconds allows the user to turn off the coolin...

Page 11: ...y basis DO NOT CLEAN WITH STEEL WOOL PADS DO NOT USE CLEANERS THAT ARE NOT SPECIFICALLY INTENDED FOR STAINLESS STEEL this includes glass tile and counter cleansers If any surface discolors or rusting appears clean it quickly with Bon Ami or Barkeepers Friend Cleanser and a non abrasive cloth Always clean in the direction of the grain Always finish this process with a high quality all in one stainl...

Page 12: ... humidity Replacing the air filter In general you should change the air filter every six months AF will show in the display to prompt you to replace the filter after six months to ensure optimal filtering of odors To replace your PureAdvantageTM air filter 1 Pull the air filter cartridge straight out 2 Remove the old filter and discard it 3 Unpack the new filter and place it inside the cartridge 4...

Page 13: ... of a solid state PTC relay with a thermally oper ated overload protector and a run capacitor See Figure C1 Figure C1 Solid State Relay The solid state relay has no moving parts It consists of a PTC resistor mounted in a plastic case with appropriate terminals PTC Positive Temperature Coefficient simply denotes a resistor which increases in resistance as its temperature is increased The self heati...

Page 14: ...o relay assembly Note On some models you will have to remove bale wire and cover to gain access to relay and overload protector 6 Use ohmmeter to check resistance between tab terminal and female pin terminal Overload protector should have less than 1 ohm of resistance at normal room temperature 7 If ohm readings are out of range install new Starter Overload Assembly See Figure 2 8 Reverse this pro...

Page 15: ...nd switch off the start winding circuit NOTE The relay will switch off the start winding circuit even though the compressor has not started as when attempting to re start after momentary power interruption With an open relay the compressor will not start since there is little or no current to the start windings The overload protector will open due to high locked rotor run winding current With a sh...

Page 16: ... desired setting The temperature display will begin to blink with the first touch Adjust the temperature by touching the key After 3 seconds of inactivity the display will beep to accept the new temperature Diagnostics Service Mode To enter the service mode press and hold the vacation mode key while pressing the on off key 3 times in 5 seconds Temperature digit display will show 1 Each press of th...

Page 17: ...e trim that holds UI in place LED Lighting Two LED lighting strips are located on each side of the interior of the cabinet Each strip has five separate banks containing a PCB and three LED s Each bank of LED s are in parallel on the strip If one should fail the others will still function The LED strip is available as one component only Evaporator Circulation Motor The Wine Tower uses two 12 vdc ev...

Page 18: ...18 C Electrical Components Operation Electrical Wiring Diagram ...

Page 19: ...19 C Electrical Components Operation Electrical Wiring Diagram ...

Page 20: ...iate product specifications are met This term usually implies the use of processes or procedures available only at a reprocessing or manufacturing facility Safety Warnings Compressor Testing Whenever testing a compressor extreme caution should be used to prevent damaging the terminals A compressor with a damaged terminal or a grounded winding can expel a terminal from its insulated housing when th...

Page 21: ...ion line drier and perimeter hot tube Refrigerant Cycle The refrigerant cycle is a continuous cycle that occurs whenever the compressor is in operation Liquid refrigerant is evaporated in the evaporator by the heat that enters the cabinet through the insulated walls and by the heat from product load and door openings The refrigerant vapor is then drawn from the evaporator through the suction line ...

Page 22: ...w compressor without first checking for possible system contamination To check for contamination obtain oil sample from old compressor If the oil has burned odor but no color change or residue follow instructions in section Installing A New Compressor NOTE It is recommended that system be flushed with dry Nitrogen However if refrigerant is used to flush the system you must look at the serial plate...

Page 23: ...no longer than necessary All replacement compressors are shipped with rubber plugs in the suction discharge and process tubes and contain the correct oil charge and a holding charge of inert gas Compressors have a low side process tube attached to the compressor shell A high side process tube is attached to the filter drier warning Do not operate reciprocating compressor when charging liquid refri...

Page 24: ...sible Leave only enough tubing to pinch off and seal defective compressor Plug or tape any open system tubing to avoid entrance of moisture and air into system Remove inoperable compressor and transfer mounting parts to new compressor 11 Install new compressor in exact same manner as original compressor 12 Reform both suction and discharge lines to align with new compressor If they are too short u...

Page 25: ...25 D Refrigeration System Figure E1 Fan Motor Fan Blade Suction Tube Connector Condenser Compressor Drier Filter PTC Starter Run Capacitor Clip 34 Defrost Drain Pan Access Cover ...

Page 26: ...gerant charge is removed the liquid line filter drier must be replaced and the system thoroughly evacuated before recharging CAUTION DO NOT unbraze the old filter drier from the system This will vaporize and drive moisture from the desiccant back into the system The old filter drier should be cut out of the system CAUTION Use only a 15 gram XH9 liquid line filter drier part number 5303305677 when ...

Page 27: ...illed in Step 7 to 1 2 from back of product 9 Remove stubs of old heat exchanger from evaporator and install new heat exchanger into evaporator 10 Push heat exchanger through hole in cabinet and set evaporator back in place 11 Slide Armor Flex over heat exchanger until cover is against hole at back of cabinet The excess cap tube can be wound around the suction line 12 Seal the hole on the inside a...

Page 28: ...s are specified for use with R 134a refrigerant Research has shown that compounds in standard refrigeration hoses may enter sealed systems and ultimately restrict the cap tube in an R 134a system D Refrigeration System Equipment Needed for Evacuation Recharging Heated charging cylinder Standard 3 port manifold gauge set 4 charging hoses Tee fitting with valve core stem removed Robinair No 40396 Ha...

Page 29: ... system is pressurized to 40 or 50 lbs psig 7 Leak test low side Close compound gauge Run compressor for a few minutes and leak test high side When leak is found recapture D Refrigeration System CAUTION Check the serial plate for the correct refrigerant type It is extremely important to verify the type of refrigerant in the system before starting any sealed system repairs After charging the system...

Page 30: ...low side process tube adaptor and solder the process tube closed 14 Check the process tubes for refrigerant leaks Hot Tube Evaporator Condenser Compressor 2 Stage Vacuum Pump Heated Charging Cylinder Process Tube Adapters Filter Drier Pressure Gauge Compound Gauge Gauge Manifold T Fitting Final Leak Test 1 With the refrigerator turned OFF leak test all low side system components 2 Turn the unit ON...

Page 31: ...components being utilized in the R 12 systems There is a 10 to 15 discharge pressure increase using R 134a with a 5 to 10 decrease in suction pressure when compared to the same product with an R 12 system operating at 90 F 32 C ambient temperature conditions Lower suction pressures result from the lower density of R 134a refrigerant which effects refrigerant flow rate R 134a systems commonly opera...

Page 32: ...ge because the exhaust from the first pumping stage is discharged into the second pumping stage This means the second stage begins pumping at a lower pressure so a lower ultimate vacuum can be achieved See 2 Stage Vacuum Pump Figure E3 VACUUM CHART Vacuum Inches Hg Microns Boiling Point of Water F 28 940 25000 77 9 29 530 10000 52 0 29 832 4600 32 0 29 882 1000 1 0 29 901 500 11 2 29 915 150 32 8 ...

Page 33: ...setting though out the 30 minutes you are running your vacuum pump to pull a vacuum on the system Every 4 to 5 minutes while you are running your vacuum pump and heating the crankcase area shake the compressor By heating the crank case you are heating the oil in the compressor This will drive the moisture out of the oil By shaking the compressor this will allow the moisture to come to the top of t...

Page 34: ...12 R 134a NAME Dichlorodifluoro methane 1 1 1 2 Tetra fluoromethane Formula CCI2 F2 CH2 F CF3 Molecular Weight g mol 120 93 102 3 Ozone Depletion Potential ODP 1 0 Global Warming Potential GWP 3 1 0 3 Boiling Point F 21 6 15 7 Vapor Pressure 77 F 80 psig 82 psig Flammability None None Solubility of Water in Refrigerant wt 77 F 0 009 0 11 Halogen specific detectors use a specialized sensor that all...

Page 35: ... 5 108 3 15 26 1 0 0 2 4 100 37 8 123 6 117 2 10 23 3 1 9 4 5 105 40 6 134 3 126 6 5 20 6 4 1 6 7 110 43 3 145 6 136 4 0 17 8 6 5 9 2 115 46 1 157 6 146 8 5 15 0 9 1 11 8 120 48 9 170 3 157 7 10 12 2 12 0 14 6 125 51 7 183 6 169 1 15 9 4 15 0 17 7 130 54 4 197 6 181 0 20 6 7 18 4 21 0 135 57 2 212 4 193 5 25 3 9 22 1 24 6 140 60 0 227 9 206 6 30 1 1 26 1 28 5 145 62 8 244 3 220 3 35 1 7 30 4 32 6 ...

Page 36: ...rdiac arrest If the person is having difficulty breathing administer oxygen If breathing has stopped give artificial respiration Spills or Leaks If a large release of vapor occurs such as from a large spill or leak the vapors may concentrate near the floor or low spots and displace the oxygen available for breathing causing suffocation Evacuate everyone until the area has been ventilated Use blowe...

Page 37: ...n either tanks or HFC 134a supply system usually prevent this Tank pressures should be monitored routinely Air lines should never be connected to storage tanks Filling and Charging Operations Before evacuating cylinders or refrigeration equipment any remaining refrigerant should be removed by recovery system Vacuum pump discharge lines should be free of restrictions that could increase discharge p...

Page 38: ...SYSTEM DIAGRAM Exploded View Diagrams Publication No 5995532214 EI24WC75HS0 SYSTEM 62 61 85 59 1 58 45 44 41 59B 29 4 24 30 55 32 60 6 22 52 34 67 24 23 23 25 25 25 24 26 W05CAAAAA1 45 65 45 45 45 45 45 89 ...

Page 39: ...00 Clip controller 34 7240405201 Grommet rubber black cond tube wire 41 7240433204 Screw hex washer head 8 18 x 5 16 44 75304456288 Clamp wiring harness strain relief galv steel 45 7241906101 Screw 10 x 3 4 TEK 52 7242016801 Bracket anti tip 55 7218909913 Capacitor run 220 VAC 15 microfarad 58 7218897002 Screw hex washer head 8 32 x 0 375 59 7241999101 Shroud cond fan 59 7240346701 Tape foam seal ...

Page 40: ...40 CABINET DIAGRAM Exploded View Diagrams Publication No 5995532214 EI24WC75HS0 CABINET 22 17 84 15 10 11 20 97 50 23 26 25 89A 96 1 2 13 38 42 92 W05BAAAAA0 28 28 43 3 35 35 94 19 72 30 42 21C 98 98 99 ...

Page 41: ...control 26 7242004001 Housing control 28 7240335502 Bolt roller adj hex washer head 1 4 20 x 4 020 2 special 30 7242004401 Bracket lower hinge 35 7242016501 Bracket roller 38 7242004601 Hinge upper 42 7242004501 Screw hinge 43 7240335005 Roller Assy adjustable front 2 50 7241511117 Board main power 50 7241524802 Seal housing 50 75304455650 Screw hex washer head 8 15A x 0 625 low profile 50 7241532...

Page 42: ...42 DOOR DIAGRAM Exploded View Diagrams Publication No 5995532214 EI24WC75HS0 DOOR W05DAAAAA0 10 21 22 21C 13 11 29 29 22 21 1 18 80 12 27 80 79 79 ...

Page 43: ... w frame 12 7241873307 Nameplate Electrolux 13 7242001201 Door Stop wine tower 18 7241881304 Handle refr door stainless 18 7241601002 Wrench allen 21 7242001501 Screw end cap 21C 7242001301 Screw door stop 22 7242001701 Bushing hinge 27 7242001101 Cover door wine tower 29 7242001401 End Cap door top bottom 79 7218755401 Screw set 10 32 x 0 375 80 7218755504 Screw shoulder 10 AB handle mounting ...

Page 44: ...44 SHELVES DIAGRAM Publication No 5995532214 EI24WC75HS0 SHELVES W05SAAAAA0 94 95 208 24 4 49 24A 47 55 Exploded View Diagrams ...

Page 45: ...501 Slide shelf 24 7242002601 Shelf Wine Rack 24A 7242005901 RACK DISPLAY 47 7242002301 Channel shelf mtg side 49 7242002401 Screw channel mtg 55 7242038901 Support display rack 94 7242016601 Housing air filter 95 7241754001 Filter air 208 7241754302 Sleeve air filter silver front 75304468028 Customer Instruct DVD ...

Page 46: ...90 to 120 psig 621 to 827 kPa 130 to 175 psig 896 to 1207 kPa Wattage last 1 3 cycle 85 to 125 85 to 125 Amps running 75 to 1 2 75 to 1 2 Base Voltage 115 vac 127 vac max CONDENSER FAN MOTOR Watts RPM Amps 2 3 1100 CW Opposite Shaft 0 15 Running WINE COOLER EVAPORATOR FAN MOTOR Quantity 2 2 76 each 1800 23 each Width Height Depth 23 1 2 inch 75 76 inches 24 7 8 inch NOTE Your Electrolux wine keepe...

Page 47: ......

Page 48: ......

Reviews: