02/22/2012 11
HI114
Heat pump with fossil fuel boiler
• Mode Dial: C
• SW Over Dial: 0
• SOT Dial: 0=30min 1=90min 2=180min 3=270min
Undersized heat pump with electric boiler
• Mode Dial: C
• SW Over Dial: 1=-15°F/ 2=-10°F/ 3=0°F/ 4=5°F/ 5=10°F/ 6=20°F/ 7=30°F
• SOT Dial 0=30min 1=90min 2=180min 3=270min
Heat pump with emergency electric boiler
• Mode Dial: C
• SW Over Dial: 0
• SOT Dial: 0=30min/ 1=90min/ 2=180min/ 3=270min
Undersized heat pump with fossil fuel boiler
• Mode Dial: C
• SW Over Dial: 1=-15°F/ 2=-10°F/ 3=0°F/ 4=5°F/ 5=10°F/ 6=20°F/ 7=30°F
• SOT Dial: 0=30min 1=90min 2=180min 3=270min
Undersized heat pump with fossil fuel furnace
• Mode Dial: B
• SW Over Dial: 1=-15°F/ 2=-10°F/ 3=0°F/ 4=5°F/ 5=10°F/ 6=20°F/ 7=30°F
• SOT Dial: 0=30min 1=90min 2=180min 3=270min
Electro Industries’ NorAire
®
Heat Pump Boiler
• Mode Dial: D
• All other dials disabled