OPERATIONAL TIPS 

 

1.

 

Indicator lights – there is a set of four indicator lights on the front cover.  Figure 1 is a reproduction of the 
front decal giving definition and information for using these indicator lights. 

2.

 

Boiler power

 LED indicates 24-volt is present on the control board and is continuous on.  Off could mean 

no 240 power, open manual reset (vessel top), open fuse, or bad transformer.  It also indicates supply sensor 
condition (solid = good, pulse = faulty). 

3.

 

240-volt element power current flow can only be measured when the external operating thermostat is calling 
for heat.  There is a 30-second delay before stage 1 turns on, this allows the pump to circulate and sample 
temperature.  Stage 2 will depend upon the temperature differential at the sensor in the supply pipe, see page 
9 sequence (assumes off-peak mode). 

4.

 

The operating thermostat heat call can be verified by the 

red 

LED marked “Mini-Boiler Heat ON” located 

on front cover. 

5.

 

Utility off-peak

 LED is on when the boiler is not being load controlled (blue wires closed). 

6.

 

The 

hi-limit auto reset

 LED is on when the vessel top hi-limit switch is open. 

7.

 

Via a small pin jumper arrangement on the control board, the circulator pump can 
be a direct function of the “W” input 

or

 interrupted by the load control device (even 

though there is a W input).  This diagram illustrates this pin jumper arrangement.  
This unit is factory setup in the “W” position meaning the pump will always run as 
a direct function of “R” to “W” operating thermostat.  By simply moving this black 
2-position jumper to the “L” the pump will be turned off during load control 
interrupt. 

8.

 

At outlet temperatures of approximately 160

 F (53° C), the maximum operating system pressure should be 

approximately 18 PSI (124 kPa).  If the PSI (or kPa) increase from cold water to operating hot water is more 
than approximately 3 to 4 PSI increase (20.6 to 27.5 kPa), the expansion tank is too small, or there is air in 
the system. 

9.

 

At the top of the vessel is a manual reset, 205° F (96° C), primary hi-limit.  This is behind the upper control 
board cover, at the top of the vessel.  At the end of the two red/blk wires there is a small red stem between 
the wire tabs.  This is the reset button. 

10.

 

Check for water leaks and repair as required. 

11.

 

If flow seems to be a concern, determine both inlet and outlet water temperature and apply GPM (L/min) 
formula detailed in previous section “Information/Water Flow Calculations”. 

 

AQUASTAT OPERATION 

 

Determine the design or anticipated outlet temperature.  If this is a radiant floor system this typically could be 
as low as 110°.  If it is staple-up or water coil, satisfactory operation may be at 140° to 160°.  If this is 
baseboard or radiators, start with 170° and during very cold weather this may need to be 180°. 
 
The front temperature set point is selected by a small screwdriver dial switch.  Use the following chart: 

 

Switch Position 

Set Point 

0 90 
1 102 
2 114 
3 126 
4 138 
5 144 
6 160 
7 180 

 

Summary of Contents for EMB-H-5

Page 1: ...s outdoor reset you should consider using model EB MO series Primary application is any hydronic water heating system high or low temperature systems where reduced flow or radiation can cause overheat conditions example zones However if it is a mixture of large and small zones the sudden capacity and flow changes may cause some internal timing over temp conditions This series is equipped for load ...

Page 2: ...ntrol 2 Zone Controller 2 Safety Temperature Control 2 Room Thermostat Placement 2 Water Flow Calculation 2 Installation Requirements 3 Electric Supply 3 Clearances 3 Mechanical Installation 4 Electrical Hookup 5 Water Fill Procedure 6 Operational Tips 8 Troubleshooting Helps 9 Drawings BX305 BH310 UAW411 BL001 XX017 ...

Page 3: ... consider installing zone controller EB 5415A see page 2 for details MULTIPLE ZONES AND RADIANT TEMPERATURES Same water temperature all zones in this case the system can be setup as one pump with the water circulated through the boiler and directly to a manifold containing the various zone valves Although this model series has a built in outlet sensing and controller mechanism for staging the elem...

Page 4: ...r tubing is under the concrete or within the sand base The controlling thermostat must have a remote bulb and this remote bulb must sense the concrete slab temperature slab stat Coordinated with the concrete pour install a PVC minimum bend radius of 7 inches and locate at approximately center vertical of the concrete slab The thermostat sensing bulb can later be pushed down this PVC conduit If the...

Page 5: ... Electro Boiler to the hydronics system The owner installer assumes all responsibility and or liability associated with any needed installation of the gas oil boiler pump plumbing system design hydronics systems or backup gas oil boiler etc Any instructions or comments made within this manual or factory phone assistance relating to the gas oil furnace are provided as comments of assistance and hel...

Page 6: ...d loop hydronic heating system an expansion tank is required Temperature Pressure Gauge Recommended to observe the operation of the system Actually a temperature gauge at the inlet and outlet is desirable Pressure Safety Valve This is required at the hot outlet and is furnished as a loose component with the boiler unit itself Failure to install the provided 30 PSI pressure relief valve as shown wi...

Page 7: ...TE This model series is designed and equipped for 240 volt residential single phase If this unit is used on 208 volt energy capacity is reduced by approximately 25 and there is a possibility of intermittent relay operation The installed transformer has a primary tap for 208 4 Circulating Pump the orange pigtail wires at the control board cube relay represent a switch closure see drawing 10 amp max...

Page 8: ...ify there is proper spacing between all power and electrical wire terminals and verify top high limit manual reset is in During shipping freight vibration there are times when the boiler vessel top manual reset high limit is popped out WATER ADDITIVES 1 Unless the source water is unusually poor and or rust elements additives are not required It is recommended the water source as shown on drawing B...

Page 9: ...nst the metal pipe and listen for air bubbles If the water flow is consistent and quiet the system is probably purged and water filled 9 Close the drain valve Open the inlet gate valve 10 The cold system pressure at the gauge should be approximately 1Ø to 14 PSI 11 Close water supply valve and disconnect water supply 12 Optional The circulating pump can be energized during this fill operation by h...

Page 10: ...angement This unit is factory setup in the W position meaning the pump will always run as a direct function of R to W operating thermostat By simply moving this black 2 position jumper to the L the pump will be turned off during load control interrupt 8 At outlet temperatures of approximately 160 F 53 C the maximum operating system pressure should be approximately 18 PSI 124 kPa If the PSI or kPa ...

Page 11: ...0 it should self reset and restart Manual reset limits surfaced mounted to the top of the vessel opens at 205 F This opens all 24V control power thus opening all element power relays The observed action is the same as a blown fuse no front panel boiler power LED To reset this device simply press the red button located on the limit switch Comment The hi limit auto reset LED and utility off peak LED...

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ......

Page 18: ...tem for Brand X boilers or dual EB R L E Series EB ZC 4 wiring and convenience interface isolated boiler end switch EB 5415A low cost 2 or 3 zones sheds one boiler stage Mini Boiler enhancement ZONE CONTROLLER SLAB STAT Sensing and controlling the system based upon radiant floor surface temperature or the concrete mass has very positive benefits Radiant floor air stat in the same area as a forced air...

Page 19: ...es boilers come standard equipped with outlet temperature pressure gauge pressure relief safety valve and when applicable the WarmFloTM electronic control sensors These kits provide the additional components for easy installation 5585 Mini Boiler 10 kW TS Series 5586 TS Series Standard 5578 3 4 Pipe 5582 1 Pipe 5579 1 1 4 Pipe 120V 1 25 HP maintenance free wet rotor circulator Pump curve example 5...

Page 20: ...ade by Electro Industries or its authorized representative Electro Industries will cover reasonable labor costs to repair defective product or product parts for ninety 90 days after installation TWENTY YEAR 20 LIMITED WARRANTY ON BOILER ELEMENTS AND VESSELS Electro Industries Inc warrants that the boiler elements and vessels of its products are free from defects in materials and workmanship throug...

Page 21: ...ill be null and void 4 The purchaser shall have maintained the product in accordance with the manual that accompanies the unit Annually a qualified and licensed contractor must inspect the product to assure it is in proper working condition 5 All related heating components must be maintained in good operating condition 6 All lines must be checked to confirm that all condensation drains properly fr...

Reviews: