6.2.1: Connect Multiple Displays
Q
One cable (housing two-wire RS-485 and two-wire power wires plus shield) is used to connect the
displays. One port of the Nexus meter supports 12 VA. Each P40N, P41N or P43N requires 3.3 VA
(maximum 3.8 VA). The Master Display (P40N) is the master in communication. The Amp, Power
and Nexus devices are slaves in communication. Therefore, the Master Display (P40N) should be at
the end of the daisy-chained units as shown in Figure 6.2 below. The Nexus port is set at 1.
Protocol is Modbus RTU and Baud Rate is 9600.
NOTE:
The power lines in Figure 6.2
are shown separate for clarity.
All lines are actually in one cable.
Q
Shown here are diagrams of the
P41N and P43N Displays with
example readings on each screen.
6.2.2: Nexus P40N Modes
Q
The Nexus P40N LED External Display has three modes:
•
Dynamic Readings Mode
(section 6.3 and 6.4)
•
Nexus Information Mode
(section 6.5 and 6.6)
•
Display Features Mode
(section 6.7 and 6.8)
Q
Each Mode is divided into Groups. Most Groups are further broken down into Readings.
•
Use the
MODE
button to scroll between Modes.
•
Use the
UP/DOWN
arrows to scroll from Group to Group within each Mode.
•
Use the
LEFT/RIGHT
arrows to scroll from Reading to Reading within each Group.
Q
Use the Communicator EXT software to Flash Update the P40N External Display.
Electro Industries/GaugeTech
Doc #: E107706 V1.2
5
6-2
P40N
P41N
P43N
+V -V S B(-) A(+)
+V -V S B(-) A(+)
+V -V S B(-) A(+)
+V -V S B(-) A(+)
NEXUS UNIT
Figure 6.2: P40N Display Daisy Chain
Figure 6.3: P41N Display
Figure 6.4: P43N Display
Summary of Contents for 1252
Page 2: ...Electro Industries GaugeTech Doc E107706 V1 25 ...
Page 6: ...Electro Industries GaugeTech Doc E107706 V1 25 iv ...
Page 24: ...Electro Industries GaugeTech Doc E107706 V1 25 1 14 ...
Page 46: ...Electro Industries GaugeTech Doc E107706 V1 25 3 8 ...
Page 58: ...Electro Industries GaugeTech Doc E107706 V1 25 4 12 ...
Page 84: ...Electro Industries GaugeTech Doc E107706 V1 25 5 26 ...
Page 134: ...Electro Industries GaugeTech Doc E107706 V1 25 11 4 ...
Page 144: ...Electro Industries GaugeTech Doc E107706 V1 25 A 2 ...
Page 145: ...Electro Industries GaugeTech Doc E107706 V1 25 A 3 ...
Page 146: ...Electro Industries GaugeTech Doc E107706 V1 25 A 4 ...
Page 147: ...Electro Industries GaugeTech Doc E107706 V1 25 A 5 ...
Page 148: ...Electro Industries GaugeTech Doc E107706 V1 25 A 6 ...