9.8: Digital Solid State Pulse Output (KYZ) Module
Digital Solid State Pulse Output (KYZ) Module Specifications
Model Number
Communication
Power Requirement
Operating Temperature
Memory
Factory Settings
Default Settings
(Reset Button)
4PO1
RS-485, Modbus RTU
Programmable Baud Rates: 4800, 9600, 19200, 57600
(-20 to 79)°C / (-4 to +158)°F
15–20Vdc at 50–200 mA;
Nexus 1250/1252 Unit
supports up to 4 Modules
256 byte I
2
C EEPROM
for storage of Programmable Settings and Nonvolatile Memory
Modbus Address: 160
Baud Rate: 57600
Modbus Address: 247
Baud Rate: 57600
9.8.1: Overview
Q
The KYZ Pulse Output Modules have 4 KYZ Pulse Outputs and accept Read and Write Commands
with at least 4 registers of data per command. Digital Solid State Pulse Output (KYZ) Modules are
user programmed to reflect VAR-hours, WATT-hours, or VA-hours. See the
Modbus Communicating
I/O Modules User Manual
for details on programming the module.
Q
Nexus 1250/1252 Unit supplies power for up to 4 connected KYZ Pulse Output modules. See
section 9.2 for power and communication details. Refer to sections 5.12 - 5.13 to determine if you
must use an additonal power source, such as the EIG PSIO.
Q
The Modbus Map for the KYZ Pulse Output Module (and operating details) can be found in the
Modbus Communicating I/O Modules Manual.
Q
NC = Normally Closed; NO = Normally Open; C = Common.
Transmit Delay Time: 0
Voltage Rating
Up to 300Vdc
Commands Accepted
Read and Write with at least 4 registers of data per command
Transmit Delay Time: 20 csec
Summary of Contents for 1252
Page 2: ...Electro Industries GaugeTech Doc E107706 V1 25 ...
Page 6: ...Electro Industries GaugeTech Doc E107706 V1 25 iv ...
Page 24: ...Electro Industries GaugeTech Doc E107706 V1 25 1 14 ...
Page 46: ...Electro Industries GaugeTech Doc E107706 V1 25 3 8 ...
Page 58: ...Electro Industries GaugeTech Doc E107706 V1 25 4 12 ...
Page 84: ...Electro Industries GaugeTech Doc E107706 V1 25 5 26 ...
Page 134: ...Electro Industries GaugeTech Doc E107706 V1 25 11 4 ...
Page 144: ...Electro Industries GaugeTech Doc E107706 V1 25 A 2 ...
Page 145: ...Electro Industries GaugeTech Doc E107706 V1 25 A 3 ...
Page 146: ...Electro Industries GaugeTech Doc E107706 V1 25 A 4 ...
Page 147: ...Electro Industries GaugeTech Doc E107706 V1 25 A 5 ...
Page 148: ...Electro Industries GaugeTech Doc E107706 V1 25 A 6 ...