background image

4

PREINSTALLATION

tions. Turn cells upside down (with the same end facing
the cabinet opening). This will locate the ionizing wires at
the right, and both contact buttons and cell handles will be
facing the power door. Air flow direction must agree with
arrow embossed on end of collecting cells.

After installing the cell sections, install pre-filters in cabi-
net tracks on the right. This will again place the pre-filters
on the air entering side (on the same side as ionizing
wires).

LOCATING THE AIR FILTER

Your air filter must be mounted in the return air duct of a
central forced-air system, on the air entering side of your
furnace. (See Figure 3 for example.)

Select a location that meets the following:

1.

The face of the cell will be at a right angle to the air
stream.

2.

Allow the following clearances to permit removal of
cells and pre-filters: (See Figures 4 and 5)

Model 10C26S-010 - 14 inches
Model 14C26S-010 - 15 inches
Model 16C28S-010 - 14 inches
Model 20C26S-010 - 15 inches

For complete dimension data refer to Figure 5.

3.

The air filter is not to be placed in the discharge of
either the heating or cooling unit.

4.

IMPORTANT:  If atomizing spray type humidifier is
used, it must be installed downstream from the air
filter.

If your furnace duct system has a pre-installed boot,
discard front cover of boot and slide the air cleaner
component inside the boot. (Applies to 14C26S-010 and
20C26S-010.)

If furnace opening cannot be enlarged to required size, a
transition sheet metal section must be used. Transition
must be planned for each job. Reduction should not be
more than 4 inches per linear foot, approximately 20
angular degrees (Figure 3).

DIRECTION OF AIR FLOW THROUGH THE

AIR CLEANER

Your air cleaner is shipped from the factory with air flow
from left-to-right. If this air flow is suitable for the installa-
tion, no further changes need to be made (Figure 4). For
right-to-left air flow, remove both pre-filter and cell sec-

Air Flow

Furnace
Opening

Not to Exceed 20

°

Air Flow

Electronic
Air Cleaner
Opening

Electronic
Air Cleaner

Furnace

Transition Section

(if Needed)

Figure 3

Cabinet

(Interchangeable)

Collecting Cell

(Interchangeable)

Collecting Cell

Outlet Box

Power Pack

Handle

Contact

Button

Contact

Button

Pre-Filters

(Interchangeable)

See text for Cell

Removal Clearance

Figure 4

6 7/8"

A

B

E

D

F

C

Knockouts for

3/4" Conduit

(three sides)

10C26S-010

24 3/4

21 5/16 18 5/8 13 9/16 16 7/16 19 1/16

14C26S-010 29 11/16 26 1/4

23 5/8 13 9/16 16 7/16 19 1/16

16C28S-010

25 1/2

21 5/16 18 5/8

17 3/4

20 5/8

23 3/8

20C26S-010 29 11/16 26 1/4

23 5/8

17 3/4

20 5/8

23 3/8

MODEL NO.

A

B

C

D

E

F

Figure 5

Summary of Contents for 10C26S-010

Page 1: ...Basic SST Service Guide Technical Repair Guide Repair Parts Electronic Air Cleaner Printed In U S A UL Listed CSA Certified by White Rodgers Please read and familiarize yourself with the contents of...

Page 2: ...unit must comply with local electric codes or other applicable codes Review and understand local codes prior to in stallation Failure to do so could result in serious personal injury or death CAUTION...

Page 3: ...and maintain Its basic components and their functions are as follows See Figure 2 Cabinet mounts to existing duct work and houses the collecting cells and pre filters Collecting Cells are made in two...

Page 4: ...ream from the air filter If your furnace duct system has a pre installed boot discard front cover of boot and slide the air cleaner component inside the boot Applies to 14C26S 010 and 20C26S 010 If fu...

Page 5: ...t offset to match air filter opening If duct connection to furnace allows less than nine inches for mounting the air cleaner shorten the lateral trunk or attach an offset fitting to the elbow HORIZONT...

Page 6: ...attached directly Figure 13 or a starting collar can first be fitted to the furnace inlet A butt or slip joint can be used Securely attach the cabinet to furnace inlet using at least two of the mount...

Page 7: ...or connections See Fig 17 Insure all wires are clamped wire connectors prop erly installed and grommets used to prevent wire abrasion 10 With the cabinet Installed reinstall pre filter s and collectin...

Page 8: ...angle to expedite the drip dry pro cess 7 Reinstall the cell s and pre filter s in the cabinet 8 Replace the power pack Turn furnace fan on After 30 minutes push ON OFF switch on the power pack to the...

Page 9: ...ely anchored at each end Support Ionizing Wire Figure 21 Rated Capacity 600 1200 cfm 1000 1600 cfm 1000 2000 cfm 1600 2200 cfm Max Pressure Drop 08 in W G 08 in W G 12 in W G 09 in W G Cell Weight 2 7...

Page 10: ...ng Light ON the small sensor element B Ensure small sensor element is centered in bushing 2 Air sensor left in bypassed condition after servicing 3 Faulty air flow sensor panel Excessive arcing during...

Page 11: ...injury or death This guide contains service checks to assist service personnel in locating and correcting any malfunction that might occur to render the air cleaner ineffective or inop erative The air...

Page 12: ...sion cord apply 120 VAC to power pack Turn power switch to ON position 5 Connect meter negative lead to metal frame of collecting cell Use high voltage probe to measure voltage at collecting cell ioni...

Page 13: ...ially at high altitudes or low air flow rates This power supply has a hairpin shaped jumper wire labeled W1 see Fig 24 that can be cut and separated in case of such complaints This will cause the powe...

Page 14: ...14 1 2 3 4 5 5 6 2 3 7 8 9 18 5 14 13 10 11 12 REPAIR PARTS...

Page 15: ...F876 0202 F876 0202 F876 0202 F876 0202 12 Power Pack Cabinet Only N A N A N A N A 13 Connector Male F827 0026 F827 0026 F827 0026 F827 0026 14 Power Supply F858 1000 F858 1000 F858 1000 F858 1000 15...

Page 16: ...a White Rodgers Electronic Air Cleaner or product containing a White Rodgers Electronic Air Cleaner Although White Rodgers does not extend a warranty directly to consumers White Rodgers does extend a...

Reviews: