![Electra LEX 25 DCI Service Manual Download Page 12](http://html1.mh-extra.com/html/electra/lex-25-dci/lex-25-dci_service-manual_2378858012.webp)
3-1
RATING CONDITIONS
Revision Y06-01
Service Manual - WNG/LEX DCI
3. RATING
CONDITIONS
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
Cooling:
Indoor: 27
o
C DB 19
o
C WB
Outdoor: 35
o
C DB
Heating:
Indoor: 20
o
C DB
Outdoor: 7
o
C DB 6
o
C WB
3.1 Operating
Limits
3.1.1 R410A
Indoor
Outdoor
Cooling
Upper limit
32
o
C DB 23
o
C WB
46
o
C DB
Lower limit
21
o
C DB 15
o
C WB
-10
o
C DB
Heating
Upper limit
27
o
C DB
24
o
C DB 18
o
C WB
Lower limit
10
o
C DB
-15
o
C DB -16
o
C WB
Voltage
198 – 264 V