background image

11

Expel the air with a vacuum pump

(Refer to Chart 27)
(please refer to its manual for the way of using manifold value)

1. Loosen and remove the maintenance nuts of stop values A and B, and connect the charge hose of

the manifold value with the maintenance terminator of stop value A. (Be sure that stop values A and B
are both closed )

2. Connect the joint of the charge hose with the vacuum pump .

3. Open the Lo-lever of the manifold value completely.

4. Turn on the vacuum pump. At the beginning of pumping, loosen the maintenance terminator nut of

stop value B a little to check whether the air comes in (the sound of the pump changes, and the
indicator of compound meter turns below zero). Then fasten the nut.

5. when the pumping has finished ,close the Lo-lever of the manifold value completely and turn off the

vacuum pump.

When you have pumped for over 15 minutes ,please confirm that the indicator of multi-meter is on
-10X10

-5

 Pa (-76mHg).

6. Loosen and remove the quadrangle cover of stop values A and B to open stop value A and B

completely, then fasten them.

SZ000288/En

06/22/2004, 5:07 PM

23

Summary of Contents for KN 30

Page 1: ...e this manual in case of further reference Nous vous prions de lire attentivement le pr sent manuel avant d utiliser cette unit d air climatis et de le conserver pour pouvoir le consulter en cas de be...

Page 2: ...TEMPORARY OPERATIONS 5 ADJUSTING AIR FLOW DIRECTION 5 HINTS FOR ECONOMICAL OPERATION 6 MAINTAINANCE 6 PHENOMENA NOT CONCERNING MALFUNCTIONS 8 TROUBLES AND CAUSES Concerning the unit 9 TROUBLES AND CA...

Page 3: ...stances or any heaters Powerful radio transmitters or any other devices radiating high frequency radio waves can cause malfunction of the air conditioner Please consult the dealer where you purchased...

Page 4: ...d NOTICE In no circumstance should the ground wire or the main power switch be cut off Don t use ruined wiring if you have found any please replace it immediately Please pre heat the air conditioner f...

Page 5: ...outlook and functions from yours NAMES AND FUNCTIONS a Indoor unit b Outdoor unit c Remote controller d Air in e Air out f Air outlet g Air flow louver at air outlet h Connecting pipe i Drain hose j...

Page 6: ...s Don t put hands or objects into the air outlet and inlet These units contain a fan running at a high speed Contacting with the moving fan will cause serious injury Don t remove the fan hood from the...

Page 7: ...ory COOL The air conditioner will run under COOL mode 3 OFF The OPERATION lamp o goes off and the air conditioner will be STAND BY ADJUSTING AIR FLOW DIRECTION While the unit is in operation you can a...

Page 8: ...ter will reduce cooling or heating efficiency please clean it once two weeks MAINTENANCE CAUTION Maintenance work can only be performed by specialized maintenance personnel The main power switch must...

Page 9: ...ck or fire do not let water fall into the indoor unit Never wipe the air flow louver violently An air conditioner without air filter cannot expel the dust out of the room which would cause malfunction...

Page 10: ...water will be sent out in the form of steam 3 Noise A kind of continuous low sound of hiss could be heard while the air conditioner is on operation This is caused by Freon flowing between the indoor a...

Page 11: ...nts 1 Inoperative The power supply is broken Wait for a while The power switch is set off Set it on The power fuse is blown or the circuit breaker has been tripped Replace it The batteries in the remo...

Page 12: ...elapsed The TIMER ON indicators go off after a lapse of certain time Check whether the timer operation is started when the TIMER ON is indicated on the display When the time set to start the air condi...

Page 13: ...installation Des changements peuvent tre effectu s dans ce manuel sans pr avis afin d am liorer la qualit de l appareil Para una correcta instalaci n lea este manual antes de iniciar la instalaci n E...

Page 14: ...ATION 2 3 ATTACHED FITTINGS 3 4 INSTALLATION PLACE 4 5 INDOOR UNIT INSTALLATION 5 6 OUTDOOR UNIT INSTALLATION 8 7 INSTALL THE CONNECTING PIPE 9 8 CONNECT THE DAIN PIPE 13 9 WIRING 15 10 TEST OPERATION...

Page 15: ...tions on system turn off main power switch of the unit Electrical shock could cause personal injury This unit shall be installed in accordance with national wiring regulations WARNING If the supply co...

Page 16: ...dealer INSTALLATION INFORMATION To install properly please read this installation manual at first The air conditioner must be installed by qualified persons When installing the indoor unit or its tubi...

Page 17: ...asp 1 3 Installation paper board 1 7 Tightening band 20 4 Bolt M6X12 4 8 Drain elbow 1 9 Seal ring 1 Protect Pipe Fittings Remote controller Its Frame 10 Wall conduit 1 12 Remote controller 1 11 Wall...

Page 18: ...m heaters 2 The outdoor unit There is enough room for installation and maintenance The air outlet and the air inlet are not impeded and can mot be reached by strong wind It must be a dry and well vent...

Page 19: ...o the hook holes in the installation board Drill four holes of M12mm 45 50mm deep at the selected positions on the ceiling Then embed the expansible hooks fittings Face the concave side of the install...

Page 20: ...ease first guarantee the flatness and horizontal of ceiling when installing it Refer to the A a mentioned above for others c Refer to the A c mentioned above for installation d Remove the installation...

Page 21: ...e that hooks of four corners are fixed well e Keep fastening the screws under the panel hooks until the thickness of the sponge between the body and the panel s outlet has been reduced to about 4 6mm...

Page 22: ...OOM FOR installation and maintenance Refer to chart 17 chart 18 If possible please remove the obstacles nearby to prevent the performance from being impeded by too little of air circulation The minimu...

Page 23: ...the surface of the flare pipe and the joint nuts with frozen oil and wrench it for 3 4 rounds with hands before fasten the flare nuts Refer to chart 19 Be sure to use two wrenches simultaneously when...

Page 24: ...ing materials when you buy the brass pipe 2 Locate The Pipes Drill a hole in the wall suitable just for the size of the wall conduit 50 53 71 series diameter is M90mm and 120 series diameter is M105mm...

Page 25: ...ely 4 Turn on the vacuum pump At the beginning of pumping loosen the maintenance terminator nut of stop value B a little to check whether the air comes in the sound of the pump changes and the indicat...

Page 26: ...ime 7 Disassemble the charge hose from the repair mouth of stop value A and fasten the unit Operate the stop valves Open the value stem until it reaches the limitator Do not open it any further Fasten...

Page 27: ...used by entered air To prevent water from flowing backwards into the air conditioner while the air conditioner stops please lean the drainpipe down toward outdoor outlet side at a degree of over 1 50...

Page 28: ...ain pump Check whether the water is discharged well a long of 1 min is allowed before discharging according to the length of the drain pipe and check whether water leaks from the joints CAUTIONS If th...

Page 29: ...n device having an air gap contact separation in all active conductors should incorporated in the fixed wiring according to the national wiring regulation 5 Be sure to locate the power wiring and the...

Page 30: ...e must be HO5VV K5G type and contain 3X4 mm2 leads b Three phase models See Figure 36 The main power supply cable must be HOVV K5G type and contain 5X2 5mm2 leads WARNING On unit with scroll type comp...

Page 31: ...rotected and isolated from any possible contact with water When the cable path runs through a wall or an acoustic ceiling it will be protected with fireproof tubing In addition the two units should be...

Page 32: ...m2 INDOOR OUTDOOR 3 CORE Cable 3X1 5mm2 3 CORE Cable YZW 300 500 3X1 5mm2 Note The cooling only type without the link listed by broken line KN 27 AIR CONDITIONER LINK CIRCUIT Chart 37 POWER 380V 50Hz...

Page 33: ...e 3X2 5mm2 POWER 220 240V 50Hz Chart 38 5 CORE Cable 5X2 5mm2 INDOOR OUTDOOR Note The cooling only type without the link listed by broken line KN 24 27 AIR CONDITIONER LINK CIRCUIT SZ000288 En 06 22 2...

Page 34: ...under the mode of COOLING with the remote controller and check the following points per the Owner s manual If there is any malfunction please resolve it as per chapter Troubles and Cause in the Owner...

Page 35: ...Part No 4527454 02 4527454 02 Cover 06 22 2004 5 08 PM 3...

Reviews: