
6-6
REFRIGERATION DIAGRAMS
Revision Y05-01
Service Manual - EMD Series
6.6
Additional Refrigerant Charge (R 22, R407C gr.)
10m
15m
25m
30m
50m
EMD 27
60
185
435
-
-
EMD 35
60
185
435
560
-
EMD 40
75
225
525
675
1275
EMD 45
75
225
525
675
1275
EMD 50
75
225
525
675
1275
EMD 60
100
300
700
900
1700
REFRIGERANT TUBING LENGTH (ONE WAY)
MODEL
MAXIMUM REFRIGARANT TUBING LENGTH
AND HEIGHT DIFFERENCE
LENGTH (m)
HEIGTH
(A)
DIFFERENCE (m)
EMD 27
25
10
EMD 35
30
10
EMD 40
50
25
EMD 45
50
25
EMD 50
50
25
EMD 60
50
25
MODEL
*
THE INDOOR UNIT CAN BE ABOVE OR BELOW THE OUTDOOR UNIT
.