PERFORMANCE DATA
5.4 WNG
12
DCI
5.4.1
Cooling Capacity Factors - Unit A,B,C or D
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC
]
OD COIL
ENTERING AIR DB
DATA
22/15
24/17
27/19
29/21
32/23
TEMPERATURE [ºC]
-10 - 20
(protection range)
TC
SC
PI
80 - 110 % of nominal
80 - 105 % of nominal
25 - 50 % of nominal
TC
0.97
1.03
1.09
1.16
1.22
25
SC
1.01
1.03
1.05
1.07
1.09
PI
0.79
0.80
0.82
0.83
0.85
TC
0.92
0.98
1.05
1.11
1.17
30
SC
0.98
1.00
1.03
1.05
1.07
PI
0.88
0.89
0.91
0.92
0.94
TC
0.87
0.94
1.00
1.06
1.13
35
SC
0.96
0.98
1.00
1.02
1.04
PI
0.97
0.99
1.00
1.02
1.03
TC
0.83
0.89
0.95
1.02
1.08
40
SC
0.93
0.95
0.97
1.00
1.02
PI
1.06
1.08
1.09
1.11
1.12
TC
0.77
0.83
0.90
0.96
1.02
46
SC
0.90
0.92
0.94
0.96
0.99
PI
1.17
1.19
1.20
1.22
1.23
LEGEND
TC
–
Total Cooling Capacity, kW
SC – Sensible
Capacity,
kW
PI
–
Power Input, kW
WB –
Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OD –
Outdoor
5.4.2 Capacity
Correction
Factors
io
27/19
22/15
24/17
29/21
32/23
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
Ca
p
a
c
it
y
Ra
t
20
25
30
35
40
45
50
Outdoor Temperature [deg C]
Revision
0
5-7