5-2
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-01
Service Manual - Delta DCI
5.1.3
Heating Capacity (kW) - Run Mode(Unit A or B)
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [
0
C]
OD COIL
ENTERING
AIR DB/WB
TEMPERATURE
[
0
C]
DATA
15
20
25
-15/-16
TC
1.78
1.66
1.53
PI
0.49
0.54
0.59
-10/-12
TC
1.98
1.86
1.73
PI
0.59
0.64
0.69
-7/-8
TC
2.14
2.01
1.89
PI
0.67
0.72
0.77
-1/-2
TC
2.21
2.09
1.96
PI
0.71
0.76
0.81
2/1
TC
2.26
2.14
2.01
PI
0.73
0.78
0.83
7/6
TC
32.92
2.80
2.68
PI
0.77
0.82
0.87
10/9
TC
3.09
2.96
2.84
PI
0.82
0.87
0.92
15/12
TC
3.25
3.12
3.00
PI
0.86
0.91
0.96
15-24
TC
85 - 105 % of nominal
(Protection Range)
PI
80 - 120 % of nominal
LEGEND
TC –
Total Cooling Capacity, kW
PI –
Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OD –
Outdoor
5.1.4
Capacity Correction Factors
Heating Capacity Ratio Vs. Outdoor Temperature
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
-15
-10
-5
0
5
10
15
Outdoor WB Temperature [deg C]
Ca
p
a
c
it
y
R
a
ti
o
n
Summary of Contents for DELTA 25