![Electra DELTA 22 Service Manual Download Page 32](http://html1.mh-extra.com/html/electra/delta-22/delta-22_service-manual_2378837032.webp)
5-18
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02
Service Manual - Delta DCI
5.6.6
Heating – Test Mode
Suction Pressure VS. Outdoor Temp.
300
400
500
600
700
800
900
1000
-15
-10
-5
0
5
10
15
Outdoor WB Temperature [ºC]
Su
c
ti
o
n
Pr
e
s
s
u
re
[
k
Pa
]
15 DB
20 DB
25 DB
Discharge Pressure VS. Outdoor Temp.
1500
1750
2000
2250
2500
2750
3000
3250
3500
3750
4000
-15
-10
-5
0
5
10
15
Outdoor WB Temperature[ºC]
D
is
c
h
a
rg
e P
res
su
re
[
k
P
a
]
15 DB
20 DB
25 DB