Fault description
2* 7
segments
LEDs blinking
Possible Reason
RUN COOL HEAT
Compressor overload
protection
H3
3
1. EEV connection problem or damaged
2. Refrigerant leakage
3. OLP damaged
Compressor overload
protection
H3
3
1. EEV connection problem or damaged
2. Refrigerant leakage
3. OLP damaged
IPM protection
H5
5
1. Abnormal power input voltage.
2. Compressor wiring mistake.
3. Liquid and gas valve are not open.
4. EEV damaged or not proper working
5. Poor heat exchange.
6. Over charged system.
PFC protection
HC
6
1. PFC module assembly problem.
2. Poor heat exchange of Heatsink
3. PFC reactor problem.
4. Abnormal power voltage
5. PFC circuit problem on PCB
Desynchronizing of
compressor
H7
7
1. Abnormal power input voltage.
2. Compressor wiring mistake.
3. Liquid and gas valve are not open.
4. EEV damaged or not proper working
5. Poor heat exchange.
6. Over charged system.
Compressor start-up failure
Lc
11
1. Compressor wiring mistake
2. Over charged system
3. System not balanced before compressor starting
4. Compressor problem
Compressor phase current
detection problem
U1
12
Phase current detection circuit for compressor has
problem.
DC over current
P5
15
1. Abnormal power input voltage.
2. Compressor wiring mistake.
3. Liquid and gas valve are not open.
4. EEV damaged or not proper working
5. Poor heat exchange.
6. Over charged system.
Charging malfunction of
capacitor
PU
17
1. Reactor open
2. Charging relay or other components damaged on
PCB.
HST failure
P7
18
1. Senor was broken or damaged
2. PCB temperature detection circuit has problem
HST over heating protection
P8
19
1. Insufficient attachment of IPM module to Heatsink
2. Outdoor PCB problem.
DC under voltage
PL
21
1. AC input voltage is too low
2. Reactor has problem
3. ODU PCB has problem
Lack Phase Protection of
Compressor
Ld
1. Compressor wiring problem
2. Compressor problem
3. IPM module problem or compressor current
detection circuit has problem
4. Compressor malfunction due to EEV problem
Summary of Contents for AWAU-VBZE218-H11
Page 17: ...Service Manual VBZE DCI 1 A 1 GB 6 1 PRESSURECURVES 6 PRESSURE CURVES...
Page 24: ...Service Manual VBZE DCI 1 A 1 GB WIRING DIAGRAM 9 5 9 6 Wiring connection between IDU and ODU...
Page 25: ...Service Manual VBZE DCI 1 A 1 GB REFRIGERATIONDIAGRAMS 10 1 10 REFRIGERATION DIAGRAMS...
Page 26: ...Service Manual VBZE DCI 1 A 1 GB 11 1 TUBINGCONNECTIONS 11 TUBING CONNECTIONS...
Page 57: ...Service Manual VBZE DCI 1 A 1 GB EXPLODED VIEW SPARE PART LIST 15 12 APPENDIX...
Page 58: ......