12.7.6.2 Deicing Protection Procedure
When starting deicing from Heat Mode, system will work as following:
1). Compressor stops. OFAN and RV will be OFF after 40s
3). Compressor starts and deicing time is counted. Compressor frequency will go to Deicing
Frequency.
12.7.6.3 Exiting Deicing
System will exit the deicing until OCT reaches to certain value (depends on OAT) or the deicing
time reaches 12 min as maximum.
12.7.7
Communication malfunction
Connected IDU number detection
If ODU does not receive correct signal from one IDU for 3min continuously, the ODU will take this
IDU as not connected one. But ODU will still send the broadcast to this IDU. If response were
received, then ODU will take it as connected.
12.7.8
IPM module protection
When the compressor starts, if there is over current or control voltage low for IPM module as some
abnormal results, IPM will detect module protection signal as the unit is on. Once the module
protective signal is detected, stop the unit with module protection immediately. If the module protection
is resumed and compressor has stopped for 3min, the unit will be allowed to operate.
If the module protection continuously occurs for 6 times
(the counter will be cleared after the
compressor has run for 7min)
, it can not resume running automatically and display malfunction, it
can resume by power reset.
12.7.9
HP switch protection
If the HP switch is opened for 3S continuously, the system will stop as protection
After the HP switch protection, if HP switch is resumed for continuous 6s, the system operating can
be resumed by power reset.
12.7.10
Module overheating protection
If the module temperature is higher than 95C, the unit will stop. If module temperature is lower than
95C, and compressor has stopped for 3min, the unit will resume operating.
If the unit stops as module overheating protection for 6 times
(the counter will be cleared after the
compressor has run for 7min)
, it can not resume running automatically and display malfunction, it can
resume by power reset.
Summary of Contents for AWAU-VBZE218-H11
Page 17: ...Service Manual VBZE DCI 1 A 1 GB 6 1 PRESSURECURVES 6 PRESSURE CURVES...
Page 24: ...Service Manual VBZE DCI 1 A 1 GB WIRING DIAGRAM 9 5 9 6 Wiring connection between IDU and ODU...
Page 25: ...Service Manual VBZE DCI 1 A 1 GB REFRIGERATIONDIAGRAMS 10 1 10 REFRIGERATION DIAGRAMS...
Page 26: ...Service Manual VBZE DCI 1 A 1 GB 11 1 TUBINGCONNECTIONS 11 TUBING CONNECTIONS...
Page 57: ...Service Manual VBZE DCI 1 A 1 GB EXPLODED VIEW SPARE PART LIST 15 12 APPENDIX...
Page 58: ......